Honeywell T8601D User Manual

T8601D Chronotherm® IV Deluxe
Programmable Thermostats
INSTALLATION INSTRUCTIONS

APPLICATION

The T8601 Chronotherm® IV Deluxe Programmable Thermostat provides electronic control of 24 Vac single-
Table 1. Description of T8601 Thermostats.
T8601 System Changeover System Selection Fan Selection Comments
D Heat-Cool Automatic Heat-Off-Cool-Auto On-Auto Use keyboard for system and fan selections
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
stage heating and cooling systems. Refer to Table 1 for a general description of the thermostat. All T8601 thermostats require a common wire to supply power.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
® U.S. Registered Trademark Copyright © 2002 Honeywell • •All Rights Reserved
69-1410-2
T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
NO
NO
[1.5 METERS]
Fig. 1. Typical location of thermostat.

Wallplate Installation

The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance only). The thermostat functions correctly even when not level.
WIRES THROUGH WALL
WALL ANCHORS (2)
Fig. 2. Mounting the wallplate.
2. Use a pencil to mark the mounting holes. See
Fig. 2.
WALL
MOUNTING HOLES
MOUNTING SCREWS
M15044
YES
5 FEET
NO
M10106
3. Remove the wallplate from the wall and drill two 3/16 in. holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.

WIRING

All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 through 5 for typical hookups. A letter code is located near each terminal for identification.
CAUTION
Electrical Hazard. Can cause electric shock and equipment damage.
Disconnect power before beginning wiring.
1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 6.
THERMOSTAT
GC
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
Fig. 3. Typical hookup in heat only application.
HEAT RELAY
RW
TRANSFORMER
L1 (HOT)
L2
1
M10357
69-1410—2 2
T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
THERMOSTAT
C
YG
COMPRESSOR CONTACTOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
2
PUMP SYSTEMS.
3
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE.
Fig. 4. Typical hookup in heat and cool
THERMOSTAT
RC
YG
2
COMPRESSOR CONTACTOR
1
L1 (HOT) L2
COOLING TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A
2
ONE TRANSFORMER SYSTEM.
3
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT PUMP SYSTEMS.
4
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE.
Fig. 5. Typical hookup in heat and cool
O
FAN RELAY
COOL DAMPER
B
2
HEAT DAMPER
HEAT RELAY
2
RW
TRANSFORMER
system with one transformer.
O
BC
3
HEAT DAMPER
HEAT RELAY
HEATING TRANSFORMER
COOL DAMPER
FAN RELAY
3
system with two transformers.
RW
OTOT
3
OUTDOOR TEMPERATURE SENSOR
L1 (HOT)
L2
4
OUTDOOR TEMPERATURE SENSOR
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
Fig. 6. Proper wiring technique.

Mounting Thermostat

1
M10353
OTOT
L1 (HOT)
L2
M10354
1. Engage tabs at the top of the thermostat and wall­plate. See Fig. 7.
2. Press lower edge of case to close and latch.
NOTES: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove top last.
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
1
B.
PRESS LOWER EDGE OF CASE TO LATCH.
Fig. 7. Mounting thermostat on wallplate.
M4826
M14628
3 69-1410—2
T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
A

Using Thermostat Keys

The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP
ND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
ENTER INDEFINITE OR TIMED HOLD MODE
SET CURRENT OR PROGRAM DAY
CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME
SET WAKE TIMES AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
SET LEAVE TIMES AND SETPOINTS
Time Set Program
Heat/Cool
Copy
Fig. 8. T8601D key locations and descriptions.

SETTINGS

System and Fan Settings

The System default setting is Heat and the Fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 9. The fan settings can be set for each program period individually. The system selection is for all the program periods.
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between
heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously. Auto: Fan operates with equipment.
• configure Installer Setup,
• check Self-Test,
• display outdoor temperature (select models),
• set the system operation,
• set the fan operation.
See Fig. 8 for the location of the keys.
SET RETURN TIMES AND SETPOINTS
Leave
Wake
Settings
DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST
Return Sleep
System Fan
Run
Set Current
Program
Hold Temp
Day
Day/Time
Daylight
Time
Time Set Program
Copy
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE
SET SLEEP TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION
CHANGE BETWEEN HEATING AND COOLING SETPOINTS
Leave
Wake
Return
Heat/Cool
System Fan
Settings
Sleep
M14625
Fig. 9. Thermostat System and Fan key locations.
NOTE: Always press the keys with your fingertip or
similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
M14624
System
Fan
69-1410—2 4
Loading...
+ 8 hidden pages