The T8601 Chronotherm® IV Deluxe Programmable
Thermostat provides electronic control of 24 Vac single-
Table 1. Description of T8601 Thermostats.
T8601 System Changeover System Selection Fan SelectionComments
DHeat-Cool AutomaticHeat-Off-Cool-AutoOn-AutoUse keyboard for system and fan selections
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the old thermostat.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
stage heating and cooling systems. Refer to Table 1 for a
general description of the thermostat. All T8601
thermostats require a common wire to supply power.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
NO
NO
[1.5 METERS]
Fig. 1. Typical location of thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall
or on a 2 in. x 4 in. wiring box. Position wallplate
horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions correctly even
when not level.
WIRES
THROUGH WALL
WALL
ANCHORS (2)
Fig. 2. Mounting the wallplate.
2. Use a pencil to mark the mounting holes. See
Fig. 2.
WALL
MOUNTING
HOLES
MOUNTING
SCREWS
M15044
YES
5 FEET
NO
M10106
3. Remove the wallplate from the wall and drill two
3/16 in. holes in the wall (if drywall) as marked. For
firmer material such as plaster, drill two 7/32 in.
holes. Gently tap anchors (provided) into the drilled
holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 through 5 for typical hookups.
A letter code is located near each terminal for
identification.
CAUTION
Electrical Hazard.
Can cause electric shock and equipment
damage.
Disconnect power before beginning wiring.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 6.
THERMOSTAT
GC
FAN
RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
Fig. 3. Typical hookup in heat only application.
HEAT
RELAY
RW
TRANSFORMER
L1
(HOT)
L2
1
M10357
69-1410—22
T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
THERMOSTAT
C
YG
COMPRESSOR
CONTACTOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
2
PUMP SYSTEMS.
3
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
SEPARATE CABLE FROM THE THERMOSTAT CABLE.
Fig. 4. Typical hookup in heat and cool
THERMOSTAT
RC
YG
2
COMPRESSOR
CONTACTOR
1
L1
(HOT)
L2
COOLING TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A
2
ONE TRANSFORMER SYSTEM.
3
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
PUMP SYSTEMS.
4
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
SEPARATE CABLE FROM THE THERMOSTAT CABLE.
Fig. 5. Typical hookup in heat and cool
O
FAN
RELAY
COOL
DAMPER
B
2
HEAT
DAMPER
HEAT
RELAY
2
RW
TRANSFORMER
system with one transformer.
O
BC
3
HEAT
DAMPER
HEAT
RELAY
HEATING TRANSFORMER
COOL
DAMPER
FAN
RELAY
3
system with two transformers.
RW
OTOT
3
OUTDOOR
TEMPERATURE
SENSOR
L1
(HOT)
L2
4
OUTDOOR
TEMPERATURE
SENSOR
FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).
FOR STRAIGHT INSERTION
STRIP 5/16 IN. (8 MM).
Fig. 6. Proper wiring technique.
Mounting Thermostat
1
M10353
OTOT
L1
(HOT)
L2
M10354
1. Engage tabs at the top of the thermostat and wallplate. See Fig. 7.
2. Press lower edge of case to close and latch.
NOTES: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; remove top
last.
A.
ENGAGE TABS
AT TOP OF
THERMOSTAT
AND WALLPLATE.
1
B.
PRESS LOWER
EDGE OF CASE
TO LATCH.
Fig. 7. Mounting thermostat on wallplate.
M4826
M14628
369-1410—2
T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
A
Using Thermostat Keys
The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
INCREASE TIME SETTING
OR SCROLL FORWARD
THROUGH INSTALLER SETUP
ND SYSTEM TEST
SET CURRENT
DAY AND TIME
RETURN TO
NORMAL
OPERATIONS
ENTER
INDEFINITE
OR TIMED
HOLD MODE
SET CURRENT OR
PROGRAM DAY
CHANGE BETWEEN
DAYLIGHT SAVINGS
AND STANDARD TIME
SET WAKE TIMES
AND SETPOINTS
Set Current
Run
Day/Time
Program
Hold Temp
Day
Daylight
Time
COPY ONE PROGRAMMED
DAY TO ANOTHER DAY
SET LEAVE TIMES
AND SETPOINTS
TimeSet Program
Heat/Cool
Copy
Fig. 8. T8601D key locations and descriptions.
SETTINGS
System and Fan Settings
The System default setting is Heat and the Fan default
setting is Auto. Use the System and Fan keys to change
the settings. See Fig. 9. The fan settings can be set for
each program period individually. The system selection is
for all the program periods.
System settings control the thermostat operation as
follows:
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between
heating and cooling operation, depending on the
indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Fan operates with equipment.
• configure Installer Setup,
• check Self-Test,
• display outdoor temperature (select models),
• set the system operation,
• set the fan operation.
See Fig. 8 for the location of the keys.
SET RETURN TIMES
AND SETPOINTS
Leave
Wake
Settings
DECREASE TIME SETTING OR
SCROLL BACKWARD THROUGH
INSTALLER SETUP AND SYSTEM TEST
ReturnSleep
SystemFan
Run
Set Current
Program
Hold Temp
Day
Day/Time
Daylight
Time
TimeSet Program
Copy
INCREASE TEMPERATURE
SETTING OR SCROLL
FORWARD THROUGH
INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE
SETTING OR SCROLL
BACKWARD THROUGH
INSTALLER SETUP OPTIONS
DISPLAY INFORMATION
SUCH AS PRESENT
SETTINGS AND OUTDOOR
TEMPERATURE
SET SLEEP TIMES
AND SETPOINTS
SELECT FAN
OPERATION
SELECT SYSTEM
OPERATION
CHANGE BETWEEN
HEATING AND COOLING
SETPOINTS
Leave
Wake
Return
Heat/Cool
System Fan
Settings
Sleep
M14625
Fig. 9. Thermostat System and Fan key locations.
NOTE: Always press the keys with your fingertip or
similar blunt tool. Sharp instruments like a pen
or pencil point can damage the keyboard.
M14624
System
Fan
69-1410—24
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.