Honeywell R4500 Classic Data sheet

DR4500A Classic Series Circular Chart Recorder

Function

Honeywell’s Classic Series recorder combines the simplicity of pen drawn analog traces with the sophistication of microprocessor controlled functions. This combination results in a user configurable recorder that is easily adapted to meet a variety of application requirements—from blast furnace to laboratory.
In addition to recording analog traces, the Classic Series recorder continuously displays process variable values in the selected engineering units.
Both one-pen and two-pen models accept inputs from any one of a variety of sensors or transmitters within the configurable range limits. Also, models are available with one or two digital controllers to generate controlled output signals to operate valves, dampers, heating elements, etc. for process control.
Figure 1—Classic Series recorder provides analog trace and continuous digital indication of process variable value.
L
3IN 86.0
3IN 86.0
1559
1559
ruline
44-45-03-15
Page 1 of 12
Specification
20992

Features

Charts — Over 5000 preprinted charts are available to meet specific recording needs.
User configurable — means that users can set and/or alter operating parameters to fit their requirements, including type of input, without recalibration. English language prompts, coupled with simple keystroke sequences, make configuring the recorder easy and straightforward.
Operator interface — includes clear, brilliant alphanumeric displays; indicators; deviation bargraph; and keypad for visual and tactile interaction.
Ink cartridge — Disposable, fiber­tip ink cartridge for reliable recording with minimal maintenance.
Control Output — up to two versa­tile PID digital controllers lets users configure the exact control action needed for their process.
Alarms — Integral "soft" alarms are easily set by users to announce selected out-of-limit conditions.

Features, continued

Setpoint Ramp — A single setpoint ramp is user programmable and is easily repeated and activated through the Run/Hold key.
Setpoint Rate — lets you define a ramp rate applied to any local setpoint change. A separate upscale or downscale rate is configurable.
Set Point Ramp/Soak Programming — Lets users program and store 18 ramp and 18 soak segments. Run or Hold of program is keyboard or remote switch selectable. For each control loop, you can build up to 6 profiles using any number of consecutive segments of the program. You can select a recovery mode for powerup.
Accutune II™ — This standard feature provides a new, truly plug and play tuning algorithm, which will, at the touch of a button or through a digital input, accurately identify and tune any process including those with deadtime and integrating processes. This speeds up and simplifies start-up plus allows re-tuning at any setpoint.

Features, continued

Fuzzy Logic — This standard feature uses fuzzy logic to suppress process variable overshoot due to SP changes or externally induced process disturbances. It operates indepen­dently from AccutuneII tuning. It does not change the PID constants, but temporarily modifies the internal controller response to suppress overshoot. This allows more aggressive tuning to co-exist with smooth PV response. It can be enabled or disabled depending on the application or the control criteria.
External Interface
Selections
Alarm Output — Ties “soft” alarms to up to two integral SPST relays to activate users external equipment.
Modbus
option allows you to network your recorders to take advantage of overall monitoring of the system using an RS485 network.
Communications
Industrial Measurement and Control, 1100 Virginia Drive, Ft. Washington, PA 19034
Printed in U.S.A. © Copyright 2002—Honeywell
44-45-03-15 Page 2
External Interface
Selections, continued
Timer — This optional feature
provides a configurable time period of 0 to 99 hours, 59 minutes or units of minutes and seconds. It can be started via the keyboard, alarm 2, or by a digital input. The timer output is Alarm 1, which energizes at the end of the Timer Period. Alarm 1 can be automatically reset. The Timer Period can be changed between each batch. Status is shown on the lower display
• Digital Input — Allows users to ini­tiate, from a remote location through two dry contact closures, selected recorder functions, such as switching from automatic to manual control mode, from direct to reverse controller action, or reset totalizer.
Auxiliary Output — there is also a 4 to 20 mA current output available. It can be used to retransmit a process variable. In addition, the 4-20 outputs on the control board can be used as an auxiliary output if not used for control.

Options

Two Totalizers — one or two totalizers are available. Eight digit totals with multiplier on digital display.
Chart Illumination — Lights the chart area to improve readability in lower light areas.
Door Options — Choice of gray, black or blue doors with standard latch or optional lock.
Optional UL and FM approved NEMA4X door available.
CE Mark — Conformity with 73/23/EEC, Low Voltage Directive and 89/336/EEC EMC Directive.
Approval Body Options — FM approval, CSA certification and UL Listing or a combination is available.
Customer ID Tag — (30 characters max.)
*Restrictions apply -- Not all of the options an be supplied together
1
ALM
CHN
RSP
OUT
F
X HR
CHRT SP
A
%
FUNC
SET
UP
LOWR
DISP
MAN
AUTO
Figure 2—Operator interface includes displays and keypad for comprehensive interaction with the recorder and the process.
User Configurable
In the Classic Series recorder, microprocessor control replaces conventional electro-mechanical recording techniques. This means that the recorder’s capabilities are now primarily determined by its software.
Since Honeywell has preprogrammed a variety of functional capabilities into the recorder, a user only has to configure those functions that are specific for the given application.
The user configures the recorder by following English language prompts that appear in the digital displays.
The configuration data (type of input, chart speed, chart range, alarm settings, tuning constants, etc.) are stored in non-volatile memory for safe keeping in the event of a power failure.
Operator Interface
Two digital displays present the process variable (PV) value and by key selection, the controller set point; controller output; deviation from reference input; dry bulb temperature; totalization value; or engineering units as desired. The lower display can also be set scroll or hold. In configuration mode, digital displays are pre-empted by English language prompts and values that you use to enter configuration data. Indicators light to show alarm condition, which channel PV is on display, use of remote set point, which output relay is on, selected temperature unit, and controller’s mode of operation.
Operator Interface, cont.
A deviation bargraph lets operators tell at a glance if the process variable is at, above, or below the controller’s setpoint.
The keypad through which config­uration data is entered also serves as an integral automatic/manual station that provides bumpless transfer for controllers.
On two-pen models, the Hold key allows continuous display of one channel process variable while the recording action proceeds automatically.
Microprocessor
Controlled Recording and
Printing
Both the chart and the pen are driven by stepper motors which are controlled by the microprocessor for precise maintenance free operation.
Since chart speed is configurable, users can easily alter the chart speed through the keypad. Gear changing or additional motors are no longer required.
The stepper motor accurately positions the pen drive without damping, thus eliminating the need for slidewire feedback gearing and drive cables.
A configurable deviation recording function lets users show graphically the difference between reference input and a process variable input.
Users can designate the channel 1 input or enter a deviation setpoint value as the reference input. This is an example of the versatility derived from microprocessor controlled recording.
CHART
RUN
HOLD
20951
Input Processing
The input can be one of many standard low-level electrical signals. And, for models with 2 pens, a relative humidity (wet/dry bulb) actuation is available using 100 ohm platinum bulbs (α = 0.00385). The input type and range are user configurable.
Ranges are easily expanded and compressed within their span limitations to meet specific measurement needs. Users can select upscale or downscale sensor break protection for many of the actuations.
Each input is sampled at a rate of 3 times per second. Each sample is amplified and then converted to a digital signal, which is isolated and passed to the microprocessor.
A digital filter with configurable time constants lets users apply input signal smoothing as desired.
All non-linear inputs are linearized by the microprocessor, using look-up tables that reside in the software. This allows mixed input actuations for 2-pen models to be recorded on a linear chart. Users can bypass linearization for recording on a non­linear chart.
An integral 24 Vdc power supply, along with 4-20 mA input configuration, allows direct operation with up to two transmitters without the need for any additional/external transmitter power supply.
To totalize a variable, such as a flow signal, users select the applicable input and set the digital display scaling factor through configuration. This eliminates the need for additional integration hardware including a mechanical counter. The totalizer has an eight-digit display.
Also has capability to reset the totalizer remotely with digital inputs, and a low flow cutoff can be set in percent of range below which the applicable totalizer does not increment.
Digital Controller
The DR4500A Series recorder controller (1 or 2 loops) includes an integral microprocessor-based PID controller.
A variety of output types, including a duplex variation for heat-cool applications, lets users select the output that is right for their final control element.
Depending on the output type users can configure the control action as On-Off, PID-A, PID-B or PD with Manual Reset.
As with the record functions, English language prompts quickly guide users through the entry of all the controller’s configurable parameters.
Diagnostics
All DR4500A Series recorders include self-diagnostic systems that check critical operations and provide error messages to alert users about detected faults.
Power-up self-diagnostics is a microprocessor controlled diagnostic program that runs tests on selected circuitry when the recorder is powered up.
A “key” test allows a user to initiate, on demand, a self-diagnostic routine that checks the keypad and front panel displays.
44-45-03-15
Page 3
Construction
The DR4500A Series recorder is housed in a molded case, which can be panel or surface, mounted.
A gasketed door with a glass or optional acrylic window protects internal components from harsh industrial environments while allowing easy access to the chart and operator interface.
Circuitry is partitioned on printed circuit boards for ease of service.
A UL and FM approved NEMA4X door is also available.
Process Interface
Power, input, and output wiring connect to terminations inside the case.
Knockouts in the sides and bottom of the case accept conduit connections for convenient wire entry.
44-45-03-15 Page 4
Specifications
Design
Digital Indication Accuracy
Minimum Input Span
Input Impedance
Source Impedance
Span Step Response Time
Sampling Rate
Input Filter
Digital Displays
Indicators
Deviation Bargraph
1 digit
Range is fully configurable with span limitation of the operating range selected.
4-20 mAdc: 250 ohms 0-10 Vdc: 200K ohms All others: 10 Megohms
RTD: 100 ohms per lead maximum
6-seconds maximum with no filtering
Each input sampled 3 times a second.
Software: Single pole low pass section with selectable time constants (off to 120 seconds).
Vacuum fluorescent, alphanumeric. A six-digit display dedicated to the process variable. Alternate information displayed during configuration mode. An eight-digit display shows key selected operating parameters. Also provides guidance during configuration.
Channel PV display (CHN 1 or 2) Alarm status (ALM 1, 2) Controller Output (OUT 1, 2) Remote Set Point (RSP) for Control 1 Temperature unit (F or C) or Engineering units Controller’s mode (A or MAN)
21 segment, color coded deviation bargraph: Green (large) = On Control Green (Small) = Deviation to ± 10% of PV
Controller Modes of Operation
Transmitter Supply Voltage
Manual Operation Automatic with local set point Automatic with remote set point
22 to 26 Vdc at input terminals (50 mAdc at 24 Vdc)
Loading...
+ 8 hidden pages