Honeywell T8611G User Manual

T8611G Chronotherm
Deluxe Zoning
Heat Pump Thermostat
INSTALLATION INSTRUCTIONS
The T8611G Chronotherm® Deluxe Zoning Heat Pump Thermostat provides electronic control of 24 Vac zoned heat pump systems. Refer to Table 1 and Table 2 for a general description of the thermostat and zoning applications.
Table 1. Description of T8611 Thermostats.
Model Power Method Changeover System Selection Fan Selection
T8611G2051 Hardwired Automatic or manual Heat-Off-Cool-Auto-Em. Heat On-Auto
Table 2. T8611 Zoning Applications.
Model TotalZone®EMM-3U EMM-3
T8611G2051 Yes Yes No
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.
4. After completing installation, use these instructions
to check out the product operation.

Location

Install the thermostat about 1.5m (5 ft) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
®

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
® U.S. Registered Trademark Copyright © 2003 Honeywell • • All Rights Reserved

Wallplate Installation

The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions correctly even when not level.
2. Use a pencil to mark the mounting holes.
See Fig. 2.
69-1414-2
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
6
E
3
3. Remove the wallplate from the wall and drill two
3/16 inch (76 mm holes) in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch (5.56 mm) holes. Gently tap anchors
YES
NO
NO
5 FEET
NO
[1.5 METERS]
(provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.

WIRING

All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 and 4 for typical hookup. A letter code is located near each terminal for identification.
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 5.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the thermostat.
The two OC terminals can be wired to the TZ-4 panel for remote operation of the Zone-A-Lone feature during the Leave and Sleep periods. See Table 9 and the TZ-4 Installation Instructions, form 68-0259, for more information.
Fig. 1. Typical location of thermostat.
WALL
MOUNTING SCREWS
M15044
WALL ANCHORS (2)
WIRES THROUGH WALL
Fig. 2. Mounting the wallplate.
MOUNTING HOLES
M1010
2
R
NORMALLY, WIRE E ON THERMOSTAT TO W1/E ON PANEL;
1
ALTERNATIVELY, INSTALL JUMPER FROM E TO Y ON THERMOSTAT AND OMIT WIRE TO W1/E ON PANEL.
2
CONNECT O/B JUMPER ON EMM-3U PANEL WHEN O/B TERMINAL ON THERMOSTAT IS CONFIGURED AS O.
1
E Y G O/BC W2 L OT OT
Fig. 3. Typical wiring diagram for EMM-3U panel.
69-1414—2 2
R C
24 VAC
40 VA
GW2Y2 M6M4M1Y1CRL
O/BW1/E
EMM-3U THERMOSTAT CONNECTORS
C7089B OUTDOOR TEMPERATUR SENSOR (OPTIONAL)
M2093
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
)
6
F I 7
4
B
OC OC
2
TZ-4 THERMOSTAT CONNECTORS
C OC OC
NORMALLY, WIRE E ON THERMOSTAT TO W1/E ON PANEL;
1
ALTERNATIVELY, INSTALL JUMPER FROM E TO Y ON THERMOSTAT AND OMIT WIRE TO W1/E ON PANEL.
2
CONNECT O/B JUMPER ON TZ-4 PANEL WHEN O/B TERMINAL ON THERMOSTAT IS CONFIGURED AS O.
3
CONNECT THE OC TERMINALS ONLY IF THE ZONE-A-LONE UNOCCUPIED FEATURE IS DESIRED. SEE TZ-4 INSTALLER INSTRUCTIONS FOR EXPLANATION.
1 3
E Y G O/BR W2 L OT OT
Fig. 4. Typical wiring diagram for T8611G on TotalZone® Control Panel.
OR WRAPAROUND
NSERTION STRIP
/16 IN. (11 MM).
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
M482
Fig. 5. Correct wiring technique.

Mounting Thermostat

1. Engage tabs at the top of the thermostat and wall-
plate. See Fig. 6. Be sure to align subbase pins to avoid damage to the thermostat.
2. Press lower edge of case to close and latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove top last.
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
.
PRESS LOWER EDGE OF CASE TO LATCH.
C7089B OUTDOOR TEMPERATURE SENSOR (OPTIONAL
M20932
M1463
Fig. 6. Mounting thermostat on wallplate.
3 69-1414—2
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
S
I O T A
NCREASE TIME SETTING
R SCROLL FORWARD HROUGH INSTALLER SETUP ND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
ENTER INDEFINITE OR TIMED HOLD MODE
SET CURRENT OR PROGRAM DAY
CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME
SET WAKE TIMES AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
SET LEAVE TIMES AND SETPOINTS
Time Set Program
Heat/Cool

Settings

Copy
Fig. 7. T8611G key locations and descriptions.

Using Thermostat Keys

The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
• configure Installer Setup,
• check System-Test,
• display outdoor temperature,
• set the system operation,
• set the fan operation.
NOTE: Always press the keys with your fingertip or sim-
ilar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
SETTINGS
SET RETURN TIMES AND SETPOINTS
Leave
Wake
DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
Return Sleep
System Fan
Fan settings control the system fan:
On: Fan operates continuously. Auto: Fan operates with equipment.
NOTE: Always press the keys with you fingertip or simi-
lar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTION
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE
SET SLEEP TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION
CHANGE BETWEEN HEATING AND COOLING SETPOINTS

Temperature Settings

Refer to Table 3 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. See Owner’s Guide, form number 69-1400, for complete instructions on changing the program.
NOTE: For most applications, the thermostat factory-
settings do not require changing. Review the factory settings in Table 3 and if no changes are necessary, go to the Installer Self-Test section.
M14624
System and Fan Settings
The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 8. The fan settings can be set for each program period individually. The system selection is for all the program periods.
System settings control thermostat operation:
Em Heat: L terminal is on continuously.Thermostat
cycles emergency heat and second stage of heat.
Cooling system is off. Compressor is de-energized. Heat: Thermostat controls the heating. Off: Both the heating and cooling are off. Cool: Thermostat controls the cooling. Auto (if selected): Thermostat automatically changes
between heating and cooling operation, depending
on the indoor temperature.
69-1414—2 4
Program
Hold Temp
Set Current
Day
Day/Time
Daylight
Time
Leave
Wake
Heat/Cool
Settings
Copy
Return
System Fan
Sleep
System
Fan
M14625
Time Set Program
Run
Fig. 8. T8611G System and Fan key locations.
Loading...
+ 8 hidden pages