Honeywell T7470A1009 PRODUCT DATA AND INSTALLATION INSTRUCTIONS

Space-Temperature Sensor
F
c
tric
tan
c
hms)
HONEYWELL EXCEL 5000 OPEN SYSTEM
PRODUCT DATA AND INSTALLATION INSTRUCTIONS
FEATURES
· Mountable directly on a wall.
· Operating range 43 to 104°F / 6 to 40°C.
· CE approved.
· IP 30 housing.
· Compact.
SENSOR CHARACTERISTIC
The 20 k NTC temperature sensor follows a specific temperature-resistance curve (see Fig. 1).
e (o
T7470A1009
80 K
70 K
60 K
50 K
GENERAL
The T7470A1009 is equipped with a 20 k NTC space­temperature sensor and can be directly wired to the following Honeywell controllers:
· W7750A,B
· W7751B,D,F,H
· W7752D,E,F,G
· W7753A
· W7761A
· W7762A,B
· W7763C,D,E
· Excel 600, 500, 100, 80, 50, 20.
Please refer to the technical specifications of the individual controllers in order to determine their suitability for use in conjunction with a given sensor application.
40 K
30 K
al resis
20 K
ele
10 K
30
40 50 60 70 80 90 100 110
0 10 20 30 40
temperature (degrees)
Fig. 1. Temperature vs. resistance for 20 k sensor
° °C
® U.S. Registered Trademark EN0B-0469GE51 R0604 Copyright © 2004 Honeywell Inc. • All rights reserved
T7470A1009 SPACE-TEMPERATURE SENSOR
SPECIFICATIONS
Dimensions (H 5 W 5 D): 2 5 1-9/16 5 3/4 in. (56 5 46 5 19.3 mm).
Construction: Two-piece construction (a cover and an internally wired sub-base). Field wiring 16 to 22 AWG (1.5 to
0.34 mm
2
) connects to a terminal block.
Operating Temperature: 43...104°F / 6...40°C.
Shipping Temperature: -40...150°F / -40...65°C.
Relative Humidity: 5% to 95% non-condensing.
Accuracy: Dt = 0.3 K +1% · |t - 25 °C| (t in °C)
Safety: terminal box
Protection standard: IP30
Approvals: CE
BEFORE MOUNTING
All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams.
Removing the Cover
The cover of the space-temperature sensor can be easily popped off by applying pressure simultaneous pressure to the right and left sides at the top and bottom (see Fig. 2).
2
1
Fig. 3. Wire insertion
To facilitate wire insertion, it is possible to temporarily remove the terminal block from the housing. After wire insertion, however, the terminal block should be snapped back into place.
MOUNTING
Mount the T7470A1009 on an inside wall approx. 54 in. (1.3 m) from the floor (or in the specified location) to allow exposure to the average zone temperature.
Maintain a mounting clearance of approx. 4 in. (10 cm) to both sides of the space-temperature sensor in order to allow free airflow.
Do not mount the space-temperature sensor on an outside wall, on a wall containing water pipes, or near air ducts. Avoid locations exposed to discharge air from registers or radiation from lights, appliances, or the sun.
Keep wiring at least one ft (305 mm) away from large induc­tive loads such as motors, line starters, lighting ballasts, and large power distribution panels. Run space-temperature sensor wiring separately from 50 Vac or greater power wiring.
The T7470A1009 can be mounted directly onto walls (see Fig. 4 for dimensions and drilling template), in which case the type of screws appropriate to the wall material should be used.
19.3
Fig. 2. Removing the cover
Space-temperature sensor wiring can be sized from 16 to 22 AWG (1.5 to 0.34 mm maximum length of wire from a device to the space­temperature sensor is 1000 ft (305 m). Twisted-pair wire is
2
), depending on the application. The
56
32.7
ABS
recommended for wire runs longer than 100 ft (30.5 m).
Wire Insertion
After removing the cover, the wires can be easily inserted into the terminal block as shown in Fig. 3. The terminals are insensitive to polarity.
Automation and Control Solutions
Honeywell GmbH Böblinger Strabe 17 D-71101 Schönaich Phone xx49-(0)7031-637-01 Fax xx49-(0)7031-637-493 Manufacturing location
46
Fig. 4. T7470A1009 dimensions (in mm)
27.8
http://europe.hbc.honeywell.com is certified to
3.25
4.5
50
40
EN0B-0469GE51 R0604