• Device status available to ModBus™ through S7810M
• Safety features:
• Access for external electrical voltage checks.
• Application flexibility.
• 0.8 or 3.0 second Flame Failure Response Time
• Dependable, long-term operation provided by
APPLICATION
The Honeywell R7140G,L,M Burner Control Modules are
microprocessor-based integrated burner controls for
automatically fired gas, oil or combination fuel single burner
applications. The Burner Control Module system consists of a
Relay Module, Q520A Subbase, Amplifier and Purge Card.
Options include S7800 Keyboard Display Modules (KDM).
The R7140 Burner Control Modules directly replace many
BC7000 PM720G,L,M, and many R4150G,L,M and
R4140G,L,M units using the existing Q520A 20-terminal
Wiring Subbase.
The R7140 can be demonstrated or tested on the FSP5004
tester. Note that the R7849 UV Amplifier or the R7851 Optical
Flame Amplifier cannot be tested.
The R7140G,L,M is programmed to provide a level of safety,
functional capability and features beyond the capacity of
conventional controls.
Functions provided by the R7140G,L,M include automatic
burner sequencing, flame supervision, system status
indication, system or self-diagnostics and troubleshooting.
• Five LEDs for sequence information. See Fig. 1.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Nonvolatile memory; R7140 retains history files and
• Report generation (optional).
NOTE: Check Service Notes on page 7 and Static Checkout
• Burner controller data (optional):
• Status of configuration jumpers.
• Status of Run/Test Switch.
INSTALLATION INSTRUCTIONS
card or S7800A1001 Series 5 Keyboard Display.
— Interlock check.
— Closed loop logic test.
— Dynamic AMPLI-CHECK™.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Expanded safe-start check.
— High Fire Purge Switch test (R7140L only).
— Internal hardware status monitoring.
— Low Fire Start Switch test.
— Tamper resistant timing and logic.
(FFRT), depending on amplifier selected.
microcomputer technology.
sequencing status after loss of power and can be
viewed using the Keyboard Display Module
S7800A1001 (sold separately).
on page 25 prior to installation of R7140.
— Lockout/alarm status.
— Total cycles of operation.
— Total hours of operation.
66-1153-2
R7140G,L,M BURNER CONTROL MODULES
Maximum Total Connected Load: 2000VA.
RUN/TEST SWITCH
Fusing—Total Connected Load: 15A fast blow, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C).
Humidity: 85% relative humidity, continuous, noncondensing.
Vibration: 0.5G environment.
Weight:
With Dust Cover and Q520A Subbase: 4 lb., 5 oz. (1.96 kg).
Dimensions:
See Fig. 2.
Approvals:
Underwriters Laboratories Inc. UL, CUL Component
SEQUENCE
STATUS
LEDs
RESET
PUSHBUTTON
FLAME
SIMULATOR INPUT
AMPLIFIER
FLAME CURRENT
TEST JACKS
PLUG-IN
PURGE
CARD
DUST
COVER
RELAY
MODULE
FLAME
M7552B
Recognized.
Fig. 1. Burner Control Module and sequence status LEDs.
Federal Communications Commission: Part 15,
Class B—Emissions.
Mounting:
Q520A 20-terminal Subbase for panel mounting.
SPECIFICATIONS
Required Components:
Plug-in Flame Signal Amplifier. See Table 1.
Electrical Ratings (See Table 1):
Plug-in Purge Timer Cards. See Table 2.
Voltage and Frequency: 120 Vac (+10%/-15%), 50 or 60 Hz
(±10%).
Power Dissipation in the Run Mode: 10W maximum.
Table 1. Flame Detection Systems.
Plug-in Flame Signal AmplifiersApplicable Flame Detectors
Plug-in Flame Signal AmplifiersApplicable Flame Detectors
Flame
Failure
Response
TypeColorSelf-CheckingModel
Time (sec)
UltravioletPurple NoR7849A0.8 or 3Gas, oil Ultraviolet
Dynamic
Ampli-Check
Dynamic
Self-Check
BlueDynamic
Self-Check
®
R7849B
R7861A
R7886A
c
0.8 or 3Gas, oil Ultraviolet
b
0.8 or 3 Gas, oil,
b
3Gas, oil,
a
FuelTypeModels
(Minipeeper)
(Minipeeper)
C7027, C7035, C7044
C7027, C7035, C7044
UltravioletC7061
coal
C7076
coal
Ultraviolet
(Adjustable
Sensitivity)
OpticalWhiteDynamic
Ampli-Check
®
Dynamic
Self-Check
a
Flame Failure Response Time (FFRT) depends on selection of amplifier.
b
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner
R7851B0.8 or 3Gas, oil,
coal
b
R7851C
3Gas, oil,
coal
Optical (UV, IR,
Visible Light)
C7927, C7935, C7915,
C7962
Optical (UV only) C7961
operation and shuts down burner if detection system fails.
c
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
d
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every 24 hours. Use C7961 Flame
Detector with R7851C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier
as ultraviolet flame detection system for appliances with burners that remain on continuously for 24 hours or longer.
e
R7847A,B Amplifiers with 0.8 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
f
Order flame rod separately; see flame detector Instructions for holder.
Above times cover the Purge timings of the R4140/50 Pro-
grammers and PM720.
Other timings exist—consult the Tradeline catalog for com-
plete list of ST7800 Purge timers.
Accessories:
The following accessories enhance the R7140 Burner Control
Module and are available through local 7800 SERIES
distributors.
Keyboard Display Modules (KDM):
S7800A1001 English language.
S7800A1035 French language.
S7800A1043 German language.
S7800A1050 Italian language.
S7800A1068 Spanish language.
S7800A1118 Katakana (Japanese) language.
S7800A1126 Portuguese language.
S7800A1142 English language.
Communications:
Q7700A1015 Network Interface Unit, 120 Vac, 50/60 Hz
applications, external modem required.
Q7700B1004 Network Interface Unit with universal 100 to
Fig. 2. Mounting dimensions of R7140G,L,M Burner Control Module with Q520A Subbase, in in. (mm).
Table 3. Terminal Ratings.
Terminal No.DescriptionRatings
G
Earth G
Flame Sensor Earth Ground
Earth Ground
a
a
—
—
L2(N)Line Voltage Common—
L1Line Voltage Supply (L1)120 Vac (+10/-15%), 50 or 60 Hz (±10%).
3Lockout/Running Interlock120 Vac, 8A run, 43A inrush.
4Pre-Ignition Interlock Input120 Vac, 1 mA.
5Pilot Valve/Ignition120 Vac. See Table 4.
6Interrupted/Intermittent Pilot Valve/First Stage Oil Valve 120 Vac. See Table 4.
7Main Fuel Valve120 Vac. See Table 4.
8Burner Motor120 Vac, 9.8 AFL, 58.8 ALR (inrush).
9Alarm120 Vac, 1A pilot duty.
10Firing Rate High Fire120 Vac, 75 VA pilot duty.
11Firing Rate Common120 Vac, 75 VA pilot duty.
12Firing Rate Modulate120 Vac, 75 VA pilot duty.
13Low Fire Switch Input120 Vac, 1 mA.
14Firing Rate Low Fire120 Vac, 75 VA pilot duty.
15High Fire Switch Input120 Vac, 1 mA.
16Burner Controller and Limits120 Vac, 1 mA.
17Shutter120 Vac, 0.5A.
18Ignition
120 Vac,
4.5A ignition.
FFlame Sensor60 to 220 Vac, current limited.
a
The R7140 must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth
ground wire must be capable of conducting the current to blow the 15A fast blow fuse (or breaker) in the event of an internal short
circuit. The R7140 needs a low impedance ground connection to the equipment frame, which, in turn, needs a low impedance
connection to earth ground.
66-1153—24
R7140G,L,M BURNER CONTROL MODULES
Table 4. Terminal Ratings.
TerminalTypical LoadMaximum Rating at 120 Vac, 60 Hz
5 or 6Ignition
7Main Fuel Valve(s) (solenoid/
Device Initiate Standby Purge
R7140G 10 sec.***4 or 10
R7140L10 or 15
R7140M10 sec. or
a
30 seconds with JR2 clipped and jumper from terminal 8 to terminal 15.
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A purge card is selected; 15 timings are available from 2 seconds to 30 minutes.
Transformer/Pilot
Valve/First Stage Fuel Valve
motorized/diaphragm) and
Vent Valve, if required
4.5A ignition and 50 VA pilot duty, or
2.5A ignition and 75 VA pilot duty.
250 VA pilot duty or 65 VA pilot duty in parallel with motorized valve(s) using a total of
1150 VA locked rotor (inrush), 460 VA to open, and 250 VA to hold or motorized valve(s)
using a total of 1500 VA locked rotor (inrush), 600 VA to open, and 250 VA to hold.
Table 5. Sequence Timing for Normal Operation.
Flame
Establishing
Period
sec.
10, 15
sec.a or
intermittent.
sec.
intermittent
a
Post
Purge
Run
Timing Interlock Circuits
*15 sec. Pre-Ignition,
Running, Low Fire
Pre-Ignition,
Lockout High and
Low Fire
Pre-Ignition,
Running, isolated
Low Fire.
Firing
Rate
Circuit
4-wire
modulating
2-wire
isolated
On-Off-On
contacts
Energy
Saving
Pre-Purge
NoUL/CSA
Approval
BodiesPilotMain
Modulating
FM/IRI
Modulating
UL/CSA
On-Off.
Code
NOTE: Allowable inrush can be up to ten times the pilot duty
rating.
EXAMPLE: Pilot duty rating = 50 VA.
At 120 V, running current is:
50/120 = 0.42A.
Maximum allowable inrush is ten times 0.42A = 4.2A.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury,
or death.
To prevent possible hazardous burner operation, verify
safety requirements each time a control is installed on
a burner.
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect the power supply before beginning
installation. More than one power supply disconnect
may be required.
566-1153—2
R7140G,L,M BURNER CONTROL MODULES
IMPORTANT
1. Wiring connections for the relay modules are unique;
therefore, refer to Fig. 4–11 or the correct
Specifications for proper subbase wiring, and
sequence charts.
2. Wiring must comply with all applicable codes,
ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage)
wiring.
4. Loads connected to the R7140 must not exceed
those listed in the Specifications; see Table 3 and 4.
5. Limits and interlocks must be rated to simultaneously
carry and break current to the ignition transformer,
pilot valve, and main fuel valve(s).
6. All external timers must be listed or component
recognized by authorities who have jurisdiction for
the specific purpose for which they are used.
7. For on-off gas-fired systems, some authorities who
have jurisdiction prohibit the wiring of any limit or
operating contacts in series between the flame
safeguard control and the main fuel valve(s).
8. Two Flame Detectors can be connected in parallel
with the exception of flame detectors C7015, C7927,
C7935, C7915, C7961, and C7962.
9. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used
in accordance with the instructions, may cause
interference to radio communications. It has been
tested and found to comply with the limits for a
Class B computing device of Part 15 of FCC rules
which are designed to provide reasonable protection
against such interference when operated in a
commercial environment. Operation of this
equipment in a residential area may cause
interference; in which case, the users at their own
expense may be required to take whatever
measures are required to correct this interference.
10.This digital apparatus does not exceed the Class B
limits for radio noise for digital apparatus set out in
the Radio Interference Regulations of the Canadian
Department of Communications.
Location
Humidity
Install the relay module where the relative humidity never
reaches the saturation point. The relay module is designed to
operate in a maximum 85 percent relative humidity
continuous, noncondensing moisture environment.
Condensing moisture may cause a safety shutdown.
Vibration
Do not install the relay module where it could be subjected to
vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weathertight.
When installed outdoors, protect the relay module using an
approved weathertight enclosure.
Mounting Wiring Subbase
1. Mount the subbase in any position except horizontally
with the quadfurcated contacts pointing down. The
standard vertical position is recommended. Any other
position decreases the maximum ambient temperature
rating.
2. Select a location on a wall, burner, or electrical panel.
The Q520A can be mounted directly in the control
cabinet. Be sure to allow adequate clearance for
servicing, installation, access or removal of the R7140,
Expanded Annunciator, Keyboard Display Module,
flame amplifier, flame amplifier signal voltage probes,
Run/Test Switch, electrical signal voltage probes and
electrical field connections.
3. For surface mounting, use the back of the subbase as a
template to mark the four screw locations. Drill the pilot
holes.
4. Securely mount the subbase using four no. 6 screws.
Wiring Subbase
WARNING
Electrical Shock Hazard.
Can cause serious injury, death or equipment
damage.
Disconnect the power supply before beginning
installation to prevent electrical shock, equipment
and control damage. More than one power supply
disconnect may be required.
1. For proper subbase wiring, internal drawings, and
sequence check charts, refer to Fig. 5, 6, 7, 8, 9 and 11.
2. Disconnect the power supply from the main disconnect
before beginning installation to prevent electrical shock
and equipment damage. More than one disconnect may
be required.
3. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where
required, must comply with NEC, Class 1 (Line Voltage)
wiring.
a. Follow recommended wire size and type.
b. Follow recommended grounding practices.
4. Recommended wire routing of leadwires:
a. Do not run high voltage ignition transformer wires in
the same conduit with the flame detector.
b. Do not route flame detector leadwires in conduit
with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector Instructions.
5. Maximum wire lengths follow:
a. R7140 leadwires—The maximum length of leadwire
is 300 feet to terminal inputs (Control, Pre-Ignition
Interlock, Running/Lockout Interlock, High Fire
Switch and Low Fire Switch).
b. Flame Detector leadwires—The maximum flame
sensor leadwire length is limited by the flame signal
strength.
c. Remote Reset leadwires—The maximum length of
wire is 1000 feet to a Remote Reset push button.
6. Make sure loads do not exceed the terminal ratings.
Refer to the label on the R7140 or to the ratings in Table
3 and 4.
66-1153—26
R7140G,L,M BURNER CONTROL MODULES
Final Wiring Check
1. Check the power supply circuit. The voltage and
frequency tolerance must match those of the R7140. A
separate power supply circuit may be required for the
R7140. Add the required disconnect means and
overload protection.
2. Check all wiring circuits and complete the Static
Checkout, Table 8, before installing the R7140 on the
subbase.
3. Install all electrical connectors.
4. Restore power to the panel.
Service Notes:
Check the Q520 Wiring Subbase terminals against the typical
wiring drawings, Figures 7, 8, 12, 13, 17, or 18.
If wires are attached to terminals that are unused in the
figures, DO NOT INSTALL THE R7140 until you have
identified the connections’ functions. Most likely the old
subbase terminals were used as tie points, so removing the
wires, capping with a wire nut, and tucking the wire down into
the subbase is all that needs to be done.
Make sure the wiring subbase of the old device is a
20-terminal Q520 (four rows of 5 terminals).
Make sure the system Controller is connected to the correct
terminal on the Q520 wiring subbase. It may be in a wire nut
tucked into the subbase. It needs to be connected to a
terminal (like terminal 4 or 16).
Make sure there is an electrical service ground wire
connection to the G terminal in the wiring subbase.
Replacing GP201 or GP301 devices:
— High Fire (or Purge Rate) Switch may be connected to
terminal D.
— Identify, remove, and connect to terminal M.
Replacing GP101 devices:
— Check wiring subbase. If D is jumpered to 8, remove
the jumper.
Replacing R4140 programmers on Carlin 1050 and 1150
burners:
— Remove jumper from 6 to 7.
— Remove jumper from L2 to 12 and wire nut the wires
together. Note: There will be no wire on terminal 12.
R4140M replacements:
Check terminal 13 of the Q520 wiring subbase.
— If nothing is on 13, install the new R7140M1007.
— If 13 is jumpered to 8, remove the jumper and install
R7140M1007.
— If 13 goes somewhere (assume a low fire switch
because the system has a damper motor), remove J1
and J2 from the back of the R7140M1007.
NOTE: J1 and J2 provide an input for the R7140M when the
system does not have a spring return damper with a
low fire switch.
Leaving J1 and J2 in place with either 13 jumpered
to 8 or with the low fire switch will cause the blower
motor to come on after the R7140M is installed and
power is supplied to the system.
Generally, the following table will apply to select the
R7140M1007 model and the status of jumpers J1
and J2.
Table 6. J1/J2 Jumper Configuration for R4140M/PM720M.
ModelPurge TimerLeave J1 & J2Remove J1 and J2
R4140M1004/M1012A1039X
R4140M1020/M1038A1047X
R4140M1046/M1053A1062X
R4140M1079 (GP101)A1062X
R4140M1103/M1111A1039X
R4140M1145/M1152A1047X
R4140M1160/M1178A1062X
R4140M1186A1047X
R4140M1194ST7800A1062
BC7000L1000 w/PM720M2002ST7800A1062X
BC7000L1000 w/PM720M2036*X
* Check terminal 8 and 15.
If jumpered, ST7800A1031 (7 second purge).
If not jumpered, ST7800A1039 (30 second purge).
766-1153—2
R7140G,L,M BURNER CONTROL MODULES
Mounting R7140 Relay Module
Installing the Programmer (Fig. 3)
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power before installation to prevent
electrical shock. More than one disconnect may be
involved.
1. Open the master switch.
2. Make sure no subbase wiring is projecting out beyond
the terminal blocks. Tuck in wiring against the back of
the subbase so it does not interfere with the contacts.
3. Grasp the programmer chassis and engage the chassis
hinge brackets with the pivot pins at the bottom of the
subbase.
4. Swing the chassis inward until the spring connectors
engage the knifeblade contacts. Push in until the
contacts are fully engaged.
5. Tighten the chassis retaining screw securely.
6. Close the master switch to restore power.
PREPURGE
HOLD
DRIVE TO
LOW FIRE
BURNER/BLOWER MOTOR
15 SEC. INTERRUPTED PILOT VALVE
RUNNING INTERLOCKS CLOSED
TO
LED
DISPLAY
BURNER
OPERATING
CONTROLS
AND
INTERLOCKS
FLAME
SIGNAL
FIRING
RATE
MOTOR
INITIATE
(INITIAL
POWERUP
ONLY)
POWER
INTERLOCK. CHECK
STANDBY
00001025001520
TIMED
PREPURGE
POWER
POWER
PILOT
FLAME
MAIN
LIMITS AND BURNER CONTROLLER CLOSED
PII CLOSED
SAFE START CHECK
R7140G SWITCHING
1011
MOTOR ACTION
POWER
PILOT
FLAME
MAIN
18
2
LOW FIRE SW.
1411
Removing the Programmer
1. Open the master switch.
2. Loosen the chassis retaining screw.
3. Pull outward on the top of the chassis.
4. Disengage the chassis hinge brackets from the subbase
pivot pins.
KNIFE-BLADE
WIRING
SUBBASE
Fig. 3. Mounting the programmer on the subbase.
R7140G
PFEP
10 SEC.
00
(4 SEC. IF
JR1
CLIPPED
POWER
PILOT
FLAME
MAIN
IGN.
5 SEC.
10 SEC. IGN./PILOT
16
4
TO
TO
CONTACTS (20)
PIVOT PIN (2)
MFEP
POWER
PILOT
FLAME
MAIN
ALARMALARMALARMALARM
5
6
MAIN VALVE
TO
L1
16
13
8
TO
FLAME PROVING
RUN
POWER
PILOT
FLAME
MAIN
ALARM
8
16
3
3TO
3
1011
TO
POSTPURGE
1
7
1411
SPRING
CONNECTORS
HINGE
BRACKET (2)
POWER
TO
STANDBY
POWER
IC
SSC
CHASSIS
RETAINING
SCREW
PROGRAMMER
CHASSIS
M22605
TERMINAL 6 HAS THE FOLLOWING OPTIONS:
1
AS RECEIVED - INTERMITTENT PILOT
JR2 CLIPPED - 15 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT)
JR2 CLIPPED PLUS TERMINALS 8 - 15 JUMPERED - 30 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT)