MicroniK 200
Fig. 1. Temperature controller
Fig. 2. LC Display
R7426B,C
TEMPERATURE CONTROLLER WITH REAL-TIME CLOCK
SPECIFICATION DATA
GENERAL
The R7426B,C temperature controllers cover all space and/or discharge air temperature applications within the specified control range of 0...50°C (LOw range) requiring sequence operation of heating, mixed air damper or energy recovery system and cooling with optional outside air temperature compensation reset of the main setpoint. The controllers can be configured to perform space or discharge air or spacedischarge air temperature cascade control with limit control.
For special higher temperature control applications, the control range 0...130 C (HI range) can be selected.
FEATURES
Weekly time schedule with up to six switching points per day
Automatic daylight saving time change
Four different operating modes: Comfort, Standby, Night, and OFF
Yearly holiday programming in advance
Three types of holiday schedules
Self-adaptive optimum start program for room control system
Night cycle program
Order Numbers
Order-No. |
Controller Description |
R7426B2012 |
Temperature controller with integrated |
|
real time clock (RTC), Plant/System |
|
ON/OFF output, and three 3-position |
|
floating outputs. The controller offers the |
|
choice of selectable different output |
|
sequence operations and output signals |
|
suitable to drive solid-state relays or step |
|
relays. |
R7426C2010 |
Temperature controller with integrated |
|
real time clock (RTC), Plant/System |
|
ON/OFF output, and three analog |
|
outputs. The controller offers selection of |
|
different output sequence operations. |
EN0B-0301GE51 R0104
R7426B,C TEMPERATURE CONTROLLER
TECHNICAL DATA
General |
Electronic |
8-bit microcontroller, 10-bit A/D converter, EEPROM, and LC |
||||
|
|
|
display |
|
|
|
|
Power supply |
24 Vac +10...-15%, 50/60 Hz |
|
|
||
|
Power consumption |
3 VA + Actuator power requirements |
|
|||
|
Control range |
0...50°C |
|
|
||
|
Battery |
|
Type CR2032 (life time 8 years) |
|
||
Temperature |
T1 |
|
Main temperature sensor |
|
accuracy 0.5 K |
|
Inputs |
T2 |
|
Cascade temperature sensor |
|
excluding |
|
|
T3 |
|
Compensation temperature sensor |
sensor |
||
|
|
|
||||
Sensor type1) |
Automatic identification of sensor type |
Temperature range |
Characteristics2) |
|||
|
Pt 1000 |
-30....+130 C |
1000 τ at 0 C |
|||
|
BALCO 500 |
-30....+130 C |
500 τ at 23.3 C |
|||
|
NTC 20kτ |
-30....+85 C / -30....+130 C1) |
20 kτ at 25 C |
|||
CPA/SPA-Input1) |
|
|
CPA/SPA range |
Sensor & CPA/SPA types |
||
|
CPATYP 0 |
CPA: 5 K |
internal |
|
||
|
CPATYP 1 (953...1053 τ) |
CPA: 5 K |
T7412B1016 (Pt 1000) |
|||
|
CPATYP 2 (0...100 kτ) |
CPA: 5 K |
T7412B1057 (Pt 1000) |
|||
|
|
|
|
|
T7412C1030 (Pt 1000) |
|
|
|
|
|
|
T7412B1008 (NTC 20kτ) |
|
|
|
|
|
|
T7412C1006 (NTC 20kτ) |
|
|
CPATYP 3 (10...20 kτ) |
SPA: 15...30 C |
T7412B1024 (BALCO 500) |
|||
|
|
|
|
|
T7412B1040 (Pt 1000) |
|
|
CPATYP 4 (0...10 kτ) |
CPA: 5 K |
HCW 23 (setpoint wheel |
|||
|
|
|
|
|
printed with +/- 5 K) |
|
|
CPATYP 5 (0...100 kτ) |
SPA: 15...30 C |
43193982-001 |
|||
|
CPATYP 6 (0...100 kτ) |
SPA: 0...50 C or 0...130 C |
43193982-001 |
|||
Analog input |
Humidity deviation (Xwrh) |
-5...+5 Vdc, 200 mV / %rh |
|
|
||
Digital inputs |
|
|
Mode |
Potential free contact |
||
|
Occupancy |
unoccupied |
open > 40 kτ |
|||
|
|
|
occupied |
closed < 100 τ |
||
|
Freeze protection input |
freeze protection operation |
open > 40 kτ |
|||
|
|
|
normal operation |
closed < 100 τ |
||
Outputs |
ON/OFF output |
OFF / ON |
|
|
||
|
TRIAC outputs |
|
Floating1) |
|
max. load |
|
|
|
|
2, 3, 4, 6 or 15-stage1) |
|
450 mA at |
|
|
|
|
|
ON (24 Vac) / OFF (0 Vac) |
|
24 Vac per |
|
|
|
|
Pulse-width modulation1) 0...100% |
output |
|
|
|
|
|
based on run time |
|
|
|
Analog outputs on controller R7426C |
Control range1) 0/2...10 Vdc (0...100%) |
max. load |
|||
|
|
|
full range 0...12 Vdc |
|
1.2 mA at |
|
|
|
|
|
|
|
12 Vdc |
Ambient limits |
Operating temperature |
0...50°C (0...122 F) |
|
|
||
|
Transport and storage temperature |
-35...+70°C (-31...+158 F) |
|
|
||
|
Relative humidity |
5...95%rh non-condensing |
|
|
||
Safety |
Protection class |
II as per EN60730-1 |
|
|
||
|
Protection standard |
IP30 or IP40 (front panel mounting) as per EN60529 |
||||
Housing |
Dimensions (H x W x D) |
105 x 152 x 37 mm |
|
|
||
|
Weight |
|
250 g |
|
|
|
|
Mounting |
Front door, back panel, wall, or rail |
|
|||
Connections |
Connection terminal |
terminals max. 1 x 1.5 mm2 |
|
|
||
1) Selectable |
2) |
same sensor type must be used for T1, T2, and T3 |
|
|
EN0B-0301GE51 R0104 |
2 |
R7426B,C TEMPERATURE CONTROLLER
CONTROL AND CONFIGURATION PARAMETER
Control Parameter |
Parameter Description |
|
Setting |
|
Reso- |
Unit |
|||
|
|
|
|
|
|
|
lution |
||
No. |
Name |
|
Low |
|
High |
Default |
|||
|
|
|
|
|
|||||
P.01 |
W1 |
Main setpoint for input T1 |
|
0 |
|
50 |
21 |
0.5 |
C |
P.02 |
Wlim |
Limit setpoint (low or high) for input T2 |
|
5 |
|
50 |
16 |
1 |
C |
P.03 |
Wcomp |
Compensation changeover point for input T3 |
-5 |
|
40 |
20 |
1 |
C |
|
P.04 |
Wi |
Winter compensation authority |
|
-350 |
|
+350 |
0 |
2 |
% |
P.05 |
Su |
Summer compensation authority |
|
-100 |
|
+100 |
0 |
1 |
% |
P.06 |
Wcas |
Submaster or cascade setpoint |
|
OFF, 0 |
|
50 |
20 |
0.5 |
C |
P.07 |
Rcas |
Cascade reset span adjustment |
|
0 |
|
40 |
10 |
0.5 |
K |
P.08 |
Xp1 |
Throttling range (main control loop) T1 |
|
0.5 |
|
40 |
2 |
0.5 |
K |
P.09 |
Xp2 |
Throttling range (cascade control loop) T2 |
|
0.5 |
|
40 |
10 |
0.5 |
K |
P.10 |
Xpc |
Cooling throttling range for sequence control |
OFF, 1 |
|
40 |
3 |
0.5 |
K |
|
P.11 |
Xph |
Heating throttling range for sequence control |
1 |
|
40 |
6 |
0.5 |
K |
|
P.12 |
tr11) |
Reset time (main control loop) T1 |
|
OFF, 20 s |
|
20min |
OFF |
10/0.5 |
sec/min |
P.13 |
tr21) |
Reset time (cascade control loop) T2 |
|
OFF, 20 s |
|
20min |
OFF |
10/0.5 |
sec/min |
P.14 |
MINPOS |
Minimal pos. for air damper actuators |
|
0 |
|
50 |
20 |
1 |
% |
P.15 |
Ystart |
Start point for mid range shift of output Y1 |
|
-20 |
|
+20 |
0 |
0.5 |
K |
P.16 |
SOFFS |
Offset of main setpoint in Standby mode |
|
0 |
|
10 |
2 |
0.1 |
K |
P.17 |
T1Cal |
Calibration of temperature sensor T1 |
|
-20 |
|
+20 |
0 |
0.1 |
K |
P.18 |
T2Cal |
Calibration of temperature sensor T2 |
|
-20 |
|
+20 |
0 |
0.1 |
K |
P.19 |
T3Cal |
Calibration of temperature sensor T3 |
|
-20 |
|
+20 |
0 |
0.1 |
K |
P.20 |
RetOffs |
Return air offset to simulate exhaust air cond. |
OFF, 0 |
|
5 |
OFF |
0.1 |
K |
|
P.21 |
RuntimeY1 |
Actuator run time for output Y1 |
|
6 |
|
180 |
60 |
1 |
sec |
P.22 |
RuntimeY3 |
Actuator run time for output Y3 |
|
6 |
|
180 |
60 |
1 |
sec |
P.23 |
RuntimeY2 |
Actuator run time for output Y2 |
|
6 |
|
180 |
60 |
1 |
sec |
P.24 |
NightLow |
Night low limit against temperature extremes |
OFF, 8 |
|
19 |
OFF |
1 |
C |
|
P.25 |
NightHigh |
Night high limit against temperature extremes |
OFF, 21 |
|
40 |
OFF |
1 |
C |
|
P.26 |
NOFFS |
Offset of main setpoint in Night mode |
|
0 |
|
30 |
5 |
0.1 |
K |
Config. Parameter |
Values |
|
|
|
|
Default |
Unit |
||
No. |
Name |
|
|
|
|
||||
|
|
|
|
|
|
|
|
||
C.01 |
DIR/REVY1 |
Dir, Rev (R7426C, only) |
|
|
|
|
|
Dir |
|
C.02 |
DIR/REVY3 |
|
|
|
|
|
Dir |
|
|
C.03 |
DIR/REVY2 |
|
|
|
|
|
|
Dir |
|
C.04 |
Ctrltyp2) |
Lo = 0...50°C (factory preset), Hi1 = 0...130°C, Hi2 = 0...130°C |
|
|
|
|
|||
C.05 |
CPATYP |
0 = internal (default), 1 = 5 K (953...1053 τ), 2 = 5 K (0 τ...100kτ), |
|
0 |
|
||||
3 = 15 … 30 C (10...20 kτ), 4 = 5 K (0...10 kτ), |
|
|
|
||||||
|
|
5 = 15 … 30 C (0...100 kτ), 6 = 0...50 C or 0...130 C (0...100 kτ) |
|
|
|
||||
C.06 |
YRange |
0 = 2 … 10 Vdc , 1 = 0 … 10 Vdc (R7426C, only) |
|
|
1 |
|
|||
C.08 |
Y1Mode |
0= floating, 1= 2 stage ON/OFF, 2= 3 stage ON/OFF, 3 = pwm, 4 = unconfig. |
4 |
|
|||||
C.09 |
Y3Mode |
4 |
|
||||||
(safe state is configured prior to controller's start-up) (R7426B, only) |
|
|
|||||||
C.10 |
Y2Mode |
|
4 |
|
|||||
|
|
|
|
|
|
|
|||
C.11 |
YMode |
0: Y1 = D, Y2 = C, Y3 = H |
1: |
Y3/2/1 = H or C |
|
0 |
|
||
2: Y3/1 = H, Y2 = C |
3: |
Y3/1 = C, Y2 = H |
|
|
|||||
|
|
4: Y1 = 2Pos D, Y2 = C, Y3 = H |
5: |
Y3/1 = 15H, Y2 = C |
|
|
|
||
C.12 |
T2ext |
0 = T2 installed |
1 = T1 signal used for T2 |
|
0 |
|
|||
C.13 |
LimTyp |
0 = Low limit |
1 = High limit |
|
|
0 |
|
||
C.14 |
Senstyp |
0 = Auto detection |
1 = NTC sensor type |
|
|
0 |
|
||
C.15 |
Y1CTRF |
Output Y1 used for: |
0 = mixed air damper |
|
0 |
|
|||
|
1= energy recovery |
|
|
|
|
||||
|
|
|
|
|
|
|
|||
C.16 |
AddHour |
Adjusts the month for winter/summer time change: 0 (disabled) = Min. 12 = Max. |
3 |
month |
|||||
C.17 |
SubHour |
Adjusts the month for summer/winter time change: 0 (disabled) = Min. 12 = Max. |
10 |
month |
3 |
EN0B-0301GE51 R0104 |
R7426B,C TEMPERATURE CONTROLLER
Config. Parameter |
|
Values |
|
|
|
Default |
Unit |
|
No. |
Name |
|
|
|
|
|||
|
|
|
|
|
|
|
||
C.18 |
PSTG_H3) |
Prestart gradient for heating: |
0 |
(disabled) = Min. |
2 |
= Max. |
0 |
K/min |
C.19 |
PSTG_C3) |
Prestart gradient for cooling: |
0 |
(disabled) = Min. |
2 |
= Max |
0 |
K/min |
C.20 |
tvd |
Use damper before comfort time: |
0 |
(normal control) = Min. 90 = Max. |
15 |
min |
||
C.21 |
Adapt |
Optimum Start Self Adaption speed: |
0 |
= Min. |
100 = Max. |
50 |
% |
|
C.22 |
Adr2) |
Serial communication address: |
0 |
= Min. |
255 = Max. |
254 |
|
|
C.23 |
DefProg |
0 = No Default programming |
1 |
= Initiates Default programming |
0 |
|
1) for tr > 2 min resolution = 0.5 min, for tr < 2 min resolution = 10 sec
2)actual value will not be changed during reset to default parameter
3)can be overwritten by controller for self-adaption purposes, resolution = 0.01 K/min
FUNCTIONS
Real-Time Clock
The time clock performs automatic change of the controller mode to OFF, Night, Standby, or Comfort in accordance with the programmed time schedule. In Standby or Night mode, the SOFFS or NOFFS is added (cooling) to and subtracted (heating) from the calculated control point. Schedules for one week and up to six switching points per day can be programmed in advance and repeated week after week. In addition, three different holiday schedule types H1, H2 and H3 can be programmed. One of these holiday types can be assigned to each holiday date of the year (01.01. ... 31.12.). Holiday type H1 and H2 is valid only for this specific day and is reset to normal time schedule at midnight of that day. H3 is valid for every year and repeated year after year for fixed holiday dates. H1 can be programmed to be in OFF mode the whole day and H2 to be ON for a short period of time on the last day of a longer holiday period to preheat or precool the space in advance before the first occupied day.
Optimum Start Program
The optimum start program’s objective is to minimize total energy consumption by calculating in room control applications the start time for heating and cooling mode which will bring its respective space temperature to the boundary of the comfort zone at the time of occupancy start. The program will start the ventilation system at the calculated start time with forced return air recirculation mixed air damper position or full energy recovery valve position to minimize energy consumption during the start-up period. At a programmable time before occupancy start, the controller will switch the output signal Y1 to normal and will supply fresh air to the space in mixed air applications. The optimum start program uses historical data for self-adaptive adjustment.
Night Cycle Program
The night cycle program offers not only energy conservation, but also the ability to assign OFF mode night low or high limits with 1 K hysteresis for the protection of a space and its contents against temperature extremes. It automatically cycles between the user selected upper and lower limits and turns on full heating or cooling whenever the limits are reached.
APPLICATION
The R7426B,C controllers can be used for sequence control applications of heating, mixed air damper or energy recovery system, and cooling.
NOTE: All diagrams show proportional control action, only. If P+I control is in operation, the slopes for heating and cooling are not defined.
Temperature Sequence Control with Heating, Mixed Air Dampers, and Cooling
This application will be active with the R7426B,C controllers when T2 is not connected. It can be used for sequence control of a heating valve, a mixed air damper, and a cooling valve.
The characteristic of each output on the R7426C controller can be selected via the control parameters DIR/REVx
(x = Y1, Y2, or Y3). The diagram shows Dir characteristic for all outputs.
Within the range Xp1, the damper signal is controlled as shown in the diagram below. If no cooling actuator is available, the control parameter Xpc can be set to OFF and the damper output is maintained at 100% above control point (CTRP1).
If the damper output should be decreased to MINPOS level above control point (CTRP1) as shown in the diagram, the control parameter Xpc has to be adjusted to any value between 1 and 40 K, also if no cooling actuator is available.
Y[%] |
|
|
|
|
|
100 |
|
1/4 Xp1 |
|
if Xpc = Off |
|
Damper |
|
|
|
||
|
|
|
|
||
|
Y1 |
|
|
|
|
|
Y3 |
|
|
Y2 |
|
MINPOS |
Heating |
|
|
Cooling |
|
|
|
|
if Xpc = Off |
|
|
0 |
|
|
|
|
|
|
|
|
Xwh / Xwc /Xwd |
||
|
CTRPH |
CTRP1 |
CTRPC |
||
|
|
|
|||
|
Xph |
Xp1 |
|
Xpc |
T2 |
|
|
|
NOTE: If the R7426B controller with floating output is used for mixed air damper control, you must ensure that the output load of maximum 450 mA is not exceeded.
EN0B-0301GE51 R0104 |
4 |