The RTH111/RTH221 thermostats can be used to control:
• a gas, oil or electric furnace — 2 or 3 wires
• a central air conditioner — 2 or 3 wires
• a hot water system (steam or gravity) with or without pump — 2 wires
• a millivolt system — 2 wires
• a central heating system with air conditioning — 4 or 5 wires
NOTE: This thermostat is not compatible with heat pumps or
multi-stage systems.
Introduction
Installation
CAUTION: ELECTRICAL HAZARD
Can cause electric shock or equipment damage.
Disconnect power before beginning installation.
2.1Removing the old thermostat
IN ORDER TO AVOID ANY RISK OF ELECTRIC SHOCK, CUT
POWER TO THE HEATING SYSTEM.
Remove the old thermostat to access the wires.
WARNING: If the old thermostat was mounted onto an electrical
box, it might have been powered by 120/240 volts. In this case,
this thermostat cannot be used. If you are unsure of the voltage
supplied to your thermostat, contact an electrician.
Identify and label each wire (with the corresponding letter on the
thermostat terminal) and remove it from the terminal.
NOTE 1: Ignore wire colors, use only letter designations to
identify wire types.
NOTE 2: If any wires are not attached to the terminals of your old
thermostat, you do not need to label them as they will not be
connected to your new thermostat.
If necessary, strip the end of each wire (maximum of 1/4 inch).
Wrap the loose wires around a pencil to
prevent them from falling into the wall.
If the hole in the wall is too big, insulate it
using a non-flammable material to avoid air
draughts behind the thermostat.
MERCURY NOTICE
If this product is replacing a control that contains mercury
in a sealed tube, do not place the old control in the trash.
Contact your local waste management authority for
instructions regarding recycling and proper disposal.
1.
NOTE: Levelling is for esthetics only and will not affect the
performance of the thermostat.
Drill holes at the marked positions and insert supplied wall
anchors.
Pass the wires through the large opening at the bottom center of
the wallplate as per Figure 2.
Secure the wallplate to the wall with supplied mounting screws
as per Figure 3.
2.
2.3Wiring
It is important that you match the wire labels with the corresponding
terminals on the thermostat.
NOTE: Depending on your system, you might not need to connect to
all terminals.
Remove the jumper wire between Rh and Rc terminals if you have
both Rh and Rc wires as shown in the following illustration.
If a wire label does not match a terminal designation on the thermostat, refer to the following illustration to find the corresponding alternate wire label.
2.2Wallplate installation
Loosen the locking screw at the bottom of the thermostat. Note
the screw is captive and cannot be removed from the wallplate.
Do not connect wires identified as C, C1, X or B as these
wires are not used with this thermostat. Wrap the bare
end of these wires with electrical tape, so they cannot
touch and short out other wires.
Separate the thermostat from the wallplate as per Figure 1.
Position the wallplate against the wall and mark hole positions
with a pencil.
RT H111/ RTH 221 1/8
69-2060EFS-02
2.4Fan operation setting
Function
number
Option
number
NOTE: This setting is not applicable if there is no fan connected to
the G terminal.
The jumper is located on the back of the thermostat faceplate. It
determines how the fan operates when placed in Automatic mode.
• HG (factory setting): Leave the jumper in this position for gas or oil
heating systems. In this position, the heating system controls the
fan operation and activates the fan only when the plenum air is
sufficiently warm.
• HE: Place the jumper to this position for electric heating systems.
In this position, the thermostat activates the fan only when there is
a call for heat.
Incorrect jumper setting:
• Incorrect HE setting in a gas or oil heating system: When
heating starts, you will initially feel cold air coming out of the vents
as the fan is running before the furnace has enough time to heat
up the air.
• Incorrect HG setting in an electric heating system: The fan will
not run when heating is activated.
2.5Battery installation
Install two AAA batteries on the back of the thermostat
faceplate as shown.
2.6Thermostat mounting
Align the two brackets on the top of the
thermostat with the corresponding slots on the
top of the wallplate.
Push the faceplate against the wallplate.
Tighten the screw at the bottom of the
thermostat.
Follow the procedure below to personalize
and configure the thermostat according to the
heating/cooling system.
Configuration menu
Press and simultaneously (for
three seconds) until the display appears
as shown on the right.
Press or to change the option.
Press and for one second to advance to the next function.
When the last function is displayed, press and for three
seconds to save any changes and exit the menu.
NOTE: If you do not press any button for 60 seconds while you are in
the setup menu, the thermostat automatically saves any changes
made and exits the menu. For the RTH221 programmable model
only, at any time you can save the changes and exit by pressing the
Run button.
Function
Temperature
1
display format
Time display
2
3
1
Applies to RTH221 programmable model only.
2
The cooling cycle is fixed at 3 cycles per hour.
1
format
Heating cycles
per hour
2
Default
setting
0
0
5
Options
0: Fahrenheit
1: Celsius
0: 12-hour display
1: 24-hour display
• 1: 60 min (steam, gravity)
• 3: 20 min (hot water, 90%+
high-efficiency furnace)
• 5: 12 min (gas or oil)
• 9: 6.7 min (electric)
3.
RT H111/ RTH 221 2/8
Figure 1
Figure 2
Figure 3
cavalier
Rh, 4 ou V
R
W1 ou H
Y1 ou M
F
RTH111/RTH221
Guide d’installation
Thermostats programmable et non programmable
Les thermostats programmables RTH111/RTH221 peuvent servir à
commander les appareils suivants :
• Fournaise au gaz, mazout, électrique — 2 ou 3 fils
• Climatiseur central — 2 ou 3 fils
• Chauffage à eau chaude (vapeur ou gravité) avec ou sans pompe — 2 fils
• Système millivolts — 2 fils
• Chauffage central avec climatisation — 4 ou 5 fils
REMARQUE : Ce thermostat n'est pas compatible avec les
thermopompes ou les systèmes multi-étages.
Introduction
Installation
MISE EN GARDE : RISQUE DE CHOC ÉLECTRIQUE
Peut provoquer des chocs électriques ou endommager le
matériel. Couper l’alimentation électrique avant
d’effectuer le raccordement.
2.1Retirer l'ancien thermostat
POUR ÉVITER TOUT RISQUE DE CHOC ÉLECTRIQUE, COUPER
L'ALIMENTATION DU SYSTÈME DE CHAUFFAGE.
Retirer l'ancien thermostat pour accéder aux fils.
MISE EN GARDE : Si l'ancien thermostat était installé sur une
boîte électrique, il pourrait avoir été alimenté par du 120/240
volts. Dans ce cas, le nouveau thermostat ne convient pas. Si
vous n’êtes pas certain de la tension d’alimentation, consulter un
électricien.
Identifier et étiqueter chaque fil (avec la lettre de la borne
correspondante) et débrancher les fils des bornes.
REMARQUE 1 : Ne pas tenir compte de la couleur des fils;
utiliser les lettres pour identifier les types de fil.
REMARQUE 2 : Si des fils ne sont pas branchés aux bornes de
l’ancien thermostat, il n’est pas nécessaire de les étiqueter,
puisque vous n’aurez pas à les brancher au nouveau
thermostat.
Au besoin, dénuder l'extrémité de chacun des fils (maximum de
6 mm).
Enrouler les fils autour d'un crayon pour les
empêcher de glisser à l’intérieur du mur.
Si l'ouverture dans le mur est trop grande,
l'isoler au moyen d'un matériau
ininflammable pour éviter tout courant d'air
derrière le thermostat.
AVIS SUR LE MERCURE
Si le nouveau thermostat remplace un ancien régulateur
contenant un contact à mercure, ne pas jeter l’ancien
régulateur à la poubelle. Communiquer avec le service local
de cueillette des déchets pour obtenir de l’information sur le
recyclage ou sur la bonne façon de se débarrasser d’un
ancien régulateur contenant un contact à mercure.
1.
2.2Installation de la plaque murale
Desserrer la vis de blocage au bas du thermostat. Noter que la
vis est captive et ne peut pas être enlevée de la plaque murale.
Séparer le thermostat de la plaque murale selon la figure 1.
Placer la plaque murale contre le mur et marquer au crayon
l’emplacement des trous.
REMARQUE : La mise à niveau est purement esthétique et
n'aura aucun effet sur le fonctionnement du thermostat.
Percer les trous aux endroits marqués et insérer les chevilles
d’ancrage fournies.
2.
Passer les fils par la grande ouverture située au centre inférieur
de la plaque murale selon la figure 2.
Fixer la plaque murale au mur avec les vis de montage fournies
selon la figure 3.
2.3Câblage
Il est important que vous jumeliez les étiquettes des fils aux bornes
correspondantes sur le thermostat.
REMARQUE : Selon votre système, vous n’aurez peut-être pas à utiliser toutes les bornes.
Enlever le cavalier (fil) entre les bornes Rc et Rh si vous avez les fils
Rh et Rc tel que montré dans l’illustration suivante.
Si une étiquette de fil ne correspond pas à aucune désignation de
borne sur le thermostat, se référer à l'illustration suivante pour trouver une autre étiquette qui peut correspondre à cette borne.
RT H111/ RTH 221 3/8
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.