The Honeywell TRADELINE® SmartValveTM System
Controls provide easy field replacement of a wide range
of SV9500, SV9501, SV9502 and SV9602 SmartValve
System models. Gas appliance manufacturers use these
models in many types of gas fired heating appliances
including central furnaces, residential boilers, rooftop
furnaces, commercial cooking appliances, and unit
heaters. These TRADELINE® controls provide
intermittent pilot gas ignition sequencing, pilot flame
sensing, and both pilot and main gas control functions in
a single control. They are directly compatible with the
Q3450 or Q3480 Intermittent Pilot burners used with the
original controls on the appliance.
The TRADELINE® SV9501 and SV9502 SmartValve
models are replacement controls only for the SV9500,
SV9501, and SV9502 models noted in Table 5. Do not
use these controls to replace other types of intermittent
pilot or direct ignition controls. Do not use these controls
to replace SmartValve
Replacement table. The controls might fit, but the gas
flow control functions might not be compatible with the
appliance.
The TRADELINE® SV9602 SmartValve
replacement controls only for the SV9500P, SV9501P,
SV9502P, SV9600P and SV9601P models noted in Table
5. The SV9602 is a prepurge, step-opening model.
IMPORTANT
Do not use these controls to replace
SmartValve
replacement table.
Prepurge is nominally 30 seconds.
The step opening function provides a timed step outlet
pressure at the start of each heating cycle to allow main
burner ignition at reduced outlet pressure.
Reducer bushings are provided with the SV9602 and
SV9601 models for adapting to smaller pipe sizes.
TM
models not listed in the
TM
models not listed in the
System Control
INSTALLATION INSTRUCTIONS
IMPORTANT
Carefully determine the full Honeywell model
number of the existing control. Use Table 4 or
Table 5 to make sure the replacement control
model is suitable for replacing the original
control. If the control is not suitable, obtain the
correct TRADELINE® replacement control as
shown in Table 4 or Table 5, or contact the
appliance manufacturer for the proper
replacement control.
INSTALLATION
When Installing this Product…
1. Read this instructions carefully. Failure to follow
the instructions as written can damage the product
or cause a hazardous situation.
2. Check the relevant chart and the ratings given in
these instructions and on the specific model to
make sure the product is suitable for the
application.
3. Installer must be a trained, experienced, licensed
(if required by local ordinance) technician.
4. Use these instructions to check product operation
after completing installation.
IMPORTANT
Make sure the control being replaced is
defective. See Fig. 13 through 16 for SV9500,
SV9501, and SV9502 Sequence of Operation
and Troubleshooting procedures.
Planning the Installation
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow these warnings exactly as written.
1. Plan the installation as outlined in this section.
2. Plan for frequent maintenance as described in
the Maintenance section of this manual.
Intermittent pilot systems used on heating equipment in
barns, greenhouses, and commercial properties, and on
heating appliances such as commercial cookers,
agricultural equipment, and pool heaters make heavy
TM
models are
TM
TM
69-1270-3
SV9501/SV9502/SV9601/SV9602 SMARTVALVE
TM
SYSTEM CONTROL
demands on the controls. Special steps are
recommended to prevent nuisance shutdowns and control
failures due to frequent cycling, or severe environmental
conditions such as exposure to moisture, corrosive
chemicals, dust, or excessive heat. Following are the
possible causes of shutdown and the preventative
solutions.
Frequent Cycling
These controls are designed to cycle three to four times
each hour during the heating season. Year around
applications and applications with more frequent cycling
rates can wear out controls more quickly than normal
operation. Perform monthly system checks to make sure
the system operates properly.
Water or Steam Cleaning
Replace any electronic control that gets wet. If the
appliance is likely to be cleaned with water or steam,
cover the control and wiring to protect them from water or
steam flow. Mount the control high enough above the
cabinet bottom to avoid getting it wet during cleaning
procedures.
High Humidity or Dripping Water
Dripping water can cause the control to fail. Never install
an appliance where water can drip on the control. High
humidity around the control can cause the control to
corrode and fail. If the appliance is located in a humid
atmosphere, make sure the air circulation around the
control is adequate to prevent water condensing on the
control. Check the system regularly for signs of
condensation and corrosion.
Corrosive Chemicals
Corrosive chemicals can erode the control, eventually
causing a failure. If chemicals are used for routine
cleaning, make sure they do not touch the control. Where
chemicals are suspended in air, for example, in some
industrial or agricultural applications, protect the control
with an enclosure.
Dust or Grease Accumulation
Heavy accumulations of dust or grease can cause the
control to malfunction. Where dust or grease are
problems, cover the control to limit contamination.
Installation
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow these warnings exactly as written.
1. Disconnect the power supply before wiring to
prevent electrical shock and equipment
damage.
2. Turn of the gas supply at the appliance service
valve before starting installation to avoid
dangerous accumulation of fuel gas.
3. Perform gas leak test after completing
installation.
4. Do not bend pilot tubing at ignition system
control or pilot burner after tightening the
compression fitting. Bending can cause gas
leakage at the connection.
5. Always install a sediment trap in the gas supply
line to prevent contamination of the ignition
system.
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow this warning exactly as written.
• Always change the main and pilot burner
orifices when converting between LP and
natural gas. Follow appliance manufacturer
specifications and instructions.
CAUTION
Equipment Damage Hazard.
Improper device replacement will damage the
equipment.
The SV9501, SV9502, SV9602, and SV9601
provide direct replacement only as shown in Table
4 or Table 5 of this manual. Use the Y8610 to
convert standing pilot systems to electronic
ignition systems.
Heat
Excessively high (above 175°F [79°C]) temperatures can
damage the control. Make sure the ambient temperature
at the control does not exceed the control rating. If the
appliance operates at very high temperatures, use
insulation, shielding and proper air circulation as
necessary to protect the control. The appliance
manufacturer should provide proper insulation or
shielding. Make sure there is proper air circulation when
installing the appliance.
69-1270—32
CAUTION
Equipment Damage Hazard.
Can Burn Out Heat Anticipator in Thermostat.
1. Never apply a jumper across or short the
terminals in the SV9501, SV9502, SV9602, or
SV9601 connectors or appliance wiring
harnesses.
2. Never short the electric fan timer (EFT) output.
Shorting the output can damage the EFT drive
circuitry.
IMPORTANT
These ignition system controls are shipped with
protective seals over inlet and outlet tappings.
Do not remove seals until ready to connect
piping.
Follow the appliance manufacturer’s instructions if
available. Otherwise, use these instructions as a guide.
SV9501/SV9502/SV9601/SV9602 SMARTVALVE
TM
SYSTEM CONTROL
Ignition system controls are set at the factory for natural
or LP gas. Do not attempt to use an ignition control made
for LP gas on a natural gas system. Do not attempt to use
an ignition control made for natural gas on an LP gas
system.
Ignition system controls with standard opening regulators
(SV9501M, SV9502M, and SV9601M) or slow opening
regulators (SV9501H and SV9502H) can be converted
between natural gas and LP gas.
Ignition system controls with step opening regulators (P
suffix) cannot be converted between gases.
Selecting the Valve
Make sure when replacing any SmartValveTM that you
know what valve is going in and what valve is coming out.
The SV9501 and SV9502 look slightly different from the
SV9500. The SV9500 features an ON/OFF control knob,
as shown in Fig. 1. The SV9501, SV9502, SV9602, and
SV9601 have an ON/OFF switch, as shown in Fig. 2. The
SV9501, SV9502, SV9601, and SV9602 have a
connector located at the top of the valve instead of on the
front.
The SV9501, SV9502, SV9602, and SV9601 have
identical valve body features and use the same
connectors.
NOTE: The SV9601 and the SV9602 do not have flange
mounting capability.
Use of Pipe Adapters
In some field service applications, space limitations make
it difficult or impossible to thread the gas control onto the
gas supply line. This problem can be resolved for many
installations by using a pipe adapter. Install the pipe
adapter on the end of the supply line in place of the gas
control by following the same precautions and instructions
that are used for installing the gas control. After the pipe
adapter is installed, attach the gas control to the adapter.
NOTE: Using a pipe adapter increases the overall length
of the gas control.
Install Pipe Adapter to Gas Control
Install adapter to gas control as follows:
Bushings
1. Remove seal over gas control inlet or outlet.
2. Apply moderate amount of good quality pipe com-
pound to bushing, leaving two end threads bare.
3. Insert bushing into gas control and carefully thread
pipe into the bushing until tight.
Installing Flange Adapters to Control
(If Required)
Mount any necessary adapters as follows:
Flanges
1. Choose the correct flange for the application.
2. Remove the seal over the ignition system control or
outlet.
3. Make sure the O-ring is fitted in the flange groove. If
the O-ring is not attached or is missing, do not use
the flange.
4. With the O-ring facing the ignition system control,
align the screw holes on the ignition system control
with the holes in the flange.
5. Insert the screws provided with the flange.
6. Tighten the screws firmly but do not over tighten
VALVE OUTLET
FLANGE
9/64 INCH HEX SCREWS (4)
Fig. 1. Front view of SV9500. Notice the ON/OFF
control knob.
M3342A
Location
Mount the SV9501, SV9502, SV9602, or SV9601 on the
gas manifold in the appliance.
Installing Piping to Control
IMPORTANT
Do not use Teflon® tape.
All piping must comply with local codes or ordinances or
with the National Fuel Gas Code (ANSI Z223.1 NFPA No.
54), whichever applies. Tubing installation must comply
with approved standards and practices.
1. Use new, properly reamed pipe that has no chips.
2. Make sure the ends are square, deburred, and
clean.
3. Make sure all tubing bends are smooth and without
deformation.
4. Get a tube-to-pipe coupling if necessary.
5. Run pipe or tubing to the ignition system control.
6. Install a sediment trap in the supply line to the
ignition system control as shown in Fig. 3.
369-1270—3
SV9501/SV9502/SV9601/SV9602 SMARTVALVE
TM
SYSTEM CONTROL
VALVE OUTLET
M17142
Fig. 2. Front view of SV9501 or SV9502. Notice the
connectors and the ON/OFF control switch.
FLANGE
9/64 INCH HEX SCREWS (4)
Installing the Control
This ignition system can be mounted from 0 to 90 degrees
in any direction including vertically from the upright
position of the ignition system control switch.
IMPORTANT
Make sure to mount the replacement control
in the same location and orientation as the
original control.
1. Mount the control so the gas flow is in the direction
of the arrow on the bottom of the ignition system
control, as shown in Fig. 4.
2. Apply a moderate amount of good quality pipe compound to the pipe, leaving the two end threads bare,
as shown in Fig. 5. For LP controls make sure to
use an LP resistant pipe compound.
3. Remove the seals over the ignition system control
inlet and outlet if necessary.
4. Thread the pipe the amount shown in Table 1. Do
not thread the pipe too far, because this could
cause valve distortion or malfunction.
5. Using a wrench on the square ends of the ignition
system control, connect the pipe to the ignition
system control inlet and outlet.
DROP
HORIZONTAL
3 IN.
(76 MM)
MINIMUM
HORIZONTAL
RISER
3 IN.
(76 MM)
MINIMUM
1
ALL BENDS IN METALLIC TUBING MUST BE SMOOTH.
CAUTION
Gas Leakage Hazard.
Failure to follow precautions can result in a gas-filled work area.
Shut off the main gas supply before removing end cap. Test for gas
leakage when installation is complete.
PIPED
GAS
SUPPLY
IGNITION
SYSTEM
CONTROL
DROP
TUBING
1
GAS
SUPPLY
IGNITION
SYSTEM
CONTROL
RISER
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
IGNITION
SYSTEM
CONTROL
M3343C
Fig. 3. Sediment trap installation.
PRESSURE REGULATOR
ADJUSTMENT (UNDER
CAP SCREW)
INLET
PRESSURE
TAP
ON
OFF
CONTROL
CONTROLS
CONNECTOR
IGNITER
INLET
IGNITION SYSTEM
CONTROL SWITCH
M7934
Fig. 4. Mount so gas flows in the
direction of the arrows.
NOTE: If the control has a flange, place the wrench on
the flange instead of on the ignition system control, as shown in Fig. 6.
IGNITER
CONNECTOR
OUTLET
PRESSURE
TAP
OUTLET
PILOT
OUTLET
PILOT ADJUSTMENT
(UNDER CAP SCREW)
Table 1. Threading the Pipe.
Maximum Depth Pipe
can be Inserted into
Control
Pipe Size
Thread Pipe
this Amount
3/8 in.9/16 in.3/8 in.
1/2 in.3/4 in.1/2 in.
3/4 in.13/16 in.3/4 in.
69-1270—34
SV9501/SV9502/SV9601/SV9602 SMARTVALVE
TWO
IMPERFECT
THREADS
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR INSERTION
INTO IGNITION SYSTEM CONTROL
IGNITION
SYSTEM
CONTROL
PIPE
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND ONLY TO PIPE
(LEAVE TWO END THREADS BARE).
Fig. 5. Use a moderate amount of pipe compound.
Connecting the Pilot Gas Tubing
NOTE:
1.The pilot tubing provides the SmartValve
system’s flame sense current path. Make
sure the connections are clean and tight.
2.Do not make sharp bends or deform the
tubing. Do not bend tubing at the ignition
system control after the compression nut is
tightened, because this can cause gas
leakage.
1. Cut the tubing to the desired length.
2. Bend the tubing as necessary for routing to the pilot
burner.
3. Square off and debur the end of the tubing.
TM
4. Unscrew the brass compression fitting from the pilot
outlet.
5. Slip the fitting over the tubing and out of the way.
6. Push the tubing into the pilot gas outlet.
7. Tap the outlet end of the control.
8. Remove and discard the old fitting.
While holding tubing all the way in, slide the new fit-
9.
ting (included with the new SmartValve
and begin thread until finger tight as shown in Fig. 7.
10. Tighten fitting one more full turn with the wrench.
M3344
Do not overtighten.
11. Connect the other end of the tubing to the pilot
burner as described in the instructions supplied with
Q3450 or Q3480 pilot hardware.
Wiring
Follow the wiring instructions supplied by the appliance
TM
manufacturer if available. Otherwise, use the following
general instructions.
NOTE:
1.In most cases, connect the wiring by plugging
the appliance wiring harness connector into
the SmartValve
sion harness if necessary.
2.Where the general instructions are different
from the appliance manufacturer ’s instructions, use the appliance manufacturer’s
instructions.
TM
. Use the supplied exten-
SYSTEM CONTROL
TM
) into place
WHEN FLANGE IS NOT USED
APPLY WRENCH FROM TOP OR
BOTTOM OF IGNITION SYSTEM
CONTROL TO EITHER SHADED AREA
Fig. 6. Proper use of wrench on ignition system control with and without flanges.
IGNITION SYSTEM CONTROL
TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT
FITTING BREAKS OFF AND CLINCHES
TUBING AS NUT IS TIGHTENED
Fig. 7. Tighten new fitting and nut.
Always use a new compression fitting.
TO PILOT
BURNER
M3346
WHEN FLANGE IS USED
APPLY WRENCH
TO FLANGE ONLY
CAUTION
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Disconnect the power supply before making wiring
connections.
IMPORTANT
All wiring must comply with applicable electrical
codes and ordinances.
M7928
569-1270—3
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.