This document provides instructions and procedures for
installing and starting up the Micronik 200 R7426A,B,C
controllers. No special tools are required for mounting and
installation. The user interface and liquid-crystal display allow
accurate and easy parameter setting and output adjustment.
BEFORE INSTALLATION NOTE
• Visually inspect equipment for shipping damage.
Report any damage to the appropriate Honeywell
representative.
• Refer to job drawings for specific installation
information and mounting location.
• Verify the controllers will be adequately separated
from the main power supply, relays, or other equipment which can possibly generate electromagnetic
interference.
• Verify that the ambient temperature and the humidity
at the controllers will not exceed 0...50°C (32...122°F)
and 5 to 95% rh.
• Use shielded wiring in areas with high EMI.
• All wiring should be separated from power lines by at
least 150 mm (6’’).
• Do not install controllers near frequency converters
or other high-frequency sources.
MOUNTING
The controllers can be mounted in an electric cabinet or other
suitable enclosure. They are suitable for back panel, DIN rail,
wall, or front panel mounting. The corresponding mounting
sequence, as well as dimensions and panel cut-out, are
illustrated in the mounting instruction sheet EN1B-0202GE51
supplied with the controllers.
If the compensation sensor signal (T3) is received from
another controller (parallel connection of compensation
sensor inputs), the jumper W303 has to be cut before
mounting the controller (see Fig. 2). This disconnects the
sensor from the internal power supply.
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK
WIRING
Screwless type, spring loaded terminals are provided on
the controllers for panel and field wiring. These terminals
are suitable for solid conductors as well as tinned or with
multicore cable end, stranded wires up to 1.5 mm
make a termination, push the wire into the terminal or insert
a small screwdriver from the front of the controller into the
spring-release hole and insert the wire. Check for proper
connection by short pull on the wire.
Table 1.
controller to CPA/SPA potentiometer
R7426A,B,C T7412B1016
terminal 2 terminal 4 terminal 4 terminal 4
terminal 4 terminal 5 terminal 6
R7426A,B,C 43193982-001 - -
terminal 2 terminal 1 - -
terminal 4 terminal 3 - -
wiring run
from controller to all
input and output
devices
Terminal Connection
T7412B1057/1008
T7412C1030/1006
Table 2. Wire Dimensions
type of
wires
local
standard
1.0 mm2 1.5 mm2
100 m 150 m
2
. To
T7412B1024
T7412B1040
terminal 5+6
length max.
W303
Fig. 2. Parallel Connection of Compensation Sensor T3
Table 3. Jumper States
jumper1) state description
closed T3 supplied by this controller
W303
1)
Default jumper position = closed. Cut (open) jumper W303
only if the T3 input is fed from another controller (parallel
connection, max. six devices). This disconnects the T3 input
from the internal power supply
Wiring should be done only according to the actual job
wiring diagrams or wiring diagrams shown in the mounting
instruction sheet EN1B-0202GE51. The wiring to the
CPA/SPA potentiometers is described in Table 1. All wiring
must conform to applicable codes, ordinances, and
regulations. The maximum allowed wiring length per wire
size are shown in Table 2.
open
T3 supplied from another
controller
POWER SUPPLY AND GROUNDING
1. Refer to job drawings and verify correct supply voltage to
transformer (230 Vac) and controller (24 Vac).
2. Connect line power conductors to transformer primary.
Line power must be supplied from a breaker panel with
dedicated controller circuit. Do not turn the line power on
until all wiring has been checked against job drawings.
3. Connect transformers 24 Vac secondary to the controller
terminals 18 and 19. Connect one conductor to terminal
marked 24 V∼ and the other to terminal marked 24 V⊥. If
controllers are interconnected all terminals 19 must be
connected to the same potential 24 V⊥ level.
4. Do not connect the secondary side of the transformer to
the installation ground.
EN1B-0203GE51 R0507C 2
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK
CONFIGURATION AND CONTROL PARAMETERS
The controllers R7426A,B,C include two groups of settings*) (I and II) for control and configuration parameters that are
automatically selected during programming. For parameter Ctrltyp = Lo, setting I is selected, and for parameter Ctrltyp =
Hi1/Hi2, setting II is selected.
config. par. R7426
no. name
description
C.01 DIR/REVY1 Selects the output action of Y1 to adapt the valve or damper direction Dir x
C.02 DIR/REVY3 Selects the output action of Y3 to adapt the valve or damper direction Dir x
C.03 DIR/REVY2 Selects the output action of Y2 to adapt the valve or damper direction Dir x
Dir
Direct acting output signal
Rev
Reverse acting output signal
C.04 Ctrltyp1) Control type selects the setpoint operating range and default parameter
setting I or II.
set-
Lo
operating range setting*)
pt.
0...50°C for ventilation systems (factory preset)
Hi1
0...130°C for heating systems
Hi2
0...130°C with pump ON/OFF operation
C.05 CPATYP Selects the Control Point /SetPoint Adjustment type. 0 x x x
C.06 YRange Selects the output control range for all outputs (Y1, Y2, and Y3) 1 x
0 1 2 ... 10 Vdc
0 ... 10 Vdc
C.07 Startup Enables the start-up routine OFF xx
OFF
ON
Disabled
Enabled
C.08 Y1Mode Y1 output mode selects an individual output function for Y1 4 x x
C.09 Y3Mode Y3 output mode selects an individual output function for Y3 4 x
C.10 Y2Mode Y2 output mode selects an individual output function for Y2 4 x
0
Synchronous / floating
1
2 stage ON/OFF
2
3 stage binary coded ON/OFF
3
Pulse-width modulation
4
Unconfigured
C.11 YMode Selects the output mode for sequence operation or multistage ON/OFF func. 0
0 Damper, cooling and heating (Y1,Y2, Y3) x x
Sequence control for heating or cooling (Y1,Y2, Y3);
1
or 6-stage ON/OFF
Sequence control for heating (Y1, Y3) and cooling (Y2);
2
or 4-stage ON/OFF for heating (Y1, Y3), and cooling (Y2)
Sequence control for cooling (Y1, Y3) and heating (Y2);
3
or 4-stage ON/OFF for cooling (Y1, Y3), and heating (Y2)
4 Two-position damper control (Y1), heating (Y3) and cooling (Y2) x x5 15-stage binary coded ON/OFF for heating (Y1, Y3), and cooling (Y2) x
Table 4. Configuration parameters R7426A,B,C
default
setting
A B C
actual
value
Lo
x x x
for I
I
II
II
xxx
xxx
xxx
3 EN1B-0203GE51 R0507C
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK
config. par. R7426
no. name
description
C.12 T2ext Enable / Disables the T1 sensor input to be used for both T1 and T2 inputs.
0 1 T2 installed
T1 signal used for T2
C.13 LimTyp Limitation type determines whether the limit function is low or high. 0 / 1
0 1 Low limit
High limit
C.14 Senstyp Sensor type determines automatic detection or manual selection of NTC
sensors.
0 1 Auto detection
NTC sensor type
C.15 Y1CTRF Controls the action of Y1 or activates the occupancy input for summer/winter
changeover.
R7426A R7426B,C 0
cooling
1
heating
2
summer/winter changeover
0 1mixed air damper
energy recovery
C.16 AddHour2) Adjusts the month for winter/summer time change.
Min.
0 (disables winter/summer time change)
Max.
12
C.17 SubHour2) Adjusts the month for summer/winter time change.
Min.
C.18 PSTG_H
2) 3)
Min.
C.19 PSTG_C
2) 3)
Min.
0 (disables summer/winter time change)
Max.
12
Determines the prestart gradient to reach the comfort setpoint for heating.
0 (disabled)
Max.
2
Determines the prestart gradient to reach the comfort setpoint for cooling.
0 (disabled)
Max.
2
C.20 tvd2) Determines the damper prestart time before scheduled comfort mode
Min.
0 (normal control)
Max.
90
C.21 Adapt2) Optimum Start Self Adaption speed
Min.
Max. 0 100
C.22 Adr1) Sets the serial communication address, used for service or maintenance.
Min.
Max. 0 255
C.23 DefProg Initiates the default programming.
0 1 No Default programming
Initiates Default programming
1)
actual value will not be changed during reset to default parameter
2)
on Controllers with Real-Time Clock, only
3)
can be overwritten by controller for self-adaption purposes, resolution = 0.01 K/min
For detailed information of configuration parameters see chapter Configuration Settings.
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK
control par. setting I / setting II R7426
no. name
P.01 W1 Main setpoint for input T1 0
P.02 Wlim Limit setpoint (low or high) for input T2
description
low high def.
50 /
130
5 /
30
50 /
130
P.03 Wcomp Compensation changeover point for input T3 -5 40 20 1 °C x x x
P.04 Wi Winter compensation authority -350 +3500 2 % x x x
P.05 Su Summer compensation authority -100 +1000 1 % x x x
P.06 Wcas Submaster or cascade setpoint OFF, 0 50 20 0.5 °C x x x
P.07 Rcas Cascade reset span adjustment 0 40 10 0.5 K x x x
P.08 Xp1 Throttling range (main control loop) for T1 0.5 40 2 0.5 K x x x
P.09 Xp2
Throttling range (cascade or limit control loop)
for T2
0.5 40 10 0.5 K x x x
P.10 Xpc Cooling throttling range for sequence control OFF, 1 40 3 0.5 K x x
P.11 Xph Heating throttling range for sequence control 1 40 6 0.5 K x x
P.12 tr11) Reset time (main control loop)
P.13 tr21) Reset time (cascade control loop)
OFF,
20 sec
OFF,
20 sec
20
min
20
min
P.14 MINPOS Minimal pos. for air damper actuators 0 50 20 1 % xx
P.15 Ystart Start point for mid range shift of output Y1 -20 +20 0 0.5 K x x x
P.16 SOFFS Offset of main setpoint in Standby mode 0 10 2 0.1 K x x x
P.17 T1Cal Calibration of temperature sensor T1 -20 +20 0 0.1 K x x x
P.18 T2Cal Calibration of temperature sensor T2 -20 +20 0 0.1 K x x x
P.19 T3Cal Calibration of temperature sensor T3 -20 +20 0 0.1 K x x x
P.20 RetOffs Return air offset to simulate exhaust air cond. OFF, 0 5 OFF0.1 K x x
P.21 RuntimeY1 Actuator run time for Y1 6 180 60 1 sec x x
P.22 RuntimeY3 Actuator run time for Y3 6 180 60 1 sec x
P.23 RuntimeY2 Actuator run time for Y2 6 180 60 1 sec x
P.24 NightLow2) Night low limit against temperature extremes OFF, 8 19 OFF1 °C x xx
P.25 NightHigh2) Night high limit against temperature extremes OFF, 2140 OFF1 °C x xx
P.26 NOFFS2) Offset of main setpoint in Night mode 0 30 5 0.1 K x x x
1)
for tr > 2 min ⇒ resolution = 0.5 min, for tr < 2 min ⇒ resolution = 10 sec
2)
on Controllers with Real-Time Clock, only
For detailed information of control parameters see chapter Parameter Settings and Adjustment.
Table 5. Control parameters R7426A,B,C
21 /
70
16 /
90
OFF
OFF
reso-
lution
unit
A B C
actual
value
0.5 °C x x x
1 °C x x x
10/
sec/
0.5
10/
0.5
x x x
min
sec/
x x x
min
5 EN1B-0203GE51 R0507C
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK
CONFIGURATION SETTINGS
The controllers R7426A,B are supplied with unconfigured
outputs to avoid damage of installed final control devices by
supply of not applicable output signals if the controller power
supply is turned on.
All configuration parameters must be set to select the correct
control functions as required for the job application and to
start control operation and synchronization of the final control
devices.
Direct - Reverse Action
Dir/Revx, x = Y1, Y2 or Y3 (C.01...C.03)
The output action of the analog outputs on the R7426C
controller must sometimes be reversed for a correct opening
and closed direction of the valve or damper. This depends on
whether the output controls a 2-way or 3-way valve or on the
direction the damper shaft moves to open the damper (cw or
ccw). It is needed only if the actuator does not provide a
direction selector switch, plug, or similar.
In the case of the R7426A,B controllers, the direction can be
changed by exchanging the wiring connections open-close
(OUT2-OUT1).
Operating Range Selection Ctrltyp (C.04)
The controllers provide two operating ranges which can be
selected by the configuration parameter Ctrltyp
(Lo = 0...50°C, Hi1/Hi2 = 0...130°C).
Depending on this parameter setting, the setpoint ranges for
the main temperature (W1), limit temperature (W
submaster temperature (W
perature applications (Ctrltyp = Lo) or for flow water
temperature applications (Ctrltyp = Hi1/Hi2).
If the configuration parameter Ctrltyp = Hi1, normal operation
for flow water application will be performed. If Ctrltyp = Hi2,
the following additional function will be active on controllers
with real-time clock:
The controller switches the ON/OFF output (e.g. the pump)
from ON to OFF if
- the outside air temperature is above 8°C and
- the output signal Y1 = 0% for more than 5 minutes during
the controller is in the Comfort, Standby, or Night mode.
Changing the configuration parameter Ctrltyp value from Hito Lo control range or vice versa causes the controller to
change all parameter values to default, depending on the
selected Ctrltyp value.
For a direct parameter reset by the user, refer to chapter How to reset Parameter Values to Default Values? on page 12.
) are selected for air tem-
cas
), and
lim
Control Point / Setpoint Adjustment CPATYP
(C.05)
The control point or setpoint can be adjusted via the internal
or external potentiometer connected to the CPA/SPA input.
The potentiometer type is selected by the configuration
parameter CPATYP (see Table 6).
CPATYP
CPAT YP 0
CPAT YP 1
(953...1053Ω)
CPAT YP 2
(100kΩ...0Ω)
CPAT YP 3
(10...20kΩ)
CPAT YP 4
(0...10kΩ)
CPAT YP 5
(0...100kΩ)
CPAT YP 6
(0...100kΩ)
Output Control Range Selection
YRange (C.06)
The configuration parameter YRange is available only on the
R7426C controller and is required to select the output control
range (0...100%) to either 2...10 Vdc (YRange = 0) or
0...10 Vdc (YRange = 1). The selected control range is
common to all outputs.
Enabling the Start-up Routine (C.07)
A start-up routine is provided to prevent start-up problems for
the R7426B,C controllers (three outputs). This routine can be
enabled by setting the configuration parameter Startup to
ON.
Individual Output Function Selection
YxMode, x = 1, 2, or 3 (C.08...C.10)
The R7426A,B controllers provide a choice of output signals
suitable for operating a range of final control devices
according to the configuration parameter Y1Mode (for
R7426A,B) and Y2Mode, Y3Mode (for R7426B, only).
Each output can be configured individually by this configuration parameter (see Table 7).
Valve or damper actuators (floating mode) 0
2-stage ON/OFF Sequence Control 1
3-stage Binary ON/OFF Sequence Control 2
Electric Heat Current Valve (pwm output) 3
unconfigured 4