Honeywell T8621C, T8621A, T8621DA, T8621D User Manual

T8621A,C,D, CHRONOTHERM III
FUEL SAVER THERMOSTATS
APPLICATION
These thermostats provide energy saving control for a 24 Vac heating/cooling system as indicated in Table 1, and are powered direct from the control transformer.
As long as thermostat is continuously powered, the thermostat will be compatible with any control system.
TABLE 1—THERMOSTAT MODELS.
STAGES SWITCHING
THERMOSTAT HEAT COOL SYSTEM FAN APPLICATION
T8621A 1 1 HEAT-AUTO-COOL-OFF ON-AUTO Single Stage T8621C 2 1 HEAT-AUTO-COOL-OFF ON-AUTO Multistage T8621D 2 2 HEAT-AUTO-COOL-OFF ON-AUTO Multistage
a
T8621D
a
SUPER TRADELINE model.
2 2 HEAT-OFF-COOL ON-AUTO Multistage
necessary. Cycle rates are adjustable for highest stage of heating.
12/24 hour clock conversion and °C/°F conversion is available on some models only.
INSTALLATION
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings on the product to make sure the product is suitable for your application.
3.Installer must be a trained, experienced service tech­nician.
4.Allow thermostat to warm to room temperature before operating.
5.After installation is complete, check out product op­eration as provided in these instructions.
CAUTION
Disconnect power supply to prevent electrical shock or equipment damage.
After wiring is complete, push excess wire back into the hole, and plug hole with nonhardening caulk, putty, or insulation to prevent drafts from affecting thermostat operation.
LOCATION
Install thermostat and subbase about 5 ft. [1.5 m] above the floor in an area with good air circulation at room temperature.
Do not install the thermostat where it may be affected by—
— drafts or dead spots behind doors, in corners, or
under cabinets. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas behind the thermostat,
such as an outside wall.
IF REPLACING AN EXISTING THERMOSTAT
Turn power to thermostat off at furnace or boiler. A two
transformer system may require turning off two switches or disconnects. Remove any existing wallplate or subbase from wall. Label or write down each wire color with the letter or number on the wiring terminal as the wire is removed, to avoid miswiring later.
IMPORTANT
IF NEW INSTALLATION
Run cable to a hole at the selected wall location, and pull about 3 in. [76 mm] of wire through the opening. Color­coded, 18 gauge thermostat cable with one conductor for each wiring terminal is recommended. Good service prac­tice recommends selecting cable with one or two more conductors than the immediate application requires.
MOUNTING SUBBASE
• The T8621 requires an additional conductor to transformer common to provide continuous 24 V power for thermostat operation.
• Set the system switch in the OFF position before mounting the subbase.
The subbase does not require leveling for proper opera-
tion, but for appearance only.
Remove thermostat from subbase (Fig. 1).
The subbase mounts directly onto the wall with the screws and anchors included in the package. If drywall construction, plastic anchors must be used; use the sub­base as a template, and with a pencil, mark the two mounting screw positions (Fig. 2). Use 3/16 in. bit to drill holes for anchors. Gently tap anchors into holes until they are flush to the wall surface. Thread wires through the center opening of the subbase. Then, mount the subbase using two screws provided. Gently tighten screws, level top surface of subbase, then securely tighten screws.
IMPORTANT
H
E A
T
A U
T O
C
O
O
L
O
F F
F A
N
O N
A U
T O
Fig. 1—Removing thermostat from subbase.
M844
C. H. Form Number 69-0330—3 Rev. 12-90 ©Honeywell Inc. 1990
WALL
WIRES THROUGH WALL OPENING
WALL ANCHORS (2)
MOUNTING HOLES
SUBBASE
MOUNTING SCREWS (2)
M846
Fig. 2—Mounting subbase on wall.
FOR STRAIGHT INSERTION – STRIP 5/16 in. (8 mm)
FOR WRAPAROUND – RESTRICT WIRING TO THIS AREA
FRONT VIEW OF
TERMINAL AREA
KEEP WIRING BELOW THIS SURFACE
CROSS-SECTIONAL VIEW OF
TERMINAL AREA
Fig. 3—Restrict wiring to recessed area surrounding
terminals.
WIRING
All wiring must comply with local electrical codes and
ordinances.
Disconnect power before wiring to prevent electrical
shock or equipment damage.
The shape of the terminal barrier permits insertion of straight or conventional wraparound wiring connections. Either method is acceptable.
Push excess wire back into the hole, and plug hole with nonhardening caulk, putty or insulation to prevent drafts from affecting thermostat operation.
STRIP 7/16 in. (11 mm)
TOP SURFACE OF SUBBASE
M847
Refer to Figs. 4-9 for typical hookups of subbase thermo-
stat. NOTE: Restrict all wiring to recessed area surrounding
terminals (Fig.3) to assure thermostat/subbase contact.
ADJUSTING CYCLE RATE
To custom-tailor the thermostats cycling performance to different types of heating equipment, cycle rate adjust­ment screws are provided on the back of the thermostat. Correct setting of these screws will provide optimum room temperature control.
NOTE: MOST APPLICATIONS WILL NOT REQUIRE A
CHANGE IN CYCLE RATE.
HEATING TRANSFORMER
R
2
HIGH LIMIT
SYSTEM SWITCH
HEAT AUTO COOL OFF
FAN SWITCH
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FOR SINGLE TRANSFORMER SYSTEM JUMPER R AND RC.
2
3
NOMINAL 24 Vac POWER MUST BE PRESENT BETWEEN R AND C FOR THERMOSTAT OPERATION.
Fig. 4—T8621A 1-stage heat/1-stage cool thermostat
with HEAT-AUTO-COOL-OFF system and AUTO-ON fan switching.
AUTO ON
POWER SUPPLY
3
C
W1
Y1
G
2
RC
COOLING TRANSFORMER
HEAT RELAY
COOLING CONTACTOR
FAN RELAY
H
C
L1 (HOT)
L2
L1 (HOT)
L2
M1574
1
1
2
HEATING TRANSFORMER
R
2
HIGH LIMIT
HIGH LIMIT
SYSTEM SWITCH
FAN SWITCH
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FOR SINGLE TRANSFORMER SYSTEM JUMPER R AND RC.
3
NOMINAL 24 Vac POWER MUST BE PRESENT BETWEEN R AND C FOR THERMOSTAT OPERATION.
HEAT
AUTO COOL OFF
AUTO ON
POWER SUPPLY
3
C
W1
W2
Y2
Y1
G
2
RC
COOLING TRANSFORMER
HEAT RELAY 1
HEAT RELAY 2
COOLING CONTACTOR 2
COOLING CONTACTOR 1
FAN RELAY
H1
H2
C2
C1
L1 (HOT)
L2
L1 (HOT)
L2
1
M1573
1
SYSTEM TRANSFORMER
R
POWER
HIGH
SUPPLY
LIMIT
HIGH LIMIT
SYSTEM SWITCH
HEAT
AUTO
COOL
OFF
C1
FAN SWITCH
AUTO
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
ADD RELAY (SPDT) TO ACCOMMODATE COOLING CHANGEOVER.
3
T8621D ONLY.
SET CYCLE RATE TO HOT WATER SETTING (3 cph).
NOTE:
THERMOSTAT DOES NOT PROVIDE MINIMUM OFF TIME IN HEATING.
C
2
H1
H2
C2
ON
RELAY K
W1
W2
COMPRESSOR CONTACTOR
3
Y2
Y1
FAN RELAY
G
RC
L1 (HOT) L2
1
K
COOLING CHANGE­OVER
M1575
Fig. 5T8621C,D 2-stage heat/2-stage cool thermostat
with HEAT-AUTO-COOL-OFF system and AUTO-ON fan switching. For T8621C, delete second cooling stage.
Fig. 6T8621C,D single-stage heat pump thermostats
with cooling changeover. HEAT-AUTO-COOL­OFF system and AUTO-ON fan switching.
3 69-0330—3
Loading...
+ 5 hidden pages