T7415A / KTF20 / DKF20
CABLE-TYPE BULB TEMPERATURE SENSORS
Fig. 1. The KTF20
GENERAL
The T7415A//KTF2/DKF20 Cable-type Bulb Temperature Sensor can be used as
•immersion sensors
•return air sensors
The sensors can be employed for hot and cold water installations in the following control systems:
•Excel 5000
•MicroniK 200
•MicroniK 100
•Excel Classic
•Excel Plus
•High Performance Excel Plus
•Excel EMC
or other systems using PT1000 or NTC 20kΩ temperature sensing elements.
PRODUCT DATA
FEATURES
•PT1000 or NTC 20kΩ temperature sensing element
•Wide sensing range
•High accuracy
Models
OS no. |
|
description |
sensing range |
T7415A1007 |
|
Cable-type Bulb PT1000 |
-20...+100 °C |
|
Temperature Sensor |
(-4...+212 °F) |
|
|
|
||
T7415A1015 |
|
Cable-type Bulb PT1000 |
-20...+300 °C |
|
Temperature Sensor |
(-4...+572 °F) |
|
|
|
||
KTF20 |
|
Cable-type Bulb NTC20kΩ |
-20...+100 °C |
|
Temperature Sensor |
(-4...+212 °F) |
|
|
|
||
DKF20 |
|
Cable-type Bulb NTC20kΩ |
-20...+100 °C |
|
Mean value Sensor |
(-4...+212 °F) |
|
|
|
||
KTF20-B |
|
Bulk shipment of 50 KTF20 |
see above |
SPECIFICATION
Nominal value |
|
|
PT1000 |
1000 Ω at 0 °C |
|
NTC20kΩ |
20 kΩ at 25 °C |
|
Accuracy |
|
|
PT1000 |
IEC751 Class B |
|
|
0.3 K +0.5% • |t| (t in °C) |
|
NTC20kΩ |
0.3 K at 25 °C |
|
Sensitivity |
|
|
PT1000 |
≈ 3.85 Ω / K |
|
NTC20kΩ |
≈ -934.5 Ω / K at 25 °C (non-linear) |
|
Response time |
τ0.5 |
|
immersion well app. |
≈ 10 s |
|
duct application |
τ0.5 |
≈ 2 min at air velocity |
of 1 m/s (3.3 ft/s)
Electrical connection
T7415A/KTF20 |
2 m cable, 2-core |
DKF20 |
2 m cable, 3-core |
Ambient Limits (wiring box) |
|
Storage temperature |
-25...+70 °C (-13…+158 °F) |
Humidity |
5…95% rh, non-condensing |
Safety |
IP64 as per EN 60529 |
Dimensions |
see Fig. 2 on page 2 |
® U.S. Registered Trademark |
|
EN0B-0362GE51 R0907 |
Copyright © 2007 Honeywell Inc. • All rights reserved |
|
|
|
|
T7415A / KTF20 / DKF20 CABLE-TYPE BULB TEMPERATURE SENSORS
DIMENSIONS
Cable-Type Bulb Sensor
6.5 |
brass bulb |
PVC cable with identifier |
(0.26”) |
|
|
|
|
6 |
|
60.5 (2.38”) |
(0.24”) |
|
30 (1.18”) |
|
|
2000 (78.74”) |
Fig. 2. Dimensions of the cable-type bulb sensor in mm (inches)
INSTALLATION
wiring run |
max. length |
Sensor to controller |
200 m (660 ft) |
|
|
Offset due to wire resistance per 10 m of distance from sensor to controller, when using the T7415A (PT100):
type of wire |
temperature offset PT100 |
|
0.5 mm2 |
(AWG20) |
0.18 °C (0.324 °F) |
1.0 mm2 |
(AWG17) |
0.09 °C (0.162 °F) |
1.5 mm2 |
(AWG15) |
0.06 °C (0.108 °F) |
WIRING OF DKF20
controller no. 1
controller no. 2
brown (1) |
green (2) |
white (3) |
INSTALLATION OF KTF20/DKF20
Fig. 3. KTF20 / DKF20 mounting into the immersion well
NOTE: Use shielded wiring in areas with high EMI. Keep 15 cm (5.9’’) minimum distance between sensor lines and 230 Vac power lines.
Fig. 4. Sensor branching for two separate controllers with DKF20 Fig. 5. Averaging with 2 x DKF20
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Straβe 17
D-71101 Schönaich
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0362GE51 R0907