Honeywell T8611G User Manual

T8611G Chronotherm
Deluxe Zoning
Heat Pump Thermostat
INSTALLATION INSTRUCTIONS
The T8611G Chronotherm® Deluxe Zoning Heat Pump Thermostat provides electronic control of 24 Vac zoned heat pump systems. Refer to Table 1 and Table 2 for a general description of the thermostat and zoning applications.
Table 1. Description of T8611 Thermostats.
Model Power Method Changeover System Selection Fan Selection
T8611G2051 Hardwired Automatic or manual Heat-Off-Cool-Auto-Em. Heat On-Auto
Table 2. T8611 Zoning Applications.
Model TotalZone®EMM-3U EMM-3
T8611G2051 Yes Yes No
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.
4. After completing installation, use these instructions
to check out the product operation.

Location

Install the thermostat about 1.5m (5 ft) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
®

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
® U.S. Registered Trademark Copyright © 2003 Honeywell • • All Rights Reserved

Wallplate Installation

The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions correctly even when not level.
2. Use a pencil to mark the mounting holes.
See Fig. 2.
69-1414-2
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
6
E
3
3. Remove the wallplate from the wall and drill two
3/16 inch (76 mm holes) in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch (5.56 mm) holes. Gently tap anchors
YES
NO
NO
5 FEET
NO
[1.5 METERS]
(provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.

WIRING

All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 and 4 for typical hookup. A letter code is located near each terminal for identification.
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 5.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the thermostat.
The two OC terminals can be wired to the TZ-4 panel for remote operation of the Zone-A-Lone feature during the Leave and Sleep periods. See Table 9 and the TZ-4 Installation Instructions, form 68-0259, for more information.
Fig. 1. Typical location of thermostat.
WALL
MOUNTING SCREWS
M15044
WALL ANCHORS (2)
WIRES THROUGH WALL
Fig. 2. Mounting the wallplate.
MOUNTING HOLES
M1010
2
R
NORMALLY, WIRE E ON THERMOSTAT TO W1/E ON PANEL;
1
ALTERNATIVELY, INSTALL JUMPER FROM E TO Y ON THERMOSTAT AND OMIT WIRE TO W1/E ON PANEL.
2
CONNECT O/B JUMPER ON EMM-3U PANEL WHEN O/B TERMINAL ON THERMOSTAT IS CONFIGURED AS O.
1
E Y G O/BC W2 L OT OT
Fig. 3. Typical wiring diagram for EMM-3U panel.
69-1414—2 2
R C
24 VAC
40 VA
GW2Y2 M6M4M1Y1CRL
O/BW1/E
EMM-3U THERMOSTAT CONNECTORS
C7089B OUTDOOR TEMPERATUR SENSOR (OPTIONAL)
M2093
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
)
6
F I 7
4
B
OC OC
2
TZ-4 THERMOSTAT CONNECTORS
C OC OC
NORMALLY, WIRE E ON THERMOSTAT TO W1/E ON PANEL;
1
ALTERNATIVELY, INSTALL JUMPER FROM E TO Y ON THERMOSTAT AND OMIT WIRE TO W1/E ON PANEL.
2
CONNECT O/B JUMPER ON TZ-4 PANEL WHEN O/B TERMINAL ON THERMOSTAT IS CONFIGURED AS O.
3
CONNECT THE OC TERMINALS ONLY IF THE ZONE-A-LONE UNOCCUPIED FEATURE IS DESIRED. SEE TZ-4 INSTALLER INSTRUCTIONS FOR EXPLANATION.
1 3
E Y G O/BR W2 L OT OT
Fig. 4. Typical wiring diagram for T8611G on TotalZone® Control Panel.
OR WRAPAROUND
NSERTION STRIP
/16 IN. (11 MM).
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
M482
Fig. 5. Correct wiring technique.

Mounting Thermostat

1. Engage tabs at the top of the thermostat and wall-
plate. See Fig. 6. Be sure to align subbase pins to avoid damage to the thermostat.
2. Press lower edge of case to close and latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove top last.
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
.
PRESS LOWER EDGE OF CASE TO LATCH.
C7089B OUTDOOR TEMPERATURE SENSOR (OPTIONAL
M20932
M1463
Fig. 6. Mounting thermostat on wallplate.
3 69-1414—2
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
S
I O T A
NCREASE TIME SETTING
R SCROLL FORWARD HROUGH INSTALLER SETUP ND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
ENTER INDEFINITE OR TIMED HOLD MODE
SET CURRENT OR PROGRAM DAY
CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME
SET WAKE TIMES AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
SET LEAVE TIMES AND SETPOINTS
Time Set Program
Heat/Cool

Settings

Copy
Fig. 7. T8611G key locations and descriptions.

Using Thermostat Keys

The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
• configure Installer Setup,
• check System-Test,
• display outdoor temperature,
• set the system operation,
• set the fan operation.
NOTE: Always press the keys with your fingertip or sim-
ilar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
SETTINGS
SET RETURN TIMES AND SETPOINTS
Leave
Wake
DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
Return Sleep
System Fan
Fan settings control the system fan:
On: Fan operates continuously. Auto: Fan operates with equipment.
NOTE: Always press the keys with you fingertip or simi-
lar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTION
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE
SET SLEEP TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION
CHANGE BETWEEN HEATING AND COOLING SETPOINTS

Temperature Settings

Refer to Table 3 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. See Owner’s Guide, form number 69-1400, for complete instructions on changing the program.
NOTE: For most applications, the thermostat factory-
settings do not require changing. Review the factory settings in Table 3 and if no changes are necessary, go to the Installer Self-Test section.
M14624
System and Fan Settings
The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 8. The fan settings can be set for each program period individually. The system selection is for all the program periods.
System settings control thermostat operation:
Em Heat: L terminal is on continuously.Thermostat
cycles emergency heat and second stage of heat.
Cooling system is off. Compressor is de-energized. Heat: Thermostat controls the heating. Off: Both the heating and cooling are off. Cool: Thermostat controls the cooling. Auto (if selected): Thermostat automatically changes
between heating and cooling operation, depending
on the indoor temperature.
69-1414—2 4
Program
Hold Temp
Set Current
Day
Day/Time
Daylight
Time
Leave
Wake
Heat/Cool
Settings
Copy
Return
System Fan
Sleep
System
Fan
M14625
Time Set Program
Run
Fig. 8. T8611G System and Fan key locations.

INSTALLER SETUP

9
t f l
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, changeover, and outdoor temperature display. Installer Setup numbers are listed in Table 4. The table includes all the configuration options and the factory settings for the T8611.
Table 3. Default Program Settings.
Period Time
Wake 6:00 AM 70°F
Leave 8:00AM 62°F
Return 5:00 PM 70°F
Sleep 10:00 PM 62°F
A combination of key presses are required to use the Installer Setup feature: — To enter the installer setup, press and hold the
information i key with the increase and decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 9 and 10.
— To advance to the next Installer Setup, press the
Time key.
— To change a setting, use the increase or
decreasekey.
— To scroll the Installer Setup numbers backward, press
the Time key.
Heat
Setpoint
(21°C)
(16.5°C)
(20°C)
(16.5°C)
Cool
Setpoint
78°F
(25.5°C)
85°F
(29.5°C)
78°F
(25.5°C)
82°F
(28°C)
Fan
Setting
Auto
Auto
Auto
Auto
— To exit the Installer Setup, press Run Program.
Wait Recovery
Hold for
Filter
Em Ht
Mon
TueWed Thu Fri Sat Sun
Wake Leave Return Sleep
Set Day/TimeSet Program
Aux Ht
Days
AM PM
Temporary Setting
Repl Batt
DST
Heat
OutdoorRoom
Cool
Fig. 9. Display of all LCD segments.
INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 3)
Fig. 10. Display of Installer Setup
number and setting.
IMPORTANT
Only configurable numbers are shown on the device. Review Table 4 factory-settings and mark any desired changes in the Actual Setting column. When Installer Setup is complete, review the settings to confirm that they match the system.
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 3)
System
Em Hea
Fan
M1455
M14618
Coo Auto
Auto
Of
On
Table 4. Thermostat Installer Setup Options.
Select
Installer Setup
Number (Press
Time key to
change)
Factory Setting
Other Choices
(Press or key to change)
Actual
SettingDisplay Description Display Description
Not Used. 1 thru 4
Heating cycle
a
rate
5 6 Stage 2 3 or 9 3—3 cph (factory setting for
6 (Not Used).
7 9 Emergency heat 3 or 6
first stage of heat)
6—6 cph used for second stage of heat
9—9 cph used for electric heat
Not Used. 8 thru 11
System setting adjustment
Adaptive Intelligent Recovery™ control.
12 1 Manual
13 0 Adaptive Intelligent
changeover
Recovery™ control is activated (system starts early so setpoint is reached by start of program period).
5 69-1414—2
0 or 2 0—Auto changeover.
2—Fixed auto changeover.
1 Conventional recovery
(system starts recovery at programmed time).
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
Table 4. Thermostat Installer Setup Options. (Continued)
Select
Degree temperature display
Installer Setup
Number (Press
Time key to
change)
Factory Setting
14 0 Temperature is
displayed in °F
Other Choices
(Press or key to change)
1 Temperature is displayed in
°C
Actual
SettingDisplay Description Display Description
Not Used. 15
Clock format. 16 0 12-hour clock
format.
1 24-hour clock format.
Not Used. 17 and 18
Extended fan operation in heating.
Extended fan operation in cooling.
19 0 No extended fan
20 No extended fan
operation after the call for heat ends.
operation after the call for cool ends.
1 Fan operation is extended
90 seconds after the call for heat ends.
1 Fan operation is extended
90 seconds after the call for cool ends.
Not Used. 21 thru 23
Outdoor temperature display (models with OT terminals).
24 0 No outdoor
temperature is displayed.
1 Outdoor temperature is
displayed. Needs a C7089B1000 Outdoor Temperature Sensor to operate.
Not Used. 25 thru 28
O/B terminal energized in heating or cooling.
Deadband 30 3 Heating and
29 0 O/B terminal
energized for reversing valve in cooling.
cooling setpoints can be set no closer than 3°F (1.5°C).
1 O/B terminal energized for
reversing valve in heating
2 thru 10 Heating and cooling
setpoints can be set no closer than the chosen value:
2—2°F (2°C) 4—4°F (2°C) 5—5°F (2.5°C) 6—6°F (3°C) 7—7°F (3.5°C) 8—8°F (4°C) 9—9°F (4.5°C) 10—10°F (5°C)
Not Used. 31 thru 32
Minimum off time for the compressor.
Temperature range stops in heating.
Temperature range stops in cooling.
System on indicator (flame=heat, snowflake= cool) is displayed.
33 5 5 minute minimum
34 90 Highest heating
35 45 Lowest cooling
36 0 LCD on symbol is
off time for the compressor.
setpoint setting.
setpoint setting.
displayed when system is energized
0 thru 4 Minimum number of minutes
40 to 89 Temperature range (1°F
46 to 99 Temperature range (1°F
(0 thru 5) the compressor is off between calls for the compressor.
increments) of heating setpoint settings.
increments) of cooling setpoint settings.
1 Icons in display are
disabled.
69-1414—2 6
Table 4. Thermostat Installer Setup Options. (Continued)
Installer Setup
Number (Press
Select
Temperature display adjustment.
Furnace Air Filter Timer.
Humidifier Pad Monitor.
Ultraviolet (UV) Air Treatment System Lamp Monitor.
IMPORTANT
Review the settings to confirm that they match the system. Press Run Program to exit the Installer Setup. The thermostat has saved the Installer Setup changes and initiated a reset in order to operate using the new settings. Be sure to set the current day and time immediately.
Time key to
change)
37 0 No difference in
43 2 30 days (System
44 0 Off 1, 2, 3 1 – 90 days
45 0 Off 1 1 – 365 days
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
Factory Setting
displayed temperature and actual room temperature.
run time)
3 thru -3 or
1.5 thru
-1.5
0, 1, 3, 4 0 – off
Other Choices
(Press or key to change)
1 (0.5)—Display adjusts to
1°F (0.5°C) higher than actual room temperature.
2 (1.0)—Display adjusts to
2°F (1.0°C) higher than actual room temperature.
3 (1.5) —Display adjusts to
3°F (1.5°C) higher than actual room temperature.
-1 (-0.5) —Display adjusts to
-1°F (-0.5°C) lower than actual room temperature.
-2 (-1.0) —Display adjusts to
-2°F (-1.0°C) lower than actual room temperature.
-3 (-1.5) —Display adjusts to
-3°F (-1.5°C) lower than actual room temperature.
1 – 10 days 3 – 60 days 4 – 120 days (Time is counted when heat, cool or fan is running.)
2 – 180 days 3 – 365 days (Time is counted by calendar days in heat mode.)
(Time is counted by calendar days in any mode.)
Actual
SettingDisplay Description Display Description
7 69-1414—2
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
9
0
1
2
3
3
4

Setting Current Day and Time

1. Press Set Current Day/Time.
NOTE: On initial powerup or after an extended power
loss, 1:00 pm flashes on the display until a key is pressed.
Set Day/Time
Set Current
Day/Time
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Program
Heat/Cool
Hold Temp
Day
Settings
Daylight
Copy
Time
System Fan
Mon
PM
M1461
2. Press Day until the current day is displayed.
NOTE: Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday.
Set Day/Time
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Day
3. Press Time or Time until the current time is dis-
NOTE: Tapping the Set Current Day/Time changes the
Program
Heat/Cool
Hold Temp
System Fan
Day
Settings
Daylight
Copy
Time
played.
time in one-hour increments.
PM
Tue
M1462
Daylight
4. Press Run Program.
Program

View or Reset Timer Settings

When the thermostat activates a timer, the thermostat flashes Filter until the timer resets.
1. Reset the timer by pressing the i key until the
2. Press the Time key to reset the timer.
Run
Program
Hold Temp
Time
Run
Program
Run
Hold Temp
expired timer is displayed.
Filter
Set Current Day/Time
Day
Daylight
Time
Set Current Day/Time
Day
Daylight
Time
Time Set Program
Leave
Wake
Heat/Cool
Settings
Copy
Time Set Program
Leave
Wake
Heat/Cool
Settings
Copy
Days
Return Sleep
System Fan
Return Sleep
System Fan
Set Day/Time
AM
Tue
Tue
Wake
DST
M1462
System
AM
DST
Heat
Fan
Room
Auto
M1462
M2024
Time
Set Day/Time
Time Set Program
Set Current
Run
Leave
Wake
Return Sleep
Day/Time
Program
Heat/Cool
Hold Temp
NOTE: If the current time is Daylight Savings Time,
press Daylight Time until DST is displayed.
System Fan
Day
Settings
Daylight
Copy
Time
AM
Tue
M1462
69-1414—2 8
Filter
Days
M2024
3. Press the Run Program key.
NOTE: You can view the number of days remaining at
any time by pressing the i key three or four times. If more than one timer is active, all active timers show sequentially when pressing the i key several times.
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
9
t f
l
2

INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat operation. Refer to Table 5 for a list of the available self-tests.
Table 5. Tests Available In Installer Self-Test.
Tes t
Number System Test Description
10-19 Heating equipment can be turned on and off.
20-29 Emergency heat equipment can be turned
on and off.
30-39 Cooling equipment can be turned on and off.
40-49 Fan equipment can be turned on and off.
60 0 to 60 19
70-79 Thermostat information including date code
Keyboard keys test.
and software versions are displayed.
CAUTION
Equipment Damage Hazard. Minimum compressor off-time is bypassed during the Installer System Test.
Avoid cycling compress quickly.
To start the system test: Press and hold the increase and decrease keys at the same time until 10 appears. All segments of the display are displayed before the 10 appears. See Fig. 10 and 11.
Table 6. Installer System Test Options.
Keys to
Press
Heating Equipment Self-Test
Time 10 Enter heating equipment self-test.
Emergency Heating Equipment Self-Test
Time 20 Change from heating to emergency heating equipment self-test.
Cooling Equipment Self-Test
Time 30 Change from heating or emergency heating to cooling equipment self-test.
Fan Equipment Self-Test
Time 40 Change from cooling to fan equipment self- test.
Tes t
Number Description
11 Stage-one heat comes on. The system fan is also energized.
12 Stage-two heat comes on. Stage-one heat and system fan remain on.
11 Stage-two heat turns off.
10 Stage-one heat and system fan turn off.
21 Emergency heat and system fan come on.
22 Stage 2 heat comes on.
21 Stage 2 heat turns off.
20 Emergency heat and system fan turn off.
31 Cool and system fan come on.
30 Cool and system fan turn off.
Wait Recovery
Hold for
Filter
Mon
TueWed Thu Fri Sat Sun
Wake Leave Return Sleep
Em Ht
Set Day/TimeSet Program
Aux Ht
Days
AM PM
Temporary Setting
Repl Batt
DST
Heat
OutdoorRoom
Cool
Fig. 11. Display of all LCD segments.
Fig. 12. Display of test number.
Refer to Table 6 for the directions and results of the specific tests.
NOTE: Press Time to advance to the next test and
Time to go back to the previous test. Press Run Program to exit the system test.
9 69-1414—2
System
Em Hea
Fan
M1455
Coo Auto
Auto
M1461
Of
On
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
3
4
5
6
7
Table 6. Installer System Test Options. (Continued)
Keys to
Press
Tes t
Number Description
41 Fan comes on.
40 Fan turns off.
Key Operation Self-Test
Time 60 2 Change from fan to key operation self-test.
NOTE: Press any key and the displayed numbers will change. Press Time to go to the previous test and Time to
go to the next test. The Run Program key does not exit this test. Press Time or Time and then the Run Program key to exit.

THERMOSTAT INFORMATION

1. Press the Time key to access the thermostat
information.
M1461
2. Press the increase  key to display the production
date code. The first two large digits are the month
and the third digit is the last digit of the year.
(Example: 027 = February 1997).
3. Press the increase  key again to display the
software identification code.
(Example: 02 = software ID code 2).
sy
M1461
4. Press the increase  key again to display the soft-
ware revision number. (Example: 001 = Revision number 1).
M1461
5. Press the increase  key again to display the
EEPROM identification code. (Example: 314 = EEPROM ID 314)
6. Press the Run Program key to exit the self- test.
The self- test times out after four minutes without any key presses.
M1461

CHECKOUT

Outdoor Temperature Sensor

Allow the outdoor temperature sensor to absorb the outdoor air for a minimum of five minutes before taking a reading.
M1461
69-1414—2 10
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT

TROUBLESHOOTING GUIDE (TABLE 7)

Table 7. Troubleshooting Guide.
Symptom Possible Cause Action
Display does not come on.
Temperature display is incorrect.
Temperature settings do not change. (Example: Cannot set the heating higher or the cooling lower.)
Heating or cooling does not come on.
System on indicator (flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers.
Outdoor tempera­ture not displayed
Outdoor temperature
display is incorrect
a
Select models.
Thermostat is not being powered.
Thermostat is not fully connected to wallplate.
Room temperature display has been reconfigured.
Thermostat is configured for °F or °C display.
• Check for 24 Vac between R and C terminals. — If missing 24 Vac:
— verify that the thermostat is correctly wired to the zone
control panel. — R on thermostat to R on the TZ-3 and C to M1. — R on thermostat to R on the EMM-3U and TZ-4 and C to C.
— verify that the thermostat is correctly wired to the zone
control panel.
—replace any broken wires and tighten any loose
connections.
— If 24 Vac is present, proceed with troubleshooting
Verify that thermostat is correctly positioned and securely latched to wallplate.
Enter Installer Setup number 37 and reconfigure the display.
Enter Installer Setup number 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat.
The upper or lower temperature limits were reached.
The setpoint temperature range stops were configured.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (4.5 to 32°C).
• Cooling limits are 48 to 99°F (7 to 37°C).
Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops.
No power to the thermostat. Use action listed under “Display will not come on.”
Thermostat minimum off time is activated.
Wait up to five minutes for the system to respond. Enter Installer Setup number 33. Reconfigure the minimum off time, if required.
System selector is set to off. Verify that the system selector is set for Heat, Cool or Auto.
Thermostat is not calling for heat or cool.
Thermostat is not wired correctly to the zone panel.
Zone panel is not correctly configured or wired correctly.
Option not activated. Enter Installer Setup number 24 and set to 1. Thermostat must
a
Outdoor sensor is connected incorrectly.
a
Wrong sensor. Replace sensor with C7089B1000 Sensor.
Verity that the heat or cool icon (flame or snowflake) is present. If not, raise or lower the setpoint to make a call for cool or heat.
Verify wiring. Check if other zones can bring on the heat or cool.
If no zones can bring on the heat, verify equipment configuration and wiring.
have OT terminals and a C7089B1000 installed.
Refer to C7089B1000 Installation Instructions and check wiring between the thermostat and sensor.
11 69-1414—2
T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT
Table 8. T8611G2051 Sequence of Operation.
Fan
Selection System Selection Call Energize Display****
AUTO OFF None None None
AUTO OFF Fan G Fan Symbol
ON OFF None G Fan Symbol
AUTO COOL None O* None
AUTO COOL or AUTO Cooling O, G, Y Snowflake Symbol,
Fan Symbol
AUTO HEAT or AUTO None B* None
AUTO HEAT or AUTO Stage 1 Heating B, Y Flame Symbol,
AUTO HEAT or AUTO Stage 2 Heating B, Y, W2 Flame Symbol,
Fan Symbol
Fan Symbol, AUX. HEAT
AUTO EM. HEAT None L EM. HEAT
AUTO EM. HEAT Stage 1 Heating L, E Flame Symbol,
AUTO EM. HEAT Stage 2 Heating L, E, W2 Flame Symbol,
Fan Symbol, EM. HEAT
Fan Symbol, EM. HEAT, AUX. HEAT
AUTO AUTO None O**, B*** None
SYSTEM and FAN selection identified on the LCD.
* = Thermostat O/B terminal is configurable for heating or cooling changover.
** = O is energized when cooling was last call from thermostat.
*** = B is energized when heating was last call from thermostat.
**** = Installer setup mode 36 disables flame and snowflake icons from display.
Table 9. Occupied Terminal Operation.
Mode OC Contacts Closed Display
Wake No None
Leave Yes None
Return No None
Sleep Yes None
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
69-1414—2 G.H. Rev. 1-03 www.honeywell.com/yourhome
M1V 4Z9
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Loading...