T7414C
STRAP-ON/OUTSIDE TEMPERATURE SENSOR
PRODUCT DATA
FEATURES
T7414C outdoor-mounted
T7414C strap-on
GENERAL
The Strap-on Temperature Sensor is used to detect the supply or return water flow temperature on the pipe work.
The Outside Air Temperature Sensor is used in heating, ventilating and air conditioning systems to detect the outside temperature for reset of the main setpoint in weatherdependent control systems.
MODELS
|
OS-No. |
|
type / sensing |
|
mounted using |
|
|
|
element |
|
|
||
|
|
|
|
|
|
|
|
T7414C1004 |
strap-on / |
|
clamp band / |
||
|
outdoor / Pt1000 |
|
screws |
|||
|
|
|
|
|||
|
T7414C1012 |
strap-on / |
|
clamp band / |
||
|
outdoor / NTC20 |
|
screws |
|||
|
|
|
|
•Pt1000 / NTC20 temperature sensing element
•Small size
•Easy mounting
•Fully encapsulated housing
SPECIFICATIONS
Ambient limits |
|
Operating temperature |
|
- Strap-on |
-30...+110 °C (-22...+230 °F) |
- Outdoor |
-30...+70 °C (-22...+158 °F) |
Transport / storage temp. |
-30...+70 °C (-22...+158 °F) |
Humidity |
5...95%rh, non-condensing |
Safety |
|
Protection standard |
IP65 as per EN60529 |
Flame-retardant housing |
V1 as per UL94 |
Housing |
Plastic |
Dimensions |
See page 2 |
Weight |
60 g |
Mounting |
Pipe and wall |
Cable length |
approx. 1 m |
Temperature sensor |
|
Sensing element |
Pt1000, NTC20kΩ |
Sensing range |
-30...+110°C (-22...+230°F) |
- Strap-on |
|
- Outdoor |
-30...+70°C (-22...+158°F) |
Response time |
τ0.5 ≈ 36 s |
- Strap-on Pt1000 |
|
- Strap-on NTC20kΩ |
τ0.5 ≈ 45 s |
- Outdoor Pt1000 |
τ0.5 ≈ 240 s |
- Outdoor NTC20kΩ |
τ0.5 ≈ 300 s |
Sensitivity |
|
-Pt1000 |
≈ 3.85Ω / K |
-NTC20kΩ |
20 kΩ at 25 °C, non-linear |
Accuracy |
|
- Pt1000 |
DIN IEC751 Class B |
|
∆T/K = 0.3 + 0.005 • t (t = °C) |
- NTC20kΩ |
0,3 K at 25 °C |
Resistance |
|
-Pt1000 |
1000Ω at 0 °C |
-NTC20kΩ |
20kΩ at 25 °C |
® U.S. Registered Trademark |
|
EN0B-0475GE51 R0907 |
Copyright © 2007 Honeywell Inc. • All rights reserved |
|
|
|
|
T7414C STRAP-ON /OUTSIDE TEMPERATURE SENSOR
DIMENSIONS
20
5
48
7.3 15
18.5 |
|
|
|
18.5 |
|
|
|
18.5 |
|
|
|
|
50
Fig. 1. Dimensions (in mm)
MOUNTING AND INSTALLATION
OUTDOOR
The outdoor air temperature sensor should be mounted on the wall of buildings having windows of the main occupancy rooms or on the coldest side (N-NW side).
It should not be subjected to direct sunshine and be mounted on an open facade so that it can detect all weather conditions.
The mounting height should be 2/3 of the way up wall on up to three-story buildings or between the second or third floor on taller buildings.
Avoid mounting the sensor above windows, doors, air extractors or other heat sources, under a balcony, the eaves, or in a wall niche.
The cable conduit through the wall must be sealed to prevent measurement errors by warm air circulation.
Fasten the sensor with the two supplied screws at the selected place on the wall as shown in Fig. 2.
Fig. 2. T7414C outdoor-mounted
STRAP-ON
The strap-on temperature sensor consists of a sensor housing and a clamp band with an adjustable lock for mounting on pipes up to a diameter of 28 mm.
The sensor is equipped with a 1 m-long two-lead connecting cable.
The strap-on sensor must be mounted onto the water pipe with the clamp band at a minimum distance of 1.5 m from the mixing valve. Avoid mounting the sensor near heat sources, as its measurement could then be influenced by warm air circulation. Fasten the sensor as shown in Fig. 3.
Fig. 3. T7414C strap-on mounted
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Straβe 17
D-71101 Schönaich
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0475GE51 R0907