The T8611G Chronotherm® Deluxe Zoning Heat Pump Thermostat provides electronic control of 24 Vac zoned heat
pump systems. Refer to Table 1 and Table 2 for a general description of the thermostat and zoning applications.
T8611G2051HardwiredAutomatic or manualHeat-Off-Cool-Auto-Em. HeatOn-Auto
Table 2. T8611 Zoning Applications.
ModelTotalZone®EMM-3UEMM-3
T8611G2051YesYesNo
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the old control.
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 1.5m (5 ft) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
®
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
The thermostat can be mounted horizontally on the wall
or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
Position wallplate horizontally on the wall or on a
2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions correctly even
when not level.
3. Remove the wallplate from the wall and drill two
3/16 inch (76 mm holes) in the wall (if drywall) as
marked. For firmer material such as plaster, drill
two 7/32 inch (5.56 mm) holes. Gently tap anchors
YES
NO
NO
5 FEET
NO
[1.5 METERS]
(provided) into the drilled holes until flush with the
wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 and 4 for typical hookup. A
letter code is located near each terminal for identification.
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power before wiring.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 5.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for
proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the thermostat.
The two OC terminals can be wired to the TZ-4 panel for
remote operation of the Zone-A-Lone feature during the
Leave and Sleep periods. See Table 9 and the TZ-4
Installation Instructions, form 68-0259, for more
information.
Fig. 1. Typical location of thermostat.
WALL
MOUNTING
SCREWS
M15044
WALL
ANCHORS (2)
WIRES
THROUGH WALL
Fig. 2. Mounting the wallplate.
MOUNTING
HOLES
M1010
2
R
NORMALLY, WIRE E ON THERMOSTAT TO W1/E ON PANEL;
1
ALTERNATIVELY, INSTALL JUMPER FROM E TO Y ON
THERMOSTAT AND OMIT WIRE TO W1/E ON PANEL.
2
CONNECT O/B JUMPER ON EMM-3U PANEL WHEN O/B TERMINAL ON
THERMOSTAT IS CONFIGURED AS O.
R SCROLL FORWARD
HROUGH INSTALLER SETUP
ND SYSTEM TEST
SET CURRENT
DAY AND TIME
RETURN TO
NORMAL
OPERATIONS
ENTER
INDEFINITE
OR TIMED
HOLD MODE
SET CURRENT OR
PROGRAM DAY
CHANGE BETWEEN
DAYLIGHT SAVINGS
AND STANDARD TIME
SET WAKE TIMES
AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED
DAY TO ANOTHER DAY
SET LEAVE TIMES
AND SETPOINTS
TimeSet Program
Heat/Cool
Settings
Copy
Fig. 7. T8611G key locations and descriptions.
Using Thermostat Keys
The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
• configure Installer Setup,
• check System-Test,
• display outdoor temperature,
• set the system operation,
• set the fan operation.
NOTE: Always press the keys with your fingertip or sim-
ilar blunt tool. Sharp instruments like a pen or
pencil point can damage the keyboard.
SETTINGS
SET RETURN TIMES
AND SETPOINTS
Leave
Wake
DECREASE TIME SETTING OR
SCROLL BACKWARD THROUGH
INSTALLER SETUP AND SYSTEM TEST
ReturnSleep
SystemFan
Fan settings control the system fan:
On: Fan operates continuously.
Auto: Fan operates with equipment.
NOTE: Always press the keys with you fingertip or simi-
lar blunt tool. Sharp instruments like a pen or
pencil point can damage the keyboard.
INCREASE TEMPERATURE
SETTING OR SCROLL
FORWARD THROUGH
INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE
SETTING OR SCROLL
BACKWARD THROUGH
INSTALLER SETUP OPTION
DISPLAY INFORMATION
SUCH AS PRESENT
SETTINGS AND OUTDOOR
TEMPERATURE
SET SLEEP TIMES
AND SETPOINTS
SELECT FAN
OPERATION
SELECT SYSTEM
OPERATION
CHANGE BETWEEN
HEATING AND COOLING
SETPOINTS
Temperature Settings
Refer to Table 3 for the default program. If the daytime
energy savings period is not used, press the period key
(Leave or Return) until the time is blank. See Owner’s
Guide, form number 69-1400, for complete instructions
on changing the program.
NOTE: For most applications, the thermostat factory-
settings do not require changing. Review the
factory settings in Table 3 and if no changes are
necessary, go to the Installer Self-Test section.
M14624
System and Fan Settings
The system default setting is Heat and the fan default
setting is Auto. Use the System and Fan keys to change
the settings. See Fig. 8. The fan settings can be set for
each program period individually. The system selection is
for all the program periods.
System settings control thermostat operation:
Em Heat: L terminal is on continuously.Thermostat
cycles emergency heat and second stage of heat.
Cooling system is off. Compressor is de-energized.
Heat: Thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: Thermostat controls the cooling.
Auto (if selected): Thermostat automatically changes
between heating and cooling operation, depending
on the indoor temperature.
69-1414—24
Program
Hold Temp
Set Current
Day
Day/Time
Daylight
Time
Leave
Wake
Heat/Cool
Settings
Copy
Return
System Fan
Sleep
System
Fan
M14625
TimeSet Program
Run
Fig. 8. T8611G System and Fan key locations.
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.