OUTSIDE AIR TEMPERATURE SENSOR
PRODUCT DATA

FEATURES

Available with different temperature sensing element: Pt 1000, NTC 20kΩΩΩ and NTC 10kΩΩΩΩ
Wide sensing range
High accuracy

Models

OS-No. Description
T7416A1014 OAT sensor with Pt 1000 sensing
T7416A1022 OAT sensor with NTC 20k sensing
T7416A1030 OAT sensor with NTC 10k sensing
element
element
element

SPECIFICATIONS

GENERAL

The T7416A outside air temperature sensor is used in heating, ventilating and air conditioning systems for reset of the main setpoint in weather dependent control systems. They are designed for wall mounting. The Outside Air Temperature Sensors are used in the following control systems
Excel Classic
Excel Plus
High Performance Excel Plus
Excel EMC
Excel 5000
MicroniK 100 and MicroniK 200
or other systems using the specified temperature sensing elements. The resistor sensing element changes its resistance value according to the temperature.
Temperature Sensor
Sensing Element
Pt 1000 1000 @ 0°C 3.85 / K DIN IEC751 Class B
NTC 20k 20 k @ 25°C nonlinear NTC 10k
Temperature Sensing
Range
-40 .... +70°C (-40 ...+158°F)
Nominal Value Sensitivity Accuracy Responce
10 k @ 25°C Charact.
Ambient Limits
Transport and -40 .... +70°C (-40 ...+158°F)
storage temperature Humidity 5...95%rh, non condensing
Safety
Protection standard IP54 in acc. with EN60529 terminal box and tube
Dimensions See page 2 Weight 60 g
T/K = 0.3 + 0.005 t (t = °C)
0.2 K @ 25°C
Time τ
7 min
τ
ττ
0.5
(43165863-172) EN0B-1005GE02 R0300
T7416A
y
r

DIMENSIONS

49
(1.93)
72
(2.8)
=
3,5
Case hole dia. Allows Pg9 cable entry
Mounting holes
53
(2.09)
37
(1.47)
l
l e w
y e
n o H
38
(1.50)

INSTALLATION

Wiring Run Maximum Length
Sensor to controller 200m (660ft)
Offset of Pt 1000 sensor due to wire resistance per 10m distance from sensor to controller; NTC sensor negligible:
Type of Wire Temperature Offset
0.5mm2 (AWG20) 0.18°C (0.324°F)
1.0mm2 (AWG17) 0.09°C (0.162°F)
1.5mm2 (AWG15) 0.06°C (0.108°F)
NOTE: Use shielded wiring in areas with high EMI.
Keep 15cm (5.9’’) minimum distance between sensor lines and 230Vac power lines.
Home and Building Control Products
Honeywell AG Böblinger Straβe 17 D-71101 Schönaich Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://europe.hbc.honeywell.com
Dimension s in m m an d ( inch)
senso
terminal
cable entr
Subject to change without notice. Printed in Germany Manufacturing location certi fied to
EN0B-1005GE02 R0300