Honeywell T8611G User Manual

APPLICATION

T8611G Chronotherm® IV
Deluxe Programmable
INSTALLATION INSTRUCTIONS
The T8611G Chronotherm® IV Deluxe Programmable Heat Pump Thermostats provides electronic control of 24 Vac single-zone heat pump systems.
Table 1. Description of T8611 Thermostats.
T8611 Changeover System Selection Fan Selection Comments
G Automatic Em Heat-Heat-Off-Cool-Auto On-Auto System and fan selections are done by keyboard.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Refer to Table 1 for a general description of the thermostat. All T8611 thermostats require a common wire to supply power.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance only). The thermostat will function correctly even when not level.
2. Use a pencil to mark the mounting holes. See Fig.
2.
3. Remove the wallplate from the wall and drill two 3/16 inch (76 mm) holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch (5.56 mm) holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
® U.S. Registered Trademark Copyright © 2002 Honeywell • • All Rights Reserved
69-1406-1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
THERMOSTAT
YES
NO
NO
5 FEET
[1.5 METERS]
Fig. 1. Typical location of thermostat.
WIRES THROUGH WALL
WALL ANCHORS (2)
WALL
O/B
Y1 G E
C
NO
FAN RELAY
COOLING OR HEATING CHANGEOVER VALVE
COMPRESSOR CONTACTOR
M10106
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 3. Typical hookup of T8611G
in a heat pump system.
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
EM. HT. RELAY
W2
HEAT RELAY 2
Fig. 4. Correct wiring technique.
RW1
EQUIPMENT
MONITOR 2
EQUIPMENT
MONITOR 1
HEAT RELAY 1
TRANSFORMER
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
X2 LX1
OT OT
OUTDOOR SENSOR
1
L1 (HOT)
L2
M11311A
M4826
MOUNTING HOLES
MOUNTING SCREWS
M15044
Fig. 2. Mounting the wallplate.

WIRING

All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typical hookup. A letter code is located near each terminal for identification.
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 4.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
69-1406—1 2

Mounting Thermostat

1. Engage tabs at the top of the thermostat and wall­plate. See Fig. 5.
2. Press lower edge of case to close and latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove top last.
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
Fig. 5. Mounting thermostat on wallplate.
M14628
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
A
A

Using Thermostat Keys (Fig. 6)

The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
• configure Installer Setup,
• check System-Test,
• display outdoor temperature (select models),
• set the system operation,
• set the fan operation.
NOTE: Always press the keys with your fingertip or sim-
ilar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.

SETTINGS

System and Fan Settings
The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 7. The fan settings can be set for each program period individually. The system selection is for all the program periods.
INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP
ND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
ENTER INDEFINITE OR TIMED HOLD MODE
SET CURRENT OR PROGRAM DAY
CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME
SET WAKE TIMES AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
Fig. 6. T8611G key locations and descriptions.
SET LEAVE TIMES AND SETPOINTS
Time Set Program
Wake
Heat/Cool
Settings
Copy
System settings control the thermostat operation:
Em Heat: Emergency heat relay is on continuously.
Thermostat cycles highest stage of heat. Cooling system is off. Compressor is de-energized.
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between
heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan:
On: Fan operates continuously. Auto: Fan operates with equipment.

LED Indication

Two LED indicators are located in the upper right of the thermostat. They indicate when a Check or Fail signal is sent to the thermostat from the system. See Fig. 8.
SET RETURN TIMES AND SETPOINTS
Leave
Return Sleep
System Fan
DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE
SET SLEEP TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION
CHANGE BETWEEN HEATING AND COOLING SETPOINTS
M14624
Time Set Program
Run
Set Current
Program
Day/Time
Hold Temp
Day
Daylight
Time
Leave
Wake
Heat/Cool
Settings
Copy
Return
System Fan
Sleep
Fig. 7. Thermostat System and Fan key locations.
M14625
System
Fan
TWO LED INDICATORS
M10675
Fig. 8. LEDs location.
3 69-1406—1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Outdoor
Fan
eat
On
o
Off
Cool
o

Temperature Settings

Refer to Table 2 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. See Owner’s Guide, form number 69-0940, for complete instructions on changing the program.
Table 2. Default Program Settings.
Period Time
Wake 6:45 AM 20°C
Leave 8:45 AM 4.5°C
Return 5:00 PM 20°C
Sleep 10:00 PM 4.5°C
Heat
Setpoint
(68°F)
(40°F)
(68°F)
(40°F)
Cool
Setpoint
25°C (77°F)
37°C (99°F)
25°C (77°F)
37°C (99°F)
Setting
Auto
Auto
Auto
Auto
Fan

INSTALLER SETUP

NOTE: For most applications, the thermostat factory-
settings will not need to be changed. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer System Test section.
The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, changeover and outdoor temperature display. Installer Setup numbers are listed in Table 3. The table includes all the configuration options and the factory-settings for the T8611.
A combination of key presses is required to use the Installer Setup feature: — To enter the installer setup, press and hold the
information i key with the increase ! and decrease " keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 9 and 10.
— To advance to the next Installer Setup, press the
Time key.
— To change a setting, use the increase ! or decrease
" key.
— To scroll the Installer Setup numbers backward, press
the Time key.
— To exit the Installer Setup, press Run Program.
Wait
Recovery Hold for
Filter
Em Ht
Tue Wed Thu Fri Sat Sun
Mon Wake Leave Return Sleep
Set Day/TimeSet Program
Aux Ht
Days
AM
PM
Temporary Setting
Room
Repl Batt
DST
Heat
Cool
Em H
Aut
Aut
M14559
Fig. 9. Display of all LCD segments.
INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 3)
Fig. 10. Display of Installer Setup
number and setting.
IMPORTANT
Only configurable numbers are shown on the device. Example: If thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 3 factory-settings and mark any desired changes in the Actual Setting column. When Installer Setup is com­plete, review the settings to confirm that they match the system.
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 3)
M14618
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup
Number (Press
Time key to
change)
Factory Setting
Other Choices
(Press ! or " key to change)
Not Used. 1 thru 4
Heating cycle rate.
5 6 Stage 2 1, 6 or 9 1—1 cph
6—6 cph used for last stage
of heat pump systems
9—9 cph used for electric
heat
6 (Not used)
7 6 Emergency heat 3, 6 or 9
Not Used. 8 thru 11
System setting adjustment
69-1406—1 4
12 1 Manual
changeover
0 or 2 0—Auto changeover
2—Fixed auto changeover
Actual
SettingDisplay Description Display Description
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Table 3. Thermostat Installer Setup Options. (Continued)
Select
Adaptive Intelligent Recovery™ control.
Degree temperature display
Installer Setup
Number (Press
Time key to
change)
13 0 Adaptive Intelligent
14 1 Temperature is
Factory Setting
Recovery™ control is activated (system starts early so setpoint is reached by start of program period).
displayed in °C
Other Choices
(Press ! or " key to change)
1 Conventional recovery
(system starts recovery at programmed time).
Temperature is displayed in
°C
Actual
SettingDisplay Description Display Description
Not Used. 15
Clock format. 16 0 12-hour clock
format.
1 24-hour clock format.
Not Used. 17 thru 23
Outdoor temperature display (models with OT terminals).
24 0 No outdoor
temperature is displayed.
1 Outdoor temperature is
displayed. Needs a C7089B1000 Outdoor Temperature Sensor to operate.
Not Used. 25 thru 28
O/B terminal energized in heating or cooling.
Deadband 30 3 Heating and
29 0 O/B terminal
energized for reversing valve in cooling.
cooling setpoints can be set no closer than 3°F (1.5°C).
1 O/B terminal energized for
4 thru 10 Heating and cooling
reversing valve in heating
setpoints can be set no closer than the chosen value:
4—4°F (2°C) 5—5°F (2.5°C) 6—6°F (3°C) 7—7°F (3.5°C) 8—8°F (4°C) 9—9°F (4.5°C) 10—10°F (5°C)
Not Used. 31 and 32
Minimum off time for the compressor.
Temperature range stops in heating.
Temperature range stops in cooling.
33 5 5 minute minimum
34 90 Highest heating
35 45 Lowest cooling
off time for the compressor.
setpoint setting.
setpoint setting.
0 thru 4 Minimum number of minutes
40 thru 89 Temperature range (1°F
46 thru 99 Temperature range (1°F
(0 thru 5) the compressor will be off between calls for the compressor.
increments) of heating setpoint settings.
increments) of cooling setpoint settings
Not Used. 36
5 69-1406—1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Table 3. Thermostat Installer Setup Options. (Continued)
Installer Setup
Number (Press
Select
Temperature display adjustment.
Furnace Air Filter Timer.
Humidifier Pad Monitor.
Ultraviolet (UV) Air Treatment System Lamp Monitor.
IMPORTANT
Review the settings to confirm that they match the system. Press Run Program to exit the Installer Setup. The thermostat has saved the Installer Setup changes and initiated a reset in order to operate using the new settings. Be sure to set the current day and time immediately.
Time key to
change)
37 0 No difference in
43 0 Off 1, 2, 3, 4 1 – 10 days
44 0 Off 1, 2, 3 1 – 90 days
45 0 Off 1 1 – 365 days
Factory Setting
displayed temperature and actual room temperature.
-3 thru 3 1—Display adjusts to 1°F
Other Choices
(Press ! or " key to change)
higher than actual room temperature.
2—Display adjusts to 2°F
higher than actual room temperature.
3—Display adjusts to 3°F
higher than actual room temperature.
-1—Display adjusts to 1°F lower than actual room temperature.
-2—Display adjusts to 2°F lower than actual room temperature.
-3—Display adjusts to 3°F lower than actual room temperature.
2 – 30 days 3 – 60 days 4 – 120 days (Times counted when heat, cool or fan is running.)
2 – 180 days 3 – 365 days (Times counted by calendar days in heat mode.)
(Times counted by calendar days in any mode.)
Actual
SettingDisplay Description Display Description
69-1406—1 6
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Outdoor
Fan
eat
On
o
Off
Cool
o

Setting Current Day and Time

1. Press Set Current Day/Time.
NOTE: On initial powerup or after an extended power
loss, 1:00 pm flashes on the display until a key is pressed.
Set Day/Time
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Set Current
Day/Time
Program
Heat/Cool
Hold Temp
Day
Settings
Daylight
Copy
Time
System Fan
Mon
2. Press Day until the current day is displayed.
NOTE: Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday
.
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Day
3. Press Time ∆ or Time until the current time is
NOTE: Tapping the Set Current Day/Time changes the
Program
Heat/Cool
Hold Temp
System Fan
Day
Settings
Daylight
Copy
Time
displayed.
time in one-hour increments.
.
Time
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Program
Heat/Cool
Hold Temp
NOTE: If the current time is Daylight Savings Time,
press Daylight Time until DST is displayed.
System Fan
Day
Settings
Daylight
Copy
Time
.
Daylight
Time
Heat/Cool
Hold Temp
System Fan
Day
Settings
Daylight
Copy
Time
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Program
4. Press Run Program.
PM
M14619
Set Day/Time
PM
Tue
M14620
Set Day/Time
AM
Tue
M14621
Set Day/Time
AM
Tue
DST
M14622

INSTALLER SYSTEM-TEST

Use the Installer System Test to check the thermostat operation. Refer to Table 4 for a list of the available system-tests.
CAUTION
Equipment Damage Hazard. Minimum compressor off-time is bypassed during INstaller System Test.
Avoid cycling compressor quickly.
To start the sytem-test: Press and hold the increase ! and decrease " keys at the same time until 10 appears. All segments of the display will be displayed before the 10 appears. See Fig. 11 and 12.
Table 4. Tests Available In Installer System Test.
Test Number System Test Description
10-19 Heating equipment can be turned
30-39 Cooling equipment can be turned on
40-49 Fan equipment can be turned on
60 0 to 60 19 Keyboard keys test.
70-79 Thermostat information including
Wait
Recovery Hold for
Filter
Em Ht
Tue Wed Thu Fri Sat Sun
Mon
Wake Leave Return Sleep
Fig. 11. Display of all LCD segments.
.
on and off.
and off.
and off.
date code and software versions are displayed.
Days
AM
PM
Temporary Setting
Room
Repl Batt
DST
Heat
Cool
Set Day/TimeSet Program
Aux Ht
Em H
Aut
Aut
M14559
M14612
Run
Program
System
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Program
Heat/Cool
Hold Temp
System Fan
Day
Settings
Daylight
Copy
Time
Wake
AM
Tue
DST
Heat
Fan
Room
Auto
Refer to Table 5 for the directions and results of the
M14623
specific tests.
NOTE: Press Time to advance to the next test and
Fig. 12. Display of test number
Time to go back to the previous test. Press Run Program to exit the system test
7 69-1406—1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Table 5. Installer System Test Options.
Keys to
Press
Tes t
Number Description
Heating Equipment System-Test
Time 10 Enter heating equipment System Test.
! 11 Stage-one heat comes on. The system fan is also energized.
! 12 Stage-two heat comes on. Stage-one heat and system fan remain on.
" 11 Stage-two heat turns off.
" 10 Stage-one heat and system fan turn off.
Emergency Heating Equipment System Test
Time 20 Change from heating to emergency heating equipment System Test.
! 21 Emergency heat come on.
" 20 Emergency heat turn off.
Cooling Equipment System Test
Time 30 Change from heating or emergency heating to cooling equipment System Test.
! 31 Cool and system fan come on.
" 30 Cool and system fan turn off.
Fan Equipment System-Test
Time 40 Change from cooling to fan equipment System Test.
! 41 Fan comes on.
" 40 Fan turns off.
Key Operation System-Test
Time 60 Change from fan to key operation System Test.
NOTE: Press any key and the displayed numbers will change. Press Time to go to the previous test and Time ∆ to
go to the next test. The Run Program key will not exit this test. Press Time or Time and then the Run Program key to exit.
69-1406—1 8
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

THERMOSTAT INFORMATION

1. Press the Time ∆ key to access the thermostat
information.
2. Press the increase ! key to display the production date code. The first two large digits are the month and the third digit is the last digit of the year. (Example: 027 = February 1997).
3. Press the increase ! key again to display the soft- ware identification code. (Example: 02 = software ID code 2).
M14613
M14614
M14615
4. Press the increase ! key again to display the soft- ware revision number (Example: 001 = Revision number 1).
5. Press the increase ! key again to display the EEPROM identification code (Example: 314 = EEPROM ID 314).
6. Press the Run Program key to exit the system test. The system test times out after four minutes without any key presses.
M14616
M14617

CHECKOUT

Outdoor Temperature Sensor (Select Models)

Allow the outdoor temperature sensor to absorb the outdoor air for a minimum of five minutes before taking a reading.
9 69-1406—1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

TROUBLESHOOTING GUIDE

Table 6. Troubleshooting Guide.
Symptom Possible Cause Action
Display will not come on.
Temperature display is incorrect.
Temperature settings will not change. (Example: Cannot set the heating higher or the cooling lower.)
Heating will not come on.
Cooling will not come on.
Thermostat is not being powered.
Room temperature display has been reconfigured.
Thermostat is configured for °F or °C display.
Bad thermostat location. Relocate the thermostat.
The upper or lower temperature limits were reached.
The setpoint temperature range stops were configured.
No power to the thermostat. • Check for 24 Vac between R and C terminals.
Thermostat minimum off time is activated.
System selection is not set to Heat.
Heating setpoint is below room temperature.
No power to the thermostat. • Check for 24 Vac between R and C.
Thermostat minimum off time is activated.
System selection is not set to Cool.
Cool setpoint is above room temperature.
• Check for 24 Vac between R and C terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the circuit
breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in
the Off position—set to the On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any
loose connections.
— If 24 Vac is present, proceed with troubleshooting
Enter Installer Setup number 37 and reconfigure the display.
Enter Installer Setup number 14 and reconfigure the display.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (4.5 to 32°C)
• Cooling limits are 48 to 99°F (7 to 37°C)
Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops.
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the circuit
breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in
the Off position—set to the On position. — check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any
loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Wait up to five minutes for the system to respond.
Set system selection to Heat.
Check heating setpoint. Set heating setpoint to desired temperature.
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the circuit
breaker.
— check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in
the Off position—set to the On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any
loose connections.
— If 24 Vac is present, proceed with troubleshooting.
• Wait up to five minutes for the system to respond.
• Enter Installer Setup number 33. Reconfigure minimum off time (if required).
Set system selection to Cool.
Check cooling setpoint. Set cooling setpoint to desired temperature.
69-1406—1 10
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Table 6. Troubleshooting Guide. (Continued)
Symptom Possible Cause Action
System on indicator (flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers.
Outdoor tempera­ture not displayed
Outdoor temperature
display is incorrect
a
Select models.
Heating or cooling equipment is not operating.
Option not activated. Enter Installer Setup number 24 and set to 1. Thermostat must
a
Outdoor sensor is connected incorrectly.
a
Wrong sensor. Replace sensor with C7089B1000 Sensor.
Verify operation of heating or cooling equipment in self-test.
have OT terminals and a C7089B1000 installed.
Refer to C7089B1000 Installation Instructions and check wiring between the thermostat and sensor.
11 69-1406—1
T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
Automation and Control Solutions
Honeywell Honeywell Limited-Ho neywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z
69-1406—1 G.H. Rev. 12-02 www.honeywell.com/yourhome
Loading...