Honeywell T8611G User Manual

APPLICATION

T8611G Chronotherm® IV
Deluxe Programmable
INSTALLATION INSTRUCTIONS
The T8611G Chronotherm® IV Deluxe Programmable Heat Pump Thermostats provides electronic control of 24 Vac single-zone heat pump systems.
Table 1. Description of T8611 Thermostats.
T8611 Changeover System Selection Fan Selection Comments
G Automatic Em Heat-Heat-Off-Cool-Auto On-Auto System and fan selections are done by keyboard.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Refer to Table 1 for a general description of the thermostat. All T8611 thermostats require a common wire to supply power.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance only). The thermostat will function correctly even when not level.
2. Use a pencil to mark the mounting holes. See Fig.
2.
3. Remove the wallplate from the wall and drill two 3/16 inch (76 mm) holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch (5.56 mm) holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
® U.S. Registered Trademark Copyright © 2002 Honeywell • • All Rights Reserved
69-1406-1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
THERMOSTAT
YES
NO
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.
WIRES THROUGH WALL
WALL ANCHORS (2)
WALL
O/B
Y1 G E
C
NO
FAN RELAY
COOLING OR HEATING CHANGEOVER VALVE
COMPRESSOR CONTACTOR
M10106
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 3. Typical hookup of T8611G
in a heat pump system.
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
EM. HT. RELAY
W2
HEAT RELAY 2
Fig. 4. Correct wiring technique.
RW1
EQUIPMENT
MONITOR 2
EQUIPMENT
MONITOR 1
HEAT RELAY 1
TRANSFORMER
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
X2 LX1
OT OT
OUTDOOR SENSOR
1
L1 (HOT)
L2
M11311A
M4826
MOUNTING HOLES
MOUNTING SCREWS
M15044
Fig. 2. Mounting the wallplate.

WIRING

All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typical hookup. A letter code is located near each terminal for identification.
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 4.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
69-1406—1 2

Mounting Thermostat

1. Engage tabs at the top of the thermostat and wall­plate. See Fig. 5.
2. Press lower edge of case to close and latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove top last.
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
Fig. 5. Mounting thermostat on wallplate.
M14628
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
A
A

Using Thermostat Keys (Fig. 6)

The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
• configure Installer Setup,
• check System-Test,
• display outdoor temperature (select models),
• set the system operation,
• set the fan operation.
NOTE: Always press the keys with your fingertip or sim-
ilar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.

SETTINGS

System and Fan Settings
The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 7. The fan settings can be set for each program period individually. The system selection is for all the program periods.
INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP
ND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
ENTER INDEFINITE OR TIMED HOLD MODE
SET CURRENT OR PROGRAM DAY
CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME
SET WAKE TIMES AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
Fig. 6. T8611G key locations and descriptions.
SET LEAVE TIMES AND SETPOINTS
Time Set Program
Wake
Heat/Cool
Settings
Copy
System settings control the thermostat operation:
Em Heat: Emergency heat relay is on continuously.
Thermostat cycles highest stage of heat. Cooling system is off. Compressor is de-energized.
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between
heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan:
On: Fan operates continuously. Auto: Fan operates with equipment.

LED Indication

Two LED indicators are located in the upper right of the thermostat. They indicate when a Check or Fail signal is sent to the thermostat from the system. See Fig. 8.
SET RETURN TIMES AND SETPOINTS
Leave
Return Sleep
System Fan
DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE
SET SLEEP TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION
CHANGE BETWEEN HEATING AND COOLING SETPOINTS
M14624
Time Set Program
Run
Set Current
Program
Day/Time
Hold Temp
Day
Daylight
Time
Leave
Wake
Heat/Cool
Settings
Copy
Return
System Fan
Sleep
Fig. 7. Thermostat System and Fan key locations.
M14625
System
Fan
TWO LED INDICATORS
M10675
Fig. 8. LEDs location.
3 69-1406—1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Outdoor
Fan
eat
On
o
Off
Cool
o

Temperature Settings

Refer to Table 2 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. See Owner’s Guide, form number 69-0940, for complete instructions on changing the program.
Table 2. Default Program Settings.
Period Time
Wake 6:45 AM 20°C
Leave 8:45 AM 4.5°C
Return 5:00 PM 20°C
Sleep 10:00 PM 4.5°C
Heat
Setpoint
(68°F)
(40°F)
(68°F)
(40°F)
Cool
Setpoint
25°C (77°F)
37°C (99°F)
25°C (77°F)
37°C (99°F)
Setting
Auto
Auto
Auto
Auto
Fan

INSTALLER SETUP

NOTE: For most applications, the thermostat factory-
settings will not need to be changed. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer System Test section.
The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, changeover and outdoor temperature display. Installer Setup numbers are listed in Table 3. The table includes all the configuration options and the factory-settings for the T8611.
A combination of key presses is required to use the Installer Setup feature: — To enter the installer setup, press and hold the
information i key with the increase ! and decrease " keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 9 and 10.
— To advance to the next Installer Setup, press the
Time key.
— To change a setting, use the increase ! or decrease
" key.
— To scroll the Installer Setup numbers backward, press
the Time key.
— To exit the Installer Setup, press Run Program.
Wait
Recovery Hold for
Filter
Em Ht
Tue Wed Thu Fri Sat Sun
Mon Wake Leave Return Sleep
Set Day/TimeSet Program
Aux Ht
Days
AM
PM
Temporary Setting
Room
Repl Batt
DST
Heat
Cool
Em H
Aut
Aut
M14559
Fig. 9. Display of all LCD segments.
INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 3)
Fig. 10. Display of Installer Setup
number and setting.
IMPORTANT
Only configurable numbers are shown on the device. Example: If thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 3 factory-settings and mark any desired changes in the Actual Setting column. When Installer Setup is com­plete, review the settings to confirm that they match the system.
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 3)
M14618
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup
Number (Press
Time key to
change)
Factory Setting
Other Choices
(Press ! or " key to change)
Not Used. 1 thru 4
Heating cycle rate.
5 6 Stage 2 1, 6 or 9 1—1 cph
6—6 cph used for last stage
of heat pump systems
9—9 cph used for electric
heat
6 (Not used)
7 6 Emergency heat 3, 6 or 9
Not Used. 8 thru 11
System setting adjustment
69-1406—1 4
12 1 Manual
changeover
0 or 2 0—Auto changeover
2—Fixed auto changeover
Actual
SettingDisplay Description Display Description
Loading...
+ 8 hidden pages