Honeywell R7847, R7849, R7886, R7849B, R7861 User Manual

...
R7824, R7847, R7848, R7849,R7851,R7861,
R7886 Amplifiers for
7800 SERIES Relay Modules
PRODUCT DATA
The R7824C Rectification Flame Amplifier is a solid state plug-in amplifier that responds to a rectified signal from a C7024E,F Self­Check Ultraviolet Flame Detector to indicate the presence of flame when used with an RM7824 Relay Module.
The R7847A,B Rectification Flame Amplifiers are solid state plug­in amplifiers that respond to a rectified signal from a rectification type flame detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7847C Self-Check Rectification Flame Amplifier is a solid state plug-in amplifier that responds to a rectified signal from a C7012E,F Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules. This is not European Community (CE) approved for EC7810, EC7820, EC/RM7830 or EC/RM7850 Relay Modules.
The R7848A,B Infrared Flame Amplifiers are solid state plug-in amplifiers that respond to an infrared signal from a C7015 Infrared Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7849A,B Ultraviolet Flame Amplifiers are solid state plug-in amplifiers that respond to an ultraviolet signal from a C7027, C7035 or C7044 Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7851B Optical Flame Amplifiers are solid state plug-in amplifiers that respond to optical signals from C7927, C7935, C7915, and C7962 Flame Detectors to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7851C Dynamic Self-Check Optical Flame Amplifier is a solid state plug-in amplifier that responds to ultraviolet signals from C7961E Dynamic Shutter-Check ultraviolet flame detectors to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7861A Self-Check Ultraviolet Flame Amplifier is a solid state plug-in amplifier that responds to an ultraviolet signal from a C7061 Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7886A Dynamic Self-Check Ultraviolet Amplifier is a solid state plug-in amplifier that responds to a pulsed direct current signal from a C7076A,C Ultraviolet Flame Detector with adjustable sensitivity to indicate the presence of flame when used with 7800 SERIES Relay Modules.

FEATURES

• Flame failure response time of 0.8 or 1 second; or 2.0 or
3.0 seconds, depending on the amplifier and relay module selected. See Table 1.
• Plug-in to 7800 SERIES Relay Module through printed circuit board edge connector keyed for proper orientation.
• Flame signal test jacks measure amplifier flame signal voltage.
• 0.0 to 5.0 Vdc Flame signal strength reading range.
• Color coded label identifies flame detection type:
— Green—rectification. Red—infrared. — Purple—ultraviolet. Blue—pulsed rectification. — White—optical.
• R7847B, R7848B, R7849B Dynamic Ampli-Check® circuitry tests all flame amplifier components 12 times per minute. The 7800 SERIES Relay Module locks out on safety shutdown with amplifier failure.
• R7824C and R7847C Dynamic Self-Check Rectification Amplifier, R7851C Dynamic Self-Check Optical Flame Amplifier, R7861 Self-Check Ultraviolet Flame Amplifier and R7886A Dynamic Self-Check Ultraviolet Amplifier test the detectors and all electronic components in the flame detection system 12 times per minute. The 7800 SERIES Relay Module locks out on safety shutdown with flame detection system failure.
NOTE: NOTE:R7824C, Series 2 or greater, and R7847C,
Series 4 or greater, pulse shutter when signal of
1.5 Vac is sensed.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ......................................................... 2
Installation ........................................................................ 4
Checkout .......................................................................... 6
® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved
65- 0109- 8
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES

SPECIFICATIONS

Models:
Flame Detection Systems (see Table 2): Rectification:
R7824C for use with C7024E,F Solid State Ultraviolet
Detectors.
R7847A for use with flame rods, rectifying photocells or
C7012A,C Solid State Ultraviolet Detectors.
R7847B for use with flame rods, rectifying photocells or
C7012A,C Solid State Ultraviolet Detectors.
R7847C for use with C7012E,F Solid State
Ultraviolet Detectors.
Infrared:
R7848A for use with C7015 Infrared (lead sulfide) Detector. R7848B for use with C7015 Infrared (lead sulfide) Detector.
Ultraviolet:
R7849A for use with C7027/C7035/C7044 Minipeeper Ultravi-
olet Detectors.
R7849B for use with C7027/C7035/C7044 Minipeeper Ultravi-
olet Detectors. R7861A for use with C7061A Ultraviolet Detector. R7886A for use with C7076A,D Ultraviolet Detectors with
adjustable sensitivity.
Optical:
R7851B for use with C7927, C7935, C7915 and C7962 Flame
Detectors. R7851C for use with C7961E Flame Detectors.
Flame Failure Response Time:
See Table 1.
Flame Signal (Volts dc):
Minimum Acceptable: 1.25 Vdc. Flame Signal Voltage Range (displayed on Keyboard Display
Module or measured with a 1M ohm/volt meter plugged into amplifier test jacks): 0.0 to 5.0 Vdc.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to 60°C). Storage: -40°F to 150°F (-40°C to 65°C).
Humidity: Operating 85% rh continuous, noncondensing. Vibration: Continuous 0.5G environment.
Weight:
Dimensions:
2.5 oz (71g), unpacked.
See Fig. 1
Approvals:
Underwriters Laboratories Inc. Listed: File no. MP268, Guide no.
MCCZZ: R7847A, R7847B, R7847C, R7861A, R7886A, R7848A, R7848B, R7849A, R7849B, R7851B. (R7851C Pending.)
Underwriters Laboratories Inc. Component Recognized: File no.
MP268, Guide no. MCCZZ: R7824C.
Canadian Standards Association Certified: LR95329-3. (R7851C
Pending.)
Factory Mutual Approved: Report J.I.1V9A0.AF. (R7851C
Pending.)
Industrial Risk Insurers: Acceptable
Table 1. Relay Module Flame Failure
Response Time (FFRT).
Flame Failure Response
Time (FFRT) in seconds
Relay Module
EC7810, EC7820, EC/RM7830,
0.8 or 1 2.0 or 3.0
1.0 2.0
EC/RM7850
EC/RM7823, EC/RM7885, EC/
0.8 3.0 RM7890, EC/RM7895, RM7896, RM7888, RM7838, RM7800, RM7840
RM7824 N/A 3.0
S
3-9/16 (91)
–+
FLAME AMPLIFIER
3
(76)
3/8 (9)
7/8 (23)
M11460
Fig. 1. Flame amplifier dimensions in in. (mm).
NOTE: .NOTE: EN298 Approved: When these amplifiers are
used with an EC7810, EC7820, EC/RM7830, or EC/RM7850 Relay Module.
Accessories:
Flame Simulators:
Rectification: 123514A. Ultraviolet: 203659.
Flame Detectors (ordered separately): select from Table 2.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
Your local Home and Building Control Sales Office (check white pages of your phone directory).
1.
Home and Building Control Customer Relations
2.
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0109—8 2
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
Table 2. Flame Detection Systems.
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Flame
Failure
Response
Type Color Self-Checking Model
Rectification Green Dymanic Self-
Check
No
No
No
Dynamic Ampli­Check®
Dynamic Ampli­Check®
Dynamic Ampli­Check®
Dynamic Self­Check
R7824C
R7847A
R7847A
R7847A
R7847B
R7847B
R7847B
R7847C
Infrared Red No R7848A 2/3 Gas, oil,
Dynamic Ampli­Check®
R7848B
Ultraviolet Purple No R7849A 0.8/1 or
Dynamic Ampli­Check®
Dynamic Self­Check
Blue Dynamic Self-
Check
Optical White Dymanic Ampli-
R7849B
R7861A
R7886A
R7851B 0.8/1 or 2/3 Gas, oil,
Check®
Dynamic Self­Check
a
Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES Relay Module.
b
R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.
c
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner operation and shuts down burner if detection system fails.
d
Use only Honeywell part no. 38316 Photocell.
e
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
f
200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter. Applies to R7847C series 3 or greater; R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.
g
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use C7012E,F Flame Detector with R7847C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously for twenty-four hours or longer.
h
R7847A,B Amplifiers with 0.8/1 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
i
R7824C Series 2 and greater and R7847C Series 4 and greater check flame detector system when flame reaches 1.5 Vdc or at 4.5 seconds, whichever occurs first.
j
Order flame rod separately; see flame detector Instructions for holder.
R7851C
Time (sec)aFuel Type Models
b,c, i
3 Gas, oil,
coal
h
0.8/1 or 2/3 Gas Rectifying Flame Rod
h
0.8/1 or
Oil Rectifying Photocell C7003, C7010, C7013,
2/3
h
2/3 Gas, oil,
coal
e,h
0.8/1 or
Gas Rectifying Flame Rod
2/3
e,h
0.8/1 or
Oil Rectifying Photocell C7003, C7010, C7013,
2/3
e,h
2/3 Gas, oil,
coal
c,f, i
2/3 Gas, oil,
coal
coal
e
3 Gas, oil,
coal
Gas, oil Ultraviolet
2/3
d
0.8/1 or
Gas, oil Ultraviolet
2/3
c,f
0.8/1 or 2/3
c,f
2/3 Gas, oil,
Gas, oil, coal
coal
coal
c
2/3 Gas, oil,
Ultraviolet (Purple
C7024E,F
Peeper®)
C7004, C7007, C7011
Holders
j
Complete Assemblies: C7008, C7009, Q179
C7014
Ultraviolet (Purple
C7012A,C.
Peeper®)
C7004, C7007, C7011
Holders
b
Complete Assemblies: C7008, C7009, Q179
C7014
Ultraviolet (Purple
C7012A,C
Peeper®)
Ultraviolet (Purple
C7012E,F
Peeper®)
Infrared (Lead
C7015
Sulfide)
Infrared (Lead
C7015
Sulfide)
(Minipeeper)
(Minipeeper)
C7027, C7035, C7044
C7027, C7035, C7044
Ultraviolet C7061
Ultraviolet (Adjustable
C7076
Sensitivity)
Optical (UV, IR, Visible Light)
C7927, C7935, C7915, C7962
Optical (UV only) C7961
coal
d
d
g
g
3 65-0109—8
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
1. Align the amplifier circuit board edge connector with the
CAUTION
Equipment Damage Hazard. Incorrect combination of relay module, amplifier and flame detector can cause equipment damage.
In infrared applications (C7015 Infrared Flame Detector and R7848 Amplifier) using the RM7890 Relay Module with software version 4004 or less requires a ten-second delay to start sequence. This applies only to the initial power of the RM7890.
keyed receptacle on the 7800 SERIES Relay Module. Be sure the amplifier nameplate faces away from the Relay Module. Push in the amplifier until the circuit board is fully
2.
inserted into the receptacle and then push the amplifier toward the 7800 SERIES Relay Module retaining clasp. Be sure the amplifier is firmly in place.
3.
4. Perform all required checkout tests.

Installing Flame Detector

INSTALLATION

When Installing this Product...

Read these instructions carefully. Failure to follow them
1.
could damage the product or cause a hazardous
condition.
Check the ratings given in the instructions and on the
2.
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced, flame
safeguard control technician.
After installation is complete, check out the product
4.
operation as provided in these instructions.
WARNING
Electric Shock Hazard. Can cause electrical shock, serious injury or death.
Disconnect the power supply before beginning installation. More than one power supply disconnection can be involved.
IMPORTANT
1. Wiring must comply with all applicable codes, ordinances and regulations
2. Wiring (where required) must comply with NEC Class 1 (Line Voltage) wiring.
3. Perform all required checkout tests after installation is complete.
NOTE: NOTE:Table 2 lists flame detection systems available
for use with 7800 SERIES Relay Modules. Be sure to use the correct combination of amplifier and flame detector.
Proper flame detector installation is the basis of a safe and reliable flame safeguard installation. Refer to the Instructions packed with the flame detector and the equipment manufac­turer instructions.
Keep the flame signal leadwires as short as possible from the flame detector to the wiring subbase. Capacitance increases with leadwire length, reducing the signal strength. The maximum permissible leadwire length depends on the type of flame detector, leadwire and conduit. However, the ultimate limiting factor for the flame detector leadwire is the flame signal; see Table 3 in the Checkout section.
CAUTION
Equipment Damage Hazard. Can cause equipment damage.
Disconnect 7800 SERIES Relay Module power before removing amplifier.

Installing Plug-In Flame Signal Amplifier (Fig. 2)

WARNING
Electric Shock Hazard. Can cause electrical shock, serious injury or death.
Disconnect the power supply before beginning installation. More than one power supply disconnection can be involved.
65-0109—8 4
Fig. 2. Installing flame signal amplifier.

Wiring

WARNING
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before beginning installation. More than one disconnection can be involved.
Remove the 7800 SERIES Relay Module from the
1.
wiring subbase. Refer to Fig. 3 for proper flame detector wiring.
2.
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
PHOTOCELL
F
X
X
G
FLAME ROD
INFRARED (C7015)
WHITE
F
BROWN
G
ULTRAVIOLET (C7027/C7035/C7044)
BLUE
F
1
WHITE
G
OPTICAL C7927A
BLUE
F
1
WHITE
G
SOLID STATE ULTRAVIOLET (C7012A,C, C7961E)
BLUE
F
2
YELLOW
G
BLACK
L1
BLACK
L2
GND
GREEN
5
SOLID STATE SELF-CHECKING ULTRAVIOLET (C7061A)
C7076A,D ULTRAVIOLET DETECTOR
X
F
G
X
6
5
4
3
F G
F
3a
G
SHUTTER
SHUTTER
3
L2
REMOTE SENSOR
3b
L1
L2
7800 SERIES
7
EARTH
2b
GROUND
8
2a
1
C7076A OR C7076D
2
TERMINAL BLOCK
L1 (HOT) L2 (COMMON)
22
5
SOLID STATE SELF-CHECKING ULTRAVIOLET (C7012E,F)
4
BLUE
F
2
YELLOW
G
WHITE
22
WHITE
L2
BLACK
L1
BLACK
L2
3
SOLID STATE SELF-CHECKING ULTRAVIOLET (C7024E,F – E SHOWN)
BLUE
BLUE
F
2
YELLOW
G
WHITE
22
WHITE
N
!
1
CAUTION: EQUIPMENT DAMAGE HAZARD. INCORRECT WIRING POLARITY CAN DAMAGE OR DESTROY UV SENSING TUBES. CONNECT FLAME DETECTOR WIRES ACCORDING TO FOOTNOTES 1 AND 2 TO PREVENT UV SENSING TUBE DAMAGE.FLAME DETECTOR LEADS ARE COLOR CODED. THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE WHITE MUST BE CONNECTED TO THE G TERMINAL. THE UV SENSING TUBE IS POLARITY SENSITIVE.
2
FLAME DETECTOR LEADS ARE COLOR CODED. THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE YELLOW MUST BE CONNECTED TO THE G TERMINAL. THE UV SENSING TUBE IS POLARITY SENSITIVE.
!
CAUTION: EQUIPMENT DAMAGE HAZARD. INCORRECT VOLTAGE CAN DAMAGE SHUTTER MECHANISM ONLY ON EC7800 SERIES
3
RELAY MODULES. INSTALL A 200/220/240 VAC TO 120 VAC, 10VA MINIMUM, STEPDOWN TRANSFORMER (NOT PROVIDED) TO DRIVE THE SHUTTER MECHANISM.
4
DO NOT USE 0.8/1 SECOND FFRT AMPLIFIER WITH C7012A,C FLAME DETECTOR.
5
GND (GREEN) LEAD WIRE ON C7961E ONLY.
3
F
YELLOW
2
G
WHITE
22
WHITE
L2
RED
3
BLACK
L2
M20309
Fig. 3. Flame detector wiring.
5 65-0109—8
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
3. Disconnect power supply before making wiring
connections to prevent electrical shock and equipment damage.
4. All wiring must comply with appropriate electrical codes,
ordinances and regulations including NEC Class 1 (Line Voltage) wiring where required.
5. Use recommended wire size and type no. 18 copper
conductors TTW(60C) or THW (75C) or THNN(90C).
6. Use recommended wire routing:
a. Keep the flame signal leadwire as short as possible
from the detector to the 7800 SERIES Relay Module. The maximum permissible leadwire length depends on the type of leadwire, conduit type and leadwire diameter. The ultimate limiting factor for flame signal leadwire length is the flame signal voltage.
b. Do not run high voltage ignition transformer wires in
the same conduit with the flame detection wiring.
c. If the flame detector leadwires are not long enough
to reach the 7800 SERIES Relay Module electrical connectors, make splices in a junction box. (1) Enclose scanner wiring without armor cable in
metal cable or conduit.
(2) Follow flame detector Instructions.
Check wiring, see Fig. 4.
7.
8. Install 7800 SERIES Relay Module.
9. Restore power to the 7800 SERIES Relay Module.
Flame detector wiring is shown in Fig. 3.
CAUTION
Equipment Damage Hazard. Improper wiring can destroy ultraviolet sensing tube.
Carefully follow polarity sensitive wiring instructions for the C7027, C7035, C7044, C7012, C7024, C7061, C7961 and C7076. Reversing the leadwires, even momentarily, can destroy the ultraviolet sensing tube.
POSITIVE (+)
NEGATIVE (-) METER LEAD
FLAME SIMULATOR TEST JACK
METER LEAD
ONE MEGOHM/VOLT METER

CHECKOUT

Preliminary Inspection

Make certain that:
Wiring connections are correct and all terminal screws
1.
and electrical connections are tight.
2. Proper flame failure response time is selected.
Amplifier is securely mounted on the 7800 SERIES
3.
Relay Module. Detectors are properly positioned and cleaned
4.
according to Detector Instructions.
5. Correct combination of amplifier and flame detector is
used.

Flame Signal Measurement (Fig. 4)

Flame signal can be measured at the Flame Signal Test Jacks, see Fig. 4, and at the Keyboard Display Module. Measure the flame signal at the appropriate times defined in the Checkout section; see applicable 7800 SERIES Relay Module Instructions. See Table 3 for acceptable and maximum flame signal voltage strengths.
M11459A
Fig. 4. Flame signal measurement with meter.
Connect blue leadwire from detector to terminal F and
1.
white leadwire from C7027/C7035/C7044/C7061 to terminal G. Connect blue leadwire from detector to terminal F and
2.
yellow leadwire from C7012/C7024/C7961 to terminal G.
3. Follow lightoff Instructions for applicable 7800 SERIES
Relay Module.

Measuring Flame Signal With Keyboard Display Module

Consult Instructions for applicable 7800 SERIES Relay Module or Keyboard Display Module.

Measuring Flame Signal with a Volt Ohmmeter

Two test jacks, positive and negative (Com) are accessible on the top of the amplifier when plugged into the 7800 SERIES Relay Module. These jacks are provided for monitoring flame signal strength. Use a one megohm/volt meter to measure the flame signal strength. Connect the positive meter lead (red) to the positive (+) amplifier test jack and the negative meter lead (black) to the negative (-) amplifier test jack. The test jacks use standard 0.180 inch diameter voltmeter probes. A minimum 1.25 Vdc flame signal is required.
65-0109—8 6
Table 3. Flame signal.
Minimum Acceptable
Flame Detector Flame Signal Amplifier
Flame Rod Photocell C7012A,C
C7012E,F
c
c
C7015A
C7024E,F
C7027A C7035A
R7847A,B
R7847C
R7848A,B
R7824C
R7849A,B
b
d,e
b
d,e
b
Steady dc Voltage
a
1.25 Vdc 5.0 Vdc at Keyboard Display Module
Maximum Expected dc Voltage
or on volt-ohmmeter.
C7044A
C7927 C7935
R7851B
b
C7915 C7962
C7061A
C7076A,D
C7961E
a
This minimum or stronger signal can be easily obtained if the detector is correctly installed and positioned to properly sense the
R7861A
R7886A
R7851C
d
d
d
flame. Obtain this voltage before completing checkout.
b
The flame amplifiers are Ampli-Check® type.
c
Adjust slightly, or face the pipe down, or extend the sight pipe on C7012A,C,E,F applications to obtain a maximum flame signal reading less than 5.0 volts.
d
The flame signal amplifier circuitry is tested one-half second every five seconds during burner operation and shuts down the burner if the amplifier fails (all installations).
e
R7824C, Series 2 or greater, and R7847C, Series 4 or greater, pulse the shutter when the flame signal reaches 1.5 Vdc.
The flame signal for the pilot alone, the main burner flame alone, and both together must be steady and a minimum of
1.25V. If the flame signal is unsteady, or less than the minimum acceptable voltage, check the flame detector installation and circuitry in the following procedure.
Check the supply voltages at terminals (L1) and L2 (N).
1.
Make sure the master switch is closed, connections are correct, and the power supply is of the correct voltage and frequency and is sinusoidal.
2. Check the detector wiring for defects including:
a. Incorrect connections. b. Wrong type of wire. c. Deteriorated wire. d. Open circuits. e. Short circuits. f. Leakage paths caused by moisture, soot or accu-
mulated dirt.
3. For a flame rod, make sure:
a. There is enough ground area. b. The flame rod is properly located in the flame. c. Temperature at the flame rod insulator is no greater
than 500¡F (260¡C).
For all optical detectors, clean the detector viewing win-
4.
dow, lens, and inside of the sight pipe as applicable.
5. With the burner running, check the temperature at the
detector. If it exceeds the detector maximum rated temperature: a. Add a heat block to stop conducted heat traveling
up the sight pipe. b. Add a shield or screen to reflect radiated heat. c. Add cooling (refer to sight pipe ventilation in the
detector Instructions).
6. Make sure that the flame adjustment is not too lean.
Make sure the optical detector is properly sighting the
7.
flame.
8. If necessary, resight or reposition the detector.
If you cannot obtain proper operation, replace the
9.
plug-in amplifier. If you cannot yet obtain proper operation, replace the
10.
flame detector.
IMPORTANT
If you make any changes to the flame detection system, repeat all required Checkout tests in Checkout section of the Instructions for the applicable 7800 SERIES Relay Module.
7 65-0109—8
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Automation and Control Solutions Honeywell International Honeywell Europe S.A. Honeywell Latin American
Honeywell Honeywell Limited-Honeywell Limitée Control Products 3 Avenue du Bourget 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley, MN 55422 Scarborough, Ontario 17 Changi Business Park Central 1 Belgium Suite 200
M1V 4Z9 Singapore 486073 Sunrise FL 33325
Region
65-0109—8 G.R. Rev. 01-02 www.honeywell.com
Loading...