GAutomaticEm Heat-Heat-Off-Cool-Auto On-AutoSystem and fan selections are done by keyboard.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Refer to Table 1 for a general description of the
thermostat. All T8611 thermostats require a common wire
to supply power.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall
or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
Position wallplate horizontally on the wall or on a
2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat will function correctly even
when not level.
2. Use a pencil to mark the mounting holes. See Fig.
2.
3. Remove the wallplate from the wall and drill two
3/16 inch (76 mm) holes in the wall (if drywall) as
marked. For firmer material such as plaster, drill
two 7/32 inch (5.56 mm) holes. Gently tap anchors
(provided) into the drilled holes until flush with the
wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
4. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
THERMOSTAT
YES
NO
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.
WIRES
THROUGH WALL
WALL
ANCHORS (2)
WALL
O/B
Y1 GE
C
NO
FAN
RELAY
COOLING OR
HEATING
CHANGEOVER
VALVE
COMPRESSOR
CONTACTOR
M10106
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
Fig. 3. Typical hookup of T8611G
in a heat pump system.
FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).
EM. HT.
RELAY
W2
HEAT
RELAY
2
Fig. 4. Correct wiring technique.
RW1
EQUIPMENT
MONITOR 2
EQUIPMENT
MONITOR 1
HEAT
RELAY
1
TRANSFORMER
FOR STRAIGHT INSERTION
STRIP 5/16 IN. (8 MM).
X2 LX1
OT OT
OUTDOOR
SENSOR
1
L1
(HOT)
L2
M11311A
M4826
MOUNTING
HOLES
MOUNTING
SCREWS
M15044
Fig. 2. Mounting the wallplate.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 for typical hookup. A letter
code is located near each terminal for identification.
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power before wiring.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 4.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for
proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
69-1406—12
Mounting Thermostat
1. Engage tabs at the top of the thermostat and wallplate. See Fig. 5.
2. Press lower edge of case to close and latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove top
last.
A.
ENGAGE TABS
AT TOP OF
THERMOSTAT
AND WALLPLATE.
B.
PRESS LOWER
EDGE OF CASE
TO LATCH.
Fig. 5. Mounting thermostat on wallplate.
M14628
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
A
A
Using Thermostat Keys (Fig. 6)
The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
• configure Installer Setup,
• check System-Test,
• display outdoor temperature (select models),
• set the system operation,
• set the fan operation.
NOTE: Always press the keys with your fingertip or sim-
ilar blunt tool. Sharp instruments like a pen or
pencil point can damage the keyboard.
SETTINGS
System and Fan Settings
The system default setting is Heat and the fan default
setting is Auto. Use the System and Fan keys to change
the settings. See Fig. 7. The fan settings can be set for
each program period individually. The system selection is
for all the program periods.
INCREASE TIME SETTING
OR SCROLL FORWARD
THROUGH INSTALLER SETUP
ND SYSTEM TEST
SET CURRENT
DAY AND TIME
RETURN TO
NORMAL
OPERATIONS
ENTER
INDEFINITE
OR TIMED
HOLD MODE
SET CURRENT OR
PROGRAM DAY
CHANGE BETWEEN
DAYLIGHT SAVINGS
AND STANDARD TIME
SET WAKE TIMES
AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED
DAY TO ANOTHER DAY
Fig. 6. T8611G key locations and descriptions.
SET LEAVE TIMES
AND SETPOINTS
TimeSet Program
Wake
Heat/Cool
Settings
Copy
System settings control the thermostat operation:
Em Heat: Emergency heat relay is on continuously.
Thermostat cycles highest stage of heat. Cooling
system is off. Compressor is de-energized.
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between
heating and cooling operation, depending on the
indoor temperature.
Fan settings control the system fan:
On: Fan operates continuously.
Auto: Fan operates with equipment.
LED Indication
Two LED indicators are located in the upper right of the
thermostat. They indicate when a Check or Fail signal is
sent to the thermostat from the system. See Fig. 8.
SET RETURN TIMES
AND SETPOINTS
Leave
ReturnSleep
SystemFan
DECREASE TIME SETTING OR
SCROLL BACKWARD THROUGH
INSTALLER SETUP AND SYSTEM TEST
INCREASE TEMPERATURE
SETTING OR SCROLL
FORWARD THROUGH
INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE
SETTING OR SCROLL
BACKWARD THROUGH
INSTALLER SETUP OPTIONS
DISPLAY INFORMATION
SUCH AS PRESENT
SETTINGS AND OUTDOOR
TEMPERATURE
SET SLEEP TIMES
AND SETPOINTS
SELECT FAN
OPERATION
SELECT SYSTEM
OPERATION
CHANGE BETWEEN
HEATING AND COOLING
SETPOINTS
M14624
TimeSet Program
Run
Set Current
Program
Day/Time
Hold Temp
Day
Daylight
Time
Leave
Wake
Heat/Cool
Settings
Copy
Return
System Fan
Sleep
Fig. 7. Thermostat System and Fan key locations.
M14625
System
Fan
TWO LED INDICATORS
M10675
Fig. 8. LEDs location.
369-1406—1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Outdoor
Fan
eat
On
o
Off
Cool
o
Temperature Settings
Refer to Table 2 for the default program. If the daytime
energy savings period is not used, press the period key
(Leave or Return) until the time is blank. The fan setting
feature is available on select thermostat models. See
Owner’s Guide, form number 69-0940, for complete
instructions on changing the program.
Table 2. Default Program Settings.
PeriodTime
Wake 6:45 AM 20°C
Leave 8:45 AM 4.5°C
Return 5:00 PM 20°C
Sleep 10:00 PM 4.5°C
Heat
Setpoint
(68°F)
(40°F)
(68°F)
(40°F)
Cool
Setpoint
25°C
(77°F)
37°C
(99°F)
25°C
(77°F)
37°C
(99°F)
Setting
Auto
Auto
Auto
Auto
Fan
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings will not need to be changed. Review
the factory settings in Table 2 and if no changes
are necessary, go to the Installer System Test
section.
The Installer Setup is used to customize the thermostat
to specific systems. Some of the options include
temperature display, changeover and outdoor
temperature display. Installer Setup numbers are listed in
Table 3. The table includes all the configuration options
and the factory-settings for the T8611.
A combination of key presses is required to use the
Installer Setup feature:
— To enter the installer setup, press and hold the
information i key with the increase ! and
decrease " keys until the first number is displayed.
All display segments appear for approximately three
seconds before the number is displayed. See Fig. 9
and 10.
— To advance to the next Installer Setup, press the
Time ∆ key.
— To change a setting, use the increase ! or decrease
" key.
— To scroll the Installer Setup numbers backward, press
the Time ∇ key.
— To exit the Installer Setup, press Run Program.
Wait
Recovery
Hold for
Filter
Em Ht
Tue Wed Thu Fri Sat Sun
Mon
Wake Leave Return Sleep
Set Day/TimeSet Program
Aux Ht
Days
AM
PM
Temporary Setting
Room
Repl Batt
DST
Heat
Cool
Em H
Aut
Aut
M14559
Fig. 9. Display of all LCD segments.
INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 3)
Fig. 10. Display of Installer Setup
number and setting.
IMPORTANT
Only configurable numbers are shown on the
device. Example: If thermostat does not have a
system key, Installer Setup Number 12 will not
be displayed. Review Table 3 factory-settings
and mark any desired changes in the Actual
Setting column. When Installer Setup is complete, review the settings to confirm that they
match the system.
FACTORY SETTING OR OTHER
CHOICE DISPLAY (COLUMN 3
OR 5 OF TABLE 3)
M14618
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup
Number (Press
Time ∆ key to
change)
Factory Setting
Other Choices
(Press ! or " key to change)
Not Used.1 thru 4—————
Heating cycle
rate.
56Stage 21, 6 or 9 1—1 cph
6—6 cph used for last stage
of heat pump systems
9—9 cph used for electric
heat
6 (Not used)————
76Emergency heat3, 6 or 9
Not Used.8 thru 11—————
System setting
adjustment
69-1406—14
121Manual
changeover
0 or 2 0—Auto changeover
2—Fixed auto changeover
Actual
SettingDisplayDescriptionDisplayDescription
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.