Honeywell R7140G, R7140L, R7140M Installation Instructions Manual

R7140G,L,M Burner Control Modules

FEATURES

• Device status available to ModBus™ through S7810M
• Safety features:
• Access for external electrical voltage checks.
• Application flexibility.
• 0.8 or 3.0 second Flame Failure Response Time
• Dependable, long-term operation provided by

APPLICATION

The Honeywell R7140G,L,M Burner Control Modules are microprocessor-based integrated burner controls for automatically fired gas, oil or combination fuel single burner applications. The Burner Control Module system consists of a Relay Module, Q520A Subbase, Amplifier and Purge Card. Options include S7800 Keyboard Display Modules (KDM).
The R7140 Burner Control Modules directly replace many BC7000 PM720G,L,M, and many R4150G,L,M and R4140G,L,M units using the existing Q520A 20-terminal Wiring Subbase.
The R7140 can be demonstrated or tested on the FSP5004 tester. Note that the R7849 UV Amplifier or the R7851 Optical Flame Amplifier cannot be tested.
The R7140G,L,M is programmed to provide a level of safety, functional capability and features beyond the capacity of conventional controls.
Functions provided by the R7140G,L,M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
• Five LEDs for sequence information. See Fig. 1.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Nonvolatile memory; R7140 retains history files and
• Report generation (optional).
NOTE: Check Service Notes on page 7 and Static Checkout
• Burner controller data (optional):
• Status of configuration jumpers.
• Status of Run/Test Switch.
INSTALLATION INSTRUCTIONS
card or S7800A1001 Series 5 Keyboard Display.
— Interlock check. — Closed loop logic test. — Dynamic AMPLI-CHECK™. — Dynamic input check. — Dynamic safety relay test. — Dynamic self-check logic. — Expanded safe-start check. — High Fire Purge Switch test (R7140L only). — Internal hardware status monitoring. — Low Fire Start Switch test. — Tamper resistant timing and logic.
(FFRT), depending on amplifier selected.
microcomputer technology.
sequencing status after loss of power and can be viewed using the Keyboard Display Module S7800A1001 (sold separately).
on page 25 prior to installation of R7140.
— Lockout/alarm status. — Total cycles of operation. — Total hours of operation.
66-1153-2
R7140G,L,M BURNER CONTROL MODULES
Maximum Total Connected Load: 2000VA.
RUN/TEST SWITCH
Fusing—Total Connected Load: 15A fast blow, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C). Humidity: 85% relative humidity, continuous, noncondensing. Vibration: 0.5G environment.
Weight:
With Dust Cover and Q520A Subbase: 4 lb., 5 oz. (1.96 kg).
Dimensions:
See Fig. 2.
Approvals:
Underwriters Laboratories Inc. UL, CUL Component
SEQUENCE STATUS LEDs
RESET PUSHBUTTON
FLAME SIMULATOR INPUT
AMPLIFIER
FLAME CURRENT TEST JACKS
PLUG-IN
PURGE
CARD
DUST
COVER
RELAY
MODULE
FLAME
M7552B
Recognized.
Fig. 1. Burner Control Module and sequence status LEDs.
Federal Communications Commission: Part 15,
Class B—Emissions.
Mounting:
Q520A 20-terminal Subbase for panel mounting.

SPECIFICATIONS

Required Components:
Plug-in Flame Signal Amplifier. See Table 1.
Electrical Ratings (See Table 1):
Plug-in Purge Timer Cards. See Table 2.
Voltage and Frequency: 120 Vac (+10%/-15%), 50 or 60 Hz
(±10%).
Power Dissipation in the Run Mode: 10W maximum.
Table 1. Flame Detection Systems.
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Flame
Failure
Response
Type Color Self-Checking Model
Rectification Green No
No
Dynamic Ampli-Check
®
Dynamic Ampli-Check®R7847B
R7847A
R7847A
R7847B
Time (sec)
e
0.8 or 3 Gas Rectifying Flame
e
3 Gas, oil,
c,e
0.8 or 3 Gas Rectifying Flame
c,e
3 Gas, oil,
a
Fuel Type Models
coal
coal
Infrared Red No R7848A 3 Gas, oil,
coal
Dynamic Ampli-Check
®
R7848B
c
3 Gas, oil,
coal
Rod Holders
f
Ultraviolet (Purple
®
Peeper
)
Rod Holders
Ultraviolet (Purple Peeper®)
Infrared (Lead Sulfide)
Infrared (Lead Sulfide)
C7004, C7007, C7011 Complete Assemblies: C7008, C7009, Q179
C7012A,C.
C7004, C7007, C7011 Complete Assemblies: C7008, C7009, Q179
C7012A,C
C7015
C7015
66-1153—2 2
R7140G,L,M BURNER CONTROL MODULES
Table 1. Flame Detection Systems. (Continued)
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Flame
Failure
Response
Type Color Self-Checking Model
Time (sec)
Ultraviolet Purple No R7849A 0.8 or 3 Gas, oil Ultraviolet
Dynamic Ampli-Check
Dynamic Self-Check
Blue Dynamic
Self-Check
®
R7849B
R7861A
R7886A
c
0.8 or 3 Gas, oil Ultraviolet
b
0.8 or 3 Gas, oil,
b
3 Gas, oil,
a
Fuel Type Models
(Minipeeper)
(Minipeeper)
C7027, C7035, C7044
C7027, C7035, C7044
Ultraviolet C7061
coal
C7076
coal
Ultraviolet (Adjustable Sensitivity)
Optical White Dynamic
Ampli-Check
®
Dynamic Self-Check
a
Flame Failure Response Time (FFRT) depends on selection of amplifier.
b
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner
R7851B 0.8 or 3 Gas, oil,
coal
b
R7851C
3 Gas, oil,
coal
Optical (UV, IR, Visible Light)
C7927, C7935, C7915, C7962
Optical (UV only) C7961
operation and shuts down burner if detection system fails.
c
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
d
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every 24 hours. Use C7961 Flame Detector with R7851C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously for 24 hours or longer.
e
R7847A,B Amplifiers with 0.8 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
f
Order flame rod separately; see flame detector Instructions for holder.
d
d
Table 2. Plug-in Purge Timer Cards.
Pre-Purge Timing Product Number
7 ST7800A1013 30 ST7800A1039 40 ST7800A1047 60 ST7800A1054 90 ST7800A1062
Above times cover the Purge timings of the R4140/50 Pro-
grammers and PM720.
Other timings exist—consult the Tradeline catalog for com-
plete list of ST7800 Purge timers.
Accessories:
The following accessories enhance the R7140 Burner Control
Module and are available through local 7800 SERIES distributors.
Keyboard Display Modules (KDM):
S7800A1001 English language. S7800A1035 French language. S7800A1043 German language. S7800A1050 Italian language. S7800A1068 Spanish language. S7800A1118 Katakana (Japanese) language. S7800A1126 Portuguese language. S7800A1142 English language.
Communications:
Q7700A1015 Network Interface Unit, 120 Vac, 50/60 Hz
applications, external modem required.
Q7700B1004 Network Interface Unit with universal 100 to
250 Vac, 50/60 Hz external power supply, external
modem required. QS7800A1001 ControlBus Module, standard. QS7800B1000 ControlBus Module, multidrop. QS7850A1001 ControlBus Module, General Purpose
Interface. ZM7850A1006 Combustion System Manager
®
software.
S7810A1009 Data ControlBus Module™ (if no KDM is
used). S7810B1007 Data ControlBus Module™, Multi-Drop
Switch Module. S7810M1003 ModBus™ Module.
Miscellaneous:
S7820A1007 Remote Reset Module. S7830A1005 Expanded Annunciator, 120 Vac, 50/60 Hz. 203541 Data ControlBus Connector, 5-wire. 203765 Remote Display Mounting Bracket. 221729 Dust cover, Relay Module. 204718A Keyboard Display Module Cover, NEMA 4, clear. 204718B Keyboard Display Module Cover, NEMA 1, clear. 204718C Keyboard Display Module Cover, NEMA 4, clear
with reset button. 205321 Flush Display mounting kit. 221818A Extension Cable, display, 5 ft. (1524 mm). 221818C Extension Cable, display, 10 ft. (3048 mm). FSP5004 Tester. 123514A Rectification Flame Simulator. 203659 Ultraviolet Flame Simulator.
3 66-1153—2
R7140G,L,M BURNER CONTROL MODULES
BURNER CONTROL
5-3/4 (146)
1-1/4
(32)
5
(127)
POWER PILOT FLAME MAIN ALARM
RESET
_
S
5
(127)
7
(177)
+
6-5/32
(156)
M22604
Fig. 2. Mounting dimensions of R7140G,L,M Burner Control Module with Q520A Subbase, in in. (mm).
Table 3. Terminal Ratings.
Terminal No. Description Ratings
G
Earth G
Flame Sensor Earth Ground
Earth Ground
a
a
L2(N) Line Voltage Common — L1 Line Voltage Supply (L1) 120 Vac (+10/-15%), 50 or 60 Hz (±10%). 3 Lockout/Running Interlock 120 Vac, 8A run, 43A inrush. 4 Pre-Ignition Interlock Input 120 Vac, 1 mA. 5 Pilot Valve/Ignition 120 Vac. See Table 4. 6 Interrupted/Intermittent Pilot Valve/First Stage Oil Valve 120 Vac. See Table 4. 7 Main Fuel Valve 120 Vac. See Table 4. 8 Burner Motor 120 Vac, 9.8 AFL, 58.8 ALR (inrush). 9 Alarm 120 Vac, 1A pilot duty. 10 Firing Rate High Fire 120 Vac, 75 VA pilot duty. 11 Firing Rate Common 120 Vac, 75 VA pilot duty. 12 Firing Rate Modulate 120 Vac, 75 VA pilot duty. 13 Low Fire Switch Input 120 Vac, 1 mA. 14 Firing Rate Low Fire 120 Vac, 75 VA pilot duty. 15 High Fire Switch Input 120 Vac, 1 mA. 16 Burner Controller and Limits 120 Vac, 1 mA. 17 Shutter 120 Vac, 0.5A. 18 Ignition
120 Vac,
4.5A ignition.
F Flame Sensor 60 to 220 Vac, current limited.
a
The R7140 must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth ground wire must be capable of conducting the current to blow the 15A fast blow fuse (or breaker) in the event of an internal short circuit. The R7140 needs a low impedance ground connection to the equipment frame, which, in turn, needs a low impedance connection to earth ground.
66-1153—2 4
R7140G,L,M BURNER CONTROL MODULES
Table 4. Terminal Ratings.
Terminal Typical Load Maximum Rating at 120 Vac, 60 Hz
5 or 6 Ignition
7 Main Fuel Valve(s) (solenoid/
Device Initiate Standby Purge
R7140G 10 sec. * ** 4 or 10
R7140L 10 or 15
R7140M 10 sec. or
a
30 seconds with JR2 clipped and jumper from terminal 8 to terminal 15.
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A purge card is selected; 15 timings are available from 2 seconds to 30 minutes.
Transformer/Pilot Valve/First Stage Fuel Valve
motorized/diaphragm) and Vent Valve, if required
4.5A ignition and 50 VA pilot duty, or
2.5A ignition and 75 VA pilot duty.
250 VA pilot duty or 65 VA pilot duty in parallel with motorized valve(s) using a total of 1150 VA locked rotor (inrush), 460 VA to open, and 250 VA to hold or motorized valve(s) using a total of 1500 VA locked rotor (inrush), 600 VA to open, and 250 VA to hold.
Table 5. Sequence Timing for Normal Operation.
Flame
Establishing
Period
sec.
10, 15 sec.a or
intermittent.
sec.
intermittent
a
Post
Purge
Run
Timing Interlock Circuits
* 15 sec. Pre-Ignition,
Running, Low Fire
Pre-Ignition, Lockout High and Low Fire
Pre-Ignition, Running, isolated Low Fire.
Firing
Rate
Circuit
4-wire modulating
2-wire isolated On-Off-On contacts
Energy Saving
Pre-Purge
No UL/CSA
Approval
BodiesPilot Main
Modulating
FM/IRI Modulating
UL/CSA On-Off.
Code
NOTE: Allowable inrush can be up to ten times the pilot duty
rating.
EXAMPLE: Pilot duty rating = 50 VA.
At 120 V, running current is: 50/120 = 0.42A.
Maximum allowable inrush is ten times 0.42A = 4.2A.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard. Can cause property damage, severe injury, or death.
To prevent possible hazardous burner operation, verify safety requirements each time a control is installed on a burner.
WARNING
Electrical Shock Hazard. Can cause serious injury or death.
Disconnect the power supply before beginning installation. More than one power supply disconnect may be required.
5 66-1153—2
R7140G,L,M BURNER CONTROL MODULES
IMPORTANT
1. Wiring connections for the relay modules are unique; therefore, refer to Fig. 4–11 or the correct Specifications for proper subbase wiring, and sequence charts.
2. Wiring must comply with all applicable codes, ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
4. Loads connected to the R7140 must not exceed those listed in the Specifications; see Table 3 and 4.
5. Limits and interlocks must be rated to simultaneously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component recognized by authorities who have jurisdiction for the specific purpose for which they are used.
7. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s).
8. Two Flame Detectors can be connected in parallel with the exception of flame detectors C7015, C7927, C7935, C7915, C7961, and C7962.
9. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference; in which case, the users at their own expense may be required to take whatever measures are required to correct this interference.
10.This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.

Location

Humidity
Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85 percent relative humidity continuous, noncondensing moisture environment. Condensing moisture may cause a safety shutdown.
Vibration
Do not install the relay module where it could be subjected to vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weathertight. When installed outdoors, protect the relay module using an approved weathertight enclosure.

Mounting Wiring Subbase

1. Mount the subbase in any position except horizontally
with the quadfurcated contacts pointing down. The standard vertical position is recommended. Any other position decreases the maximum ambient temperature rating.
2. Select a location on a wall, burner, or electrical panel.
The Q520A can be mounted directly in the control cabinet. Be sure to allow adequate clearance for servicing, installation, access or removal of the R7140, Expanded Annunciator, Keyboard Display Module, flame amplifier, flame amplifier signal voltage probes, Run/Test Switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a
template to mark the four screw locations. Drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws.

Wiring Subbase

WARNING
Electrical Shock Hazard. Can cause serious injury, death or equipment damage.
Disconnect the power supply before beginning installation to prevent electrical shock, equipment and control damage. More than one power supply disconnect may be required.
1. For proper subbase wiring, internal drawings, and
sequence check charts, refer to Fig. 5, 6, 7, 8, 9 and 11.
2. Disconnect the power supply from the main disconnect
before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be required.
3. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Voltage) wiring. a. Follow recommended wire size and type. b. Follow recommended grounding practices.
4. Recommended wire routing of leadwires:
a. Do not run high voltage ignition transformer wires in
the same conduit with the flame detector.
b. Do not route flame detector leadwires in conduit
with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector Instructions.
5. Maximum wire lengths follow:
a. R7140 leadwires—The maximum length of leadwire
is 300 feet to terminal inputs (Control, Pre-Ignition Interlock, Running/Lockout Interlock, High Fire Switch and Low Fire Switch).
b. Flame Detector leadwires—The maximum flame
sensor leadwire length is limited by the flame signal strength.
c. Remote Reset leadwires—The maximum length of
wire is 1000 feet to a Remote Reset push button.
6. Make sure loads do not exceed the terminal ratings.
Refer to the label on the R7140 or to the ratings in Table 3 and 4.
66-1153—2 6
R7140G,L,M BURNER CONTROL MODULES

Final Wiring Check

1. Check the power supply circuit. The voltage and
frequency tolerance must match those of the R7140. A separate power supply circuit may be required for the R7140. Add the required disconnect means and overload protection.
2. Check all wiring circuits and complete the Static
Checkout, Table 8, before installing the R7140 on the subbase.
3. Install all electrical connectors.
4. Restore power to the panel.
Service Notes:
Check the Q520 Wiring Subbase terminals against the typical wiring drawings, Figures 7, 8, 12, 13, 17, or 18.
If wires are attached to terminals that are unused in the figures, DO NOT INSTALL THE R7140 until you have identified the connections’ functions. Most likely the old subbase terminals were used as tie points, so removing the wires, capping with a wire nut, and tucking the wire down into the subbase is all that needs to be done.
Make sure the wiring subbase of the old device is a 20-terminal Q520 (four rows of 5 terminals).
Make sure the system Controller is connected to the correct terminal on the Q520 wiring subbase. It may be in a wire nut tucked into the subbase. It needs to be connected to a terminal (like terminal 4 or 16).
Make sure there is an electrical service ground wire connection to the G terminal in the wiring subbase.
Replacing GP201 or GP301 devices:
— High Fire (or Purge Rate) Switch may be connected to
terminal D.
— Identify, remove, and connect to terminal M.
Replacing GP101 devices:
— Check wiring subbase. If D is jumpered to 8, remove
the jumper.
Replacing R4140 programmers on Carlin 1050 and 1150 burners:
— Remove jumper from 6 to 7. — Remove jumper from L2 to 12 and wire nut the wires
together. Note: There will be no wire on terminal 12. R4140M replacements:
Check terminal 13 of the Q520 wiring subbase.
— If nothing is on 13, install the new R7140M1007. — If 13 is jumpered to 8, remove the jumper and install
R7140M1007.
— If 13 goes somewhere (assume a low fire switch
because the system has a damper motor), remove J1
and J2 from the back of the R7140M1007. NOTE: J1 and J2 provide an input for the R7140M when the
system does not have a spring return damper with a low fire switch.
Leaving J1 and J2 in place with either 13 jumpered to 8 or with the low fire switch will cause the blower motor to come on after the R7140M is installed and power is supplied to the system.
Generally, the following table will apply to select the R7140M1007 model and the status of jumpers J1 and J2.
Table 6. J1/J2 Jumper Configuration for R4140M/PM720M.
Model Purge Timer Leave J1 & J2 Remove J1 and J2
R4140M1004/M1012 A1039 X
R4140M1020/M1038 A1047 X
R4140M1046/M1053 A1062 X
R4140M1079 (GP101) A1062 X
R4140M1103/M1111 A1039 X
R4140M1145/M1152 A1047 X
R4140M1160/M1178 A1062 X
R4140M1186 A1047 X
R4140M1194 ST7800A1062
BC7000L1000 w/PM720M2002 ST7800A1062 X
BC7000L1000 w/PM720M2036 * X
* Check terminal 8 and 15.
If jumpered, ST7800A1031 (7 second purge). If not jumpered, ST7800A1039 (30 second purge).
7 66-1153—2
R7140G,L,M BURNER CONTROL MODULES

Mounting R7140 Relay Module

Installing the Programmer (Fig. 3)
WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power before installation to prevent electrical shock. More than one disconnect may be involved.
1. Open the master switch.
2. Make sure no subbase wiring is projecting out beyond
the terminal blocks. Tuck in wiring against the back of the subbase so it does not interfere with the contacts.
3. Grasp the programmer chassis and engage the chassis
hinge brackets with the pivot pins at the bottom of the subbase.
4. Swing the chassis inward until the spring connectors
engage the knifeblade contacts. Push in until the contacts are fully engaged.
5. Tighten the chassis retaining screw securely.
6. Close the master switch to restore power.
PREPURGE HOLD DRIVE TO LOW FIRE
BURNER/BLOWER MOTOR
15 SEC. INTERRUPTED PILOT VALVE
RUNNING INTERLOCKS CLOSED
TO
LED DISPLAY
BURNER
OPERATING CONTROLS AND INTERLOCKS
FLAME SIGNAL
FIRING RATE MOTOR
INITIATE (INITIAL POWERUP ONLY)
POWER
INTERLOCK. CHECK
STANDBY
00 00 10 25 00 1520
TIMED PREPURGE
POWER
POWER
PILOT
FLAME
MAIN
LIMITS AND BURNER CONTROLLER CLOSED
PII CLOSED
SAFE START CHECK
R7140G SWITCHING
10 11
MOTOR ACTION
POWER
PILOT
FLAME
MAIN
18
2
LOW FIRE SW.
14 11
Removing the Programmer
1. Open the master switch.
2. Loosen the chassis retaining screw.
3. Pull outward on the top of the chassis.
4. Disengage the chassis hinge brackets from the subbase
pivot pins.
KNIFE-BLADE
WIRING SUBBASE
Fig. 3. Mounting the programmer on the subbase.
R7140G
PFEP 10 SEC.
00
(4 SEC. IF JR1
CLIPPED
POWER
PILOT
FLAME
MAIN
IGN.
5 SEC.
10 SEC. IGN./PILOT
16
4
TO
TO
CONTACTS (20)
PIVOT PIN (2)
MFEP
POWER
PILOT
FLAME
MAIN
ALARMALARMALARMALARM
5
6
MAIN VALVE
TO
L1
16
13
8
TO
FLAME PROVING
RUN
POWER
PILOT
FLAME
MAIN
ALARM
8
16
3
3TO
3
10 11
TO
POSTPURGE
1
7
14 11
SPRING CONNECTORS
HINGE BRACKET (2)
POWER
TO
STANDBY
POWER
IC
SSC
CHASSIS RETAINING SCREW
PROGRAMMER CHASSIS
M22605
TERMINAL 6 HAS THE FOLLOWING OPTIONS:
1
AS RECEIVED - INTERMITTENT PILOT JR2 CLIPPED - 15 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT) JR2 CLIPPED PLUS TERMINALS 8 - 15 JUMPERED - 30 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT)
PII MEANS PRE-IGNITION INTERLOCK.
2
FOR R7140G1000:
3
L1 TO 4 4 TO 3
Fig. 4. Operating sequence, R7140G1000/R7140G2008.
66-1153—2 8
M23319
L1
RESET PUSHBUTTON
RUN/TEST SWITCH
CONFIGURATION JUMPERS
MICROCOMPUTER
RELAY DRIVE CIRCUIT
L1 (HOT) L2
1
120 Vac, 50/60 Hz
2K
3K
4K
5K
6K
7K
8K
9K
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
PLUG-IN FLAME AMPLIFIER
TEST
R7140G,L,M BURNER CONTROL MODULES
TEST JACK
F
G
17
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
SAFETY RELAY
6K1
3K1
RS485
2
CIRCUIT
PRE-IGNITION INTERLOCK
4
LOW FIRE SWITCH
13
REMOTE
3
RESET
R1
STATUS LEDs
LIMITS
CONTROLLER
KEYBOARD DISPLAY MODULE
DDL
DDL COMMUNICATIONS
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
8K1
8K2
9K2
1K
RUNNING/ LOCKOUT INTERLOCK
16
HIGH FIRE
COMMON
MODULATE
LOW FIRE
POWER SUPPLY
9K1
1K1 2K1 5K1
3
10
11
12
14
CONTROL POWER
R1
IGNITION
18
4K1
7K1
2K2
INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLT INPUTS
FIELD WIRING INTERNAL WIRING
5
6
7
8
9
PILOT
PILOT/V2
MAIN VALVE
BLOWER
ALARM
L2
M23320
Fig. 5. Internal block diagram of the R7140G1000. (See Fig. 8 for detailed wiring.)
9 66-1153—2
R7140G,L,M BURNER CONTROL MODULES
L1
CONFIGURATION JUMPERS
RUN/TEST SWITCH
CONTROLLER
LIMITS
16
13
6K1
3K1
MICROCOMPUTER
PRE-IGNITION INTERLOCK
RUNNING/ LOCKOUT INTERLOCK
LOW FIRE SWITCH
8K1
8K2
9K2
L1 (HOT)
1
120 Vac, 50/60 Hz
POWER SUPPLY
4
1K1 2K1 5K1
3
HIGH FIRE
COMMON
MODULATE
9K1
LOW FIRE
L2
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
4K1
7K1
2K2
12
13
15
14
TEST
TEST JACK
F
PLUG-IN FLAME AMPLIFIER
CONTROL POWER
18
5
6
7
8
9
INDICATES FEEDBACK SENSING
OF RELAY CONTACT STATUS
AND LINE VOLT INPUTS
FIELD WIRING
INTERNAL WIRING
G
17
IGNITION
PILOT
PILOT/V2
MAIN VALVE
BLOWER
ALARM
L2
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 6. Internal block diagram of the R7140G2008. (See Fig. 7 for detailed wiring.)
66-1153—2 10
M23321
Loading...
+ 22 hidden pages