Honeywell T8621C, T8621A, T8621DA, T8621D User Manual

T8621A,C,D, CHRONOTHERM III
FUEL SAVER THERMOSTATS
APPLICATION
These thermostats provide energy saving control for a 24 Vac heating/cooling system as indicated in Table 1, and are powered direct from the control transformer.
As long as thermostat is continuously powered, the thermostat will be compatible with any control system.
TABLE 1—THERMOSTAT MODELS.
STAGES SWITCHING
THERMOSTAT HEAT COOL SYSTEM FAN APPLICATION
T8621A 1 1 HEAT-AUTO-COOL-OFF ON-AUTO Single Stage T8621C 2 1 HEAT-AUTO-COOL-OFF ON-AUTO Multistage T8621D 2 2 HEAT-AUTO-COOL-OFF ON-AUTO Multistage
a
T8621D
a
SUPER TRADELINE model.
2 2 HEAT-OFF-COOL ON-AUTO Multistage
necessary. Cycle rates are adjustable for highest stage of heating.
12/24 hour clock conversion and °C/°F conversion is available on some models only.
INSTALLATION
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings on the product to make sure the product is suitable for your application.
3.Installer must be a trained, experienced service tech­nician.
4.Allow thermostat to warm to room temperature before operating.
5.After installation is complete, check out product op­eration as provided in these instructions.
CAUTION
Disconnect power supply to prevent electrical shock or equipment damage.
After wiring is complete, push excess wire back into the hole, and plug hole with nonhardening caulk, putty, or insulation to prevent drafts from affecting thermostat operation.
LOCATION
Install thermostat and subbase about 5 ft. [1.5 m] above the floor in an area with good air circulation at room temperature.
Do not install the thermostat where it may be affected by—
— drafts or dead spots behind doors, in corners, or
under cabinets. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas behind the thermostat,
such as an outside wall.
IF REPLACING AN EXISTING THERMOSTAT
Turn power to thermostat off at furnace or boiler. A two
transformer system may require turning off two switches or disconnects. Remove any existing wallplate or subbase from wall. Label or write down each wire color with the letter or number on the wiring terminal as the wire is removed, to avoid miswiring later.
IMPORTANT
IF NEW INSTALLATION
Run cable to a hole at the selected wall location, and pull about 3 in. [76 mm] of wire through the opening. Color­coded, 18 gauge thermostat cable with one conductor for each wiring terminal is recommended. Good service prac­tice recommends selecting cable with one or two more conductors than the immediate application requires.
MOUNTING SUBBASE
• The T8621 requires an additional conductor to transformer common to provide continuous 24 V power for thermostat operation.
• Set the system switch in the OFF position before mounting the subbase.
The subbase does not require leveling for proper opera-
tion, but for appearance only.
Remove thermostat from subbase (Fig. 1).
The subbase mounts directly onto the wall with the screws and anchors included in the package. If drywall construction, plastic anchors must be used; use the sub­base as a template, and with a pencil, mark the two mounting screw positions (Fig. 2). Use 3/16 in. bit to drill holes for anchors. Gently tap anchors into holes until they are flush to the wall surface. Thread wires through the center opening of the subbase. Then, mount the subbase using two screws provided. Gently tighten screws, level top surface of subbase, then securely tighten screws.
IMPORTANT
H
E A
T
A U
T O
C
O
O
L
O
F F
F A
N
O N
A U
T O
Fig. 1—Removing thermostat from subbase.
M844
C. H. Form Number 69-0330—3 Rev. 12-90 ©Honeywell Inc. 1990
WALL
WIRES THROUGH WALL OPENING
WALL ANCHORS (2)
MOUNTING HOLES
SUBBASE
MOUNTING SCREWS (2)
M846
Fig. 2—Mounting subbase on wall.
FOR STRAIGHT INSERTION – STRIP 5/16 in. (8 mm)
FOR WRAPAROUND – RESTRICT WIRING TO THIS AREA
FRONT VIEW OF
TERMINAL AREA
KEEP WIRING BELOW THIS SURFACE
CROSS-SECTIONAL VIEW OF
TERMINAL AREA
Fig. 3—Restrict wiring to recessed area surrounding
terminals.
WIRING
All wiring must comply with local electrical codes and
ordinances.
Disconnect power before wiring to prevent electrical
shock or equipment damage.
The shape of the terminal barrier permits insertion of straight or conventional wraparound wiring connections. Either method is acceptable.
Push excess wire back into the hole, and plug hole with nonhardening caulk, putty or insulation to prevent drafts from affecting thermostat operation.
STRIP 7/16 in. (11 mm)
TOP SURFACE OF SUBBASE
M847
Refer to Figs. 4-9 for typical hookups of subbase thermo-
stat. NOTE: Restrict all wiring to recessed area surrounding
terminals (Fig.3) to assure thermostat/subbase contact.
ADJUSTING CYCLE RATE
To custom-tailor the thermostats cycling performance to different types of heating equipment, cycle rate adjust­ment screws are provided on the back of the thermostat. Correct setting of these screws will provide optimum room temperature control.
NOTE: MOST APPLICATIONS WILL NOT REQUIRE A
CHANGE IN CYCLE RATE.
HEATING TRANSFORMER
R
2
HIGH LIMIT
SYSTEM SWITCH
HEAT AUTO COOL OFF
FAN SWITCH
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FOR SINGLE TRANSFORMER SYSTEM JUMPER R AND RC.
2
3
NOMINAL 24 Vac POWER MUST BE PRESENT BETWEEN R AND C FOR THERMOSTAT OPERATION.
Fig. 4—T8621A 1-stage heat/1-stage cool thermostat
with HEAT-AUTO-COOL-OFF system and AUTO-ON fan switching.
AUTO ON
POWER SUPPLY
3
C
W1
Y1
G
2
RC
COOLING TRANSFORMER
HEAT RELAY
COOLING CONTACTOR
FAN RELAY
H
C
L1 (HOT)
L2
L1 (HOT)
L2
M1574
1
1
2
HEATING TRANSFORMER
R
2
HIGH LIMIT
HIGH LIMIT
SYSTEM SWITCH
FAN SWITCH
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FOR SINGLE TRANSFORMER SYSTEM JUMPER R AND RC.
3
NOMINAL 24 Vac POWER MUST BE PRESENT BETWEEN R AND C FOR THERMOSTAT OPERATION.
HEAT
AUTO COOL OFF
AUTO ON
POWER SUPPLY
3
C
W1
W2
Y2
Y1
G
2
RC
COOLING TRANSFORMER
HEAT RELAY 1
HEAT RELAY 2
COOLING CONTACTOR 2
COOLING CONTACTOR 1
FAN RELAY
H1
H2
C2
C1
L1 (HOT)
L2
L1 (HOT)
L2
1
M1573
1
SYSTEM TRANSFORMER
R
POWER
HIGH
SUPPLY
LIMIT
HIGH LIMIT
SYSTEM SWITCH
HEAT
AUTO
COOL
OFF
C1
FAN SWITCH
AUTO
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
ADD RELAY (SPDT) TO ACCOMMODATE COOLING CHANGEOVER.
3
T8621D ONLY.
SET CYCLE RATE TO HOT WATER SETTING (3 cph).
NOTE:
THERMOSTAT DOES NOT PROVIDE MINIMUM OFF TIME IN HEATING.
C
2
H1
H2
C2
ON
RELAY K
W1
W2
COMPRESSOR CONTACTOR
3
Y2
Y1
FAN RELAY
G
RC
L1 (HOT) L2
1
K
COOLING CHANGE­OVER
M1575
Fig. 5T8621C,D 2-stage heat/2-stage cool thermostat
with HEAT-AUTO-COOL-OFF system and AUTO-ON fan switching. For T8621C, delete second cooling stage.
Fig. 6T8621C,D single-stage heat pump thermostats
with cooling changeover. HEAT-AUTO-COOL­OFF system and AUTO-ON fan switching.
3 69-0330—3
SYSTEM TRANSFORMER
R
POWER SUPPLY
HIGH LIMIT
HIGH LIMIT
SYSTEM SWITCH
HEAT
AUTO COOL
OFF
C1
FAN SWITCH
AUTO
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
T8621D ONLY. NOTE:
SET CYCLE RATE TO HOT WATER SETTING (3 cph). THERMOSTAT DOES NOT PROVIDE MINIMUM OFF TIME IN HEATING.
C
HEATING
H1
H2
C2
ON
CHANGEOVER
W1
COMPRESSOR CONTACTOR
W2
2
Y2
Y1
FAN RELAY
G
RC
L1 (HOT) L2
1
M1576
HEATING TRANSFORMER
R
4
POWER
C
COOL 1
HIGH LIMIT
SUPPLY
COOL 2
HEAT 1
HEAT 2
W1
W2
B
HEATING DAMPER OR CHANGEOVER RELAY
COOLING DAMPER OR CHANGEOVER RELAY
O
Y2
Y1
G
3
RC
COOLING TRANSFORMER
HIGH LIMIT
FAN OPERATION SWITCH
3
ELECTRIC
2
NON­ELECTRIC
SYSTEM SWITCH
HEAT
OFF
COOL
FAN SWITCH
AUTO
ON
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
2
FOR GAS OR OIL APPLICATIONS OR ELECTRIC HEAT APPLICATIONS WHERE THE FAN OPERATION IS CONTROLLED INDEPENDENTLY OF THE THERMOSTAT (AUTO FAN OPERATES WITH Y1 ONLY). TWO TRANSFORMERS MAY BE USED. SET SWITCH TO NONELECTRIC POSITION.
FOR ELECTRIC HEAT APPLICATIONS (AUTO FAN OPERATES
3
WITH W1 AND Y1), USE ONLY ONE TRANSFORMER; JUMPER R AND RC. SET SWITCH TO ELECTRIC POSITION.
4
NOMINAL 24 VAC POWER MUST BE PRESENT BETWEEN R AND C FOR THERMOSTAT OPERATION.
L1 (HOT)
1
STAGE 1 HEAT RELAY
STAGE 2 HEAT RELAY
STAGE 2 COOLING RELAY
STAGE 1 COOLING RELAY
FAN RELAY
1
L1 (HOT)
M13444
L2
L2
Fig. 7T8621C,D single-stage heat pump thermostats
with heating changeover. HEAT-AUTO-COOL­OFF system and AUTO-ON fan switching.
Fig. 8T8621D 2-stage heat/2-stage cool manual
changeover thermostat with auto fan on heat and cool; convertible to auto fan on cool only. HEAT-OFF-COOL system and AUTO-ON fan switching.
4
SYSTEM TRANSFORMER
R
3
HIGH LIMIT
FAN OPERATION SWITCH
2
ELECTRIC
NON-ELECTRIC
SYSTEM SWITCH
HEAT
OFF
COOL
FAN SWITCH
AUTO
ON
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FAN OPERATION SWITCH MAY BE IN EITHER POSITION. NOMINAL 24 VAC POWER MUST BE PRESENT BETWEEN R AND C
3
FOR THERMOSTAT OPERATION.
POWER SUPPLY
HIGH LIMIT
HEAT 1
HEAT 2
COOL 1 COOL 2
C
W1
W2
B
O
Y2
Y1
G
RC
L1 (HOT)
1
HEATING CHANGEOVER RELAY
COOLING CHANGEOVER RELAY
COMPRESSOR CONTACTOR
FAN RELAY
M1546A
FAN OPERATION OPTION SWITCH
The SUPER TRADELINE model includes a fan opera­tion option switch on the subbase, visible before the ther-
L2
mostat is mounted on the subbase. The switch should be in electric heat position for electric heating systems that do not have independent fan control.
INSTALLING BATTERIES
Three AAA alkaline batteries are provided as backup to prevent program loss in case of power outage. Batteries are included with thermostat. Install batteries in back of thermo­stat as shown in Fig. 11.
Without battery backup, the program will remain about 30 seconds in event of power loss.
TO 1 TURN
IN IN
IN
TO 1 TURN
IMPORTANT
1B
PER HOUR
OUT 1/2
IN
OUT 1/2
CYCLES
1
3
6
9
1A 2A 2B
TIME/TEMP
DISPLAY
1B
24 HR
12 HR
o
o
1
2B
2A
IN
OUT 1/2
TO 1 TURN
C
F
IN
OUT 1/2
TO 1 TURN
M311A
When batteries are first installed, the display will flash
1:00 PM and 32° or 0°. The temperature display will
stay at 32° or 0° until the thermostat is powered from
the system wiring.
SYSTEM
1A
OUT 1/2
GRAVITY
TO 1 TURN
AIR/WATER
HOT
OUT 1/2
WATER
TO 1 TURN
GAS/OIL
(FACTORY SETTING)
WARM AIR ELECTRIC
WARM AIR
1 SCREWS 2A, 2B ONLY AVAILABLE ON SOME MODELS.
Fig. 10Cycle rate adjustment.
Fig. 9T8621D single-stage manual changeover heat
pump thermostat. HEAT-OFF-COOL system and AUTO-ON fan switching.
The room air temperature will normally vary slightly from the comfort temperature setting with the cycling of the furnace or air conditioner.
The heating cycle rate of this thermostat is factory-set for gas/oil warm air heating. The cooling cycle rate cannot be adjusted. The heating cycle rate can be adjusted by turning one or both cycle rate adjustment screws located on the back of the thermostat. In multistage heat systems, the cycle rate adjustment applies to stage 2 only; stage 1 is fixed. See Fig. 10.
TIME/TEMPERATURE CONVERSION (SOME MODELS)
The display readout may be converted between 12 and 24 hour clock or °C and °F using screws 2A and 2B as indicated in Fig. 10.
BATTERY PLACEMENT (NOTE CORRECT PLUS AND MINUS DIRECTION)
M372A
Fig. 11Battery placement.
5 69-0330—3
When the batteries are low, the display will flash REPL BAT. The building owner will have 20-30 seconds to install new batteries after removing old batteries from thermostat. After 20-30 seconds, it will be necessary to reprogram. REPL BAT indication will disappear when ther­mostat is mounted back on the subbase.
If batteries are completely dead, the display will go blank. After replacing the battery in this case, reprogram­ming will be necessary.
POWER OUTAGES
Backup batteries will hold the programming and keep
the display on during most power outages. Once the power is restored, the system will resume normal operation.
If the display goes off when power is lost, either the backup batteries need to be replaced or are not installed. When power is restored, the display will flash 1:00 PM to remind you to reprogram.
MOUNTING THE THERMOSTAT
Hang the thermostat on the tabs at the top of the base (Fig. 12a). Swing down and press on lower edge until thermostat snaps in place (Fig. 12b). Open cover, and tighten the captive mounting screws (Fig. 12c).
A.
N
A
F
TO
U
A
N
O
F
F
O
L
O
O
C
O
T
U
A
T
A
E
H
C.
P
S
E
T
P
R
E
S
E
N
T
D
A
Y
/T
IM
E
H
O
L
D
T
E
M
P
H
E
Fig. 12Mounting thermostat on subbase.
SETTING DAY AND TIME
Restore 24 V power to the thermostat. When power is applied to the thermostat, the display will read 1:00 PM and room temperature. It will go off for a few seconds, then begin to flash on and off. Set present day and time.
DAY key advances the display one day.
SET
PRESENT DAY/TIME
Press .
DAY
Press to set the current day. Each press of the
Press TIME or to set the current time.
AHEAD
BACK
A
MON
MORNIMG
R
U
N
R
O
G
R
A
M
C
O
P
Y
D
A
Y
P
E
R
IO
D
F
R
O
M
S
E
T
C
A
N
C
E
L
C
O
P
Y
A
T
/C
O
O
L
P
E
R
IO
D
T
O
B.
SYSTEM
AM
ROOM
MON
MORNIMG
HEAT ON
AU
T
O
SYSTEM
M
ROOM
HEAT ON
T
E
M
P
E
R
A
T
U
R
E
P
R
E
S
E
N
T
S
E
T
T
IN
G
T
IM
E
S
K
IP
N
E
X
T
A
H
E
A
D
W
A
R
M
E
R
P
E
R
IO
D
C
H
A
N
G
E
B
A
C
K
C
O
O
LE
R
T
O
L
A
S
T
P
E
R
IO
D
M843
If the display will not come on check mounting of thermostat to subbase. If loose or
misaligned, remove thermostat and reinstall on the subbase, making sure it is firmly attached.
check to see that heat or cool system power is on.check voltage between R and C; should be 24 to 30
Vac.
CHECKOUT
HEATING
NOTE: When heating setting is changed, thermostat will
wait up to 5 minutes before turning on the heating
equipment. This delay protects the compressor.
Move the system switch to HEAT and the fan switch to AUTO. Press WARMER key until the setting is about 10° F [6° C] above room temperature. Heating should start (both stages if multistage), and the fan should run (may be a short
delay on gas or oil forced air systems). Press COOLER key until the setting is about 10° F [6° C] below room tempera­ture. The heating equipment should shut off, followed by the fan.
NOTE: On an AUTO changeover thermostat, the cooling
temperature must be set at least 3° F [2° C] above the heating temperature, or display will flash.
6
COOLING
CAUTION
Do not operate cooling if outdoor temperature is
below 50° F [10° C]. Refer to manufacturers recom-
mendations. NOTE: When cooling setting is changed, thermostat will
wait up to 5 minutes before turning on the cooling
equipment. This delay protects the compressor.
Move the system switch to COOL and the fan switch to AUTO. Press COOLER key until the setting is about 10° F [6° C] below room temperature. The cooling equipment and fan should start. Press WARMER key until the setting is about 10° F [6° C] above room temperature. The cooling equipment and fan should stop.
NOTE: On an AUTO changeover thermostat, the heating
temperature must be set at least 3° F [2° C] below the
cooling temperature, or display will flash.
FAN
Move the system switch to OFF, and the fan switch to ON. The fan should run continuously. When the fan switch is in the AUTO position, fan operates directly with the cooling system, and also with heating system on some models.
INSTALLER SELF-TEST (optional)
AC power must be present on thermostat to con­duct self-test. Relays will not toggle, codes will not be present and thermostat will not manually exit self-test without ac power.
Five-minute time delay on cooling does not func­tion during self-test.
Perform the following test as a check of all thermostat functions. If thermostat does not respond as indicated, thermostat must be replaced.
1. Press AHEAD and BACK keys at the same time. While holding keys down, all segments of the display should be on (Fig. 13).
MON
SUN MORNING
Fig. 13All segments on display.
2.Set system switch to OFF. Press AHEAD and BACK and PRESENT SETTING keys at the same time to enter self-test.
3.Press each key as listed below, and look for response listed as key is held down and released.
IMPORTANT
REPL
AM
BAT
TUE WED THU FRI SAT TEMPORARY
PM
SET PT
ROOM
OUTDOOR
MIDDAY EVENING NIGHT COOL ON HEAT ON
M525A
SYSTEM PRESS LOOK FOR THIS RESPONSE SWITCH THIS KEY KEY POSITION KEY DOWN RELEASED
OFF 03 Blank
COOL or 15 1st stage cooling, AUTO (with fan and SYSTEM fan in AUTO) LED on.
NOTE: If single-stage cooling system, press key twice
instead of 4 times; once to turn cooling, fan and SYS­TEM LED on, second time to turn off.
OFF 06 Blank
(CHECK 12 See note A EACH POSITION)
OFF 08 Blank
HEAT or 14 1st stage heating and AUTO 1 SYSTEM LED on.
NOTE: If single-stage heating system, press key twice
instead of 4 times; once to turn heating and SYSTEM LED on, second time to turn off.
OFF 10 Blank
1 For electric heat fan operationThe fan will operate
with the heating system when fan switch is in AUTO.
A HEAT displayed when system switch is in HEAT,
COOL when in COOL, HEAT and COOL when in AUTO, neither when in OFF. Also, a four-digit code is displayed, with each digit explained below.
CHANGE
TO LAST
PERIOD
SKIP
NEXT
PERIOD
PRESENT SETTING
PRESENT
SETTING
PRESENT SETTING
PRESENT SETTING
PRESENT SETTING
WARMER
COOLER
AHEAD
BACK
COPY
FROM
COPY
TO
PERIOD
CANCEL PERIOD
DAY
SET
HEAT/COOL
SET
PRESENT DAY/TIME
SET
PRESENT DAY/TIME
SET
PRESENT DAY/TIME
SET
PRESENT DAY/TIME
SET
PRESENT DAY/TIME
HOLD
TEMP
RUN
PROGRAM
07 Blank
15 Blank
15 2nd stage cooling
also on.
15 2nd stage cooling off.
15 1st stage cooling, fan
and SYSTEM LED off.
02 Blank
05 Blank
04 Blank
01 Blank
00 Blank
13 Microprocessor mask
no. and revision no.
09 Blank
14 Blank
14 2nd stage heating
also on.
14 2nd stage heating off.
14 1st stage heating and
SYSTEM LED off.
11 Normal operating
display.
7 69-0330—3
CYCLE RATE SETTING
FIRST stage 1 on 1-heat models,
DIGIT stage 2 on 2-heat models)
(CPH at 50% on time for
THIRD MANUAL OR AUTO SWITCH
DIGIT CHANGEOVER POSITION
SYSTEM
0 Manual HEAT or OFF 1 Auto HEAT or OFF 3 Auto AUTO 4 Manual COOL 5 Auto COOL
M13443
SECOND STAGES OF
DIGIT HEAT COOL
FOURTH CLOCK SWITCH
DIGIT DEGREES (HRS) POSITION
0 F 12 COOL, AUTO 1 F 24 COOL, AUTO
SYSTEM
or OFF
or OFF 2 F 12 HEAT 3 F 24 HEAT 4 C 12 COOL, AUTO
5 C 24 COOL, AUTO
or OFF
or OFF 6 C 12 HEAT 7 C 24 HEAT
This equipment is a Class B digital apparatus which complies with Canadian Radio Interference Regulations, CRC c. 1374.
U.S.A.: 1885 Douglas Drive N. Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Golden Valley, MN 55422-4386 Spain, Taiwan, United Kingdom, U.S.A. CANADA: 740 Ellesmere Road Scarborough, Ontario M1P 2V9 PRINTED IN TAIWAN R.O.C.
Honeywell Inc. International Sales Offices in all principal cities of the world. Manufacturing in
QUALITY IS KEY
Loading...