Honeywell T7460H User Manual

INSTALLATION AND OPERATING INSTRUCTIONS
T7460H SETPOINT SELECTOR
DESCRIPTION
MCR 35, 36, 40, 200
DHC 23
Excel 500
Not for MCR 200-61 large installations and MCR 200-62.
INSTALLATION OF THE T7460H
Figure 1: Locations for installation
1. Remove housing cover of the setpoint selector.
Figure 2: Removing housing cover
® U.S. Registered Trademark EN1H-0154GE51 R0508
Copyright © 2008 Honeywell Inc. • All Rights Reserved.
T7460H – Installation and Operating Instructions
2. Screw setpoint adjuster to the under plaster distribution box.
Figure 3: Dimensions of housing
3. Connect the cable coming from the controller.
Figure 4: Wiring diagram
Wiring of the terminals:
1 Setpoint 4 not used 2 + 10 V 5 Room sensor 3 Gnd 6 LED
4. Return cover to housing by placing top edge against back­plate and snap lower part of cover onto housing (2).
Figure 5: Replacing of housing cover
EN1H-0154GE51 R0508
T7460H – Installation and Operating Instructions
OPERATION AND FUNCTIONS
Figure 6: Operating devices and indicators
1 Operating mode switch
2 LED (error indicator)
3 Temperature selector with scale
4 Temperature sensor (to the side)
T7460H in operation with systems MCR 35, 36, 40, 200, DHC 23 and EXCEL 500
Operating mode switch
The operating mode switch allows for the selection of three different functions:
Position Operating
mode
Auto
Automatic Heating is controlled by timer.
Daytime Only desired value for day applies.
Switch-off Heating is switched off. In the event of
Note
The operating mode switch of the T7460H does not in any way influence the domestic hot water program.
Temperature selector
The desired value can be changed only if the operating mode switch is set to positions Auto or respectively.
Range: –7...+7 °C
Mid-point position: 0 °C (in relation to controller settings)
Function
danger of frost, the heating pump and the burner are automatically switched on.
LED
Function in operation with MCR 200: The LED is on if the controller has detected an error.
The LED may also be used with other systems. The input voltage is 5 – 24 V AC or DC.
EN1H-0154GE51 R0508
T7460H – Installation and Operating Instructions
T7460H in operation with Excel 500 System
If the T7460H is operated with the Excel 500 System, the tem­perature range and options of the operating mode switch can be chosen to suit your needs.
In such an installation, the feedback control system of the Excel System provides information on the current configuration of the switch.
TECHNICAL DATA
Sensor device: NTC thermistor Resistance: 20 kOhm at 25 °C Temperature range: 6...40 °C Dimensions (H×W×D): 103 × 98 × 28 mm Installation: Installation on wall or on standard 60 mm distribution box Max. operating
temperature / humidity: 0...50 °C / 5...95% humidity Max. storage temperature / humidity: –35...+70 °C / 5...95% humidity Electric connection: Terminals for max. 1.0 mm
wire diameter Protection class: IP 30, DIN 40 050
or IEC 144
Technical data regarding the NTC thermistor: see publication EN0B-0476GE51.
2
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich / Germany Phone: (49) 7031 637 01 Fax: (49) 7031 637 493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
7157408 EN1H-0154GE51 R0508