Fig. 1. Components of R4140G and R4140M Programmers.
RESET BUTTON
TIP JACK
PLUG-IN
FLAME SIGNAL
AMPLIFIER
HANDLE
CHASSIS RETAINING
SCREW
TIMER
MOTOR
RELAY 4K
SAFETY SWITCH
BUTTON
CHASSIS
HINGE
BRACKET (2)
M10053
SAFETY SWITCH
BUTTON
OPTIONAL HEAVY DUTY
COVER (PART NO.
202050C OR 139695C)
RELAY/TIMER
COVER
Fig. 2. Components of R4140L Programmers.
IMPORTANT
Applications, Features, Specifications (including
dimension drawings), Operation (including
schematics and bar charts), and Wiring Diagrams
are included in these Specifications for models of
the R4140G, L, and M: R4140G—60-2337;
R4140L—60-2339; R4140M—60-2340.
Service Information ............................................................. 27
Testing and Maintenance .................................................... 28
60-0770-2
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced, flame
safeguard control technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
1.Disconnect power supply before beginning
installation to prevent electrical shock and
equipment damage.
2.All wiring must be NEC Class 1 (line voltage).
3.Loads connected to the control terminals must
not exceed those listed on the R4140 label or in
the Specifications section of the Specifications for
the R4140G,L or M.
4.Limits and interlocks must be rated to carry and
break current to the ignition transformer, pilot
valve, and main fuel valve(s) simultaneously.
5.All external timers must be listed or component
recognized by authorities having jurisdiction for
the specific purpose for which they are used.
Weather
The R4140 is not designed to be weather tight. If it is installed
outdoors, it must be protected.
Mounting the Wiring Subbase
NOTE: For installation dimensions, see Fig. 1 and 2 in the
Specifications for the R4140G,L or M.
The subbase can be mounted in any position except
horizontally with the knife-blade contacts pointing down.
The standard vertical position (shown in Fig. 5) is
recommended. Any other position decreases the
maximum ambient temperature rating.
Select a location on a wall or instrument panel. (The
0520A Subbase can be mounted directly in the
customer’s cabinet.) Be sure to allow clearances for
servicing and for removal of the R4140.
IMPORTANT
Do not mount the wiring subbase horizontally with
the knife-blade contacts pointing down.
For surface mounting, use the back of the subbase as
a template to mark the four screw locations. Drill the
pilot holes.
Insert the mounting screws and tighten them securely.
Wiring to Subbase
IMPORTANT
1. For on-off gas-fired systems, some authorities
having jurisdiction prohibit the wiring of any limit or
operating contacts in series between the flame
safeguard control and the main fuel valve(s).
2. Do not connect more than two C7012E,F or C7076A
Ultraviolet Flame Detectors (with self-checking
shutter) in parallel to the same terminals.
Use applicable installation instructions provided by the burner
manufacturer in addition to the corresponding instructions
given here. Before putting the system into service, check out
the installation using the procedures in the Checkout section
and any other procedures stipulated by the burner
manufacturer.
Location
Temperature
Install the R4140 where the surrounding temperatures
remain within the Ambient Operating Temperature Ratings in
the Specifications section of the Specifications for the
R4140G,L or M.
Humidity
Install the R4140 where the relative humidity never reaches
the saturation point. Condensation of moisture on the R4140
can cause enough leakage to short the flame signal to ground
and thus prevent the burner from starting.
Vibration
Do not install the R4140 where it could be subjected to
excessive vibration. Vibration shortens the life of the
electronic components.
CAUTION
Make sure the wiring to terminal 7 does not touch any
other terminal, especially terminal 8.
All wiring must comply with all applicable electrical
codes, ordinances, and regulations. Use NEC Class 1
(line voltage) wiring.
For normal installations, use moisture-resistant No. 14
wire suitable for at least 194°F (90°C).
For high temperature installations, use moisture
resistant No. 14 wire, selected for a temperature rating
above the maximum operating temperature, for all but
the ignition and flame detector F leadwires.
a.For the ignition, use Honeywell specification
no. R1061012 Ignition Cable or equivalent. This
wire is rated at 350°F (177°C) for continuous
duty, and up to 500°F (260°C) for intermittent
use. It has been tested to 25,000 volts.
b.For the flame detector F leadwire, use Honeywell
specification no. R1298020 or equivalent. This
wire is rated up to 400°F (204°C) for continuous
duty. It is tested for operation up to 600 volts and
breakdown up to 7500 volts.
IMPORTANT
Do not run high voltage ignition transformer wires in
the same conduit with the flame detector wiring.
For ignition installations in a contaminating
environment, use Honeywell specification no. R1239001
High Tension Ignition Cable or equivalent. This wire is
very resistant to severe conditions of oil, heat, and
corona, and is tested to withstand high voltages up to
60-0770—2
2
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
25,000V rms in a salt bath for one minute without
breakdown. It is rated at 200°F (93°C) for continuous
duty, and up to 350°F (177°C) for intermittent use.
Refer to the appropriate wiring diagram in the
Specifications for the R4140G,L or M. Follow the burner
manufacturer’s wiring diagram, if provided.
Make sure the loads do not exceed the terminal ratings.
Refer to the label on the R4140 or to the Terminal
Ratings in the Specifications section of the
Specifications for the R41406,L or M.
Check the power supply circuit. The voltage and
frequency must match those of the R4140. Do not
connect the R4140 to a circuit that is subjected to line
voltage variations, such as would occur with on-off
switching of heavy loads. A separate power supply
circuit can be required for the flame safeguard control.
Add required disconnect means and overload
protection.
Check all wiring circuits and complete the Static
Checkout in Table 2 before installing the R4140.
Installing the Flame Detector
NOTE: Table 1 lists the flame detection systems available
for use with R4140 Programmers. Make sure you
are using the correct combination of amplifier and
flame detector(s).
Proper flame detector installation is the basis of a safe and
reliable flame safeguard installation. Refer to the instructions
packed with the flame detector and the burner manufacturer’s
instructions. Follow the instructions carefully for the best
possible flame detector application.
Keep the flame signal lead wires as short as possible from
the flame detector to the wiring subbase. Capacitance
increases with Ieadwire length, reducing the signal strength.
The maximum permissible leadwire length depends on the
type of flame detector, leadwire, and conduit. The ultimate
limiting factor in flame signal leadwire length is the signal
current. Refer to Table 4 in the Checkout section.
Table 1. Flame Detection Systems.
Plug-In Flame Signal AmplifiersApplicable Flame Detectors
TypeColor
CheckingModel
Rectification GreenNoR7247A2 to 4 secondGasRectifying
UltravioletPurpleNoR7249A2 to 4 secondGas, OilUltraviolet
C7027, C7035, C7044.
(Minipeeper)
BlueDynamic
Self-Check
R7476A
d
Gas, Oil,
Coal
Ultraviolet
(Adjustable
C7076.
Sensitivity)
a
Order flame rod separately; see Instructions for the holder.
b
Circuitry tests the flame signal amplifier at least 150 times a minute during burner operation and shuts down the burner if the
amplifier fails.
c
Use only Honeywell part no. 38316 Photocell.
d
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 60 to 240 times a minute during
burner operation and shuts down the burner if the detection system fails.
3
60-0770—2
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
Special Considerations for a C7012E or F
The R4140 provides two sources of power for a C7012E or F
Purple Peeper Ultraviolet Flame Detector (with self-checking
shutter). The power to the black leadwires of a C7012E can
be 120V, 208V, 220V, or 240 Vac, depending on the model of
the detector. The C7012F is available only in a 120V model.
This voltage must match the power supply of the R4140.
After checking all wiring circuits, perform this checkout before
installing the programmer on the subbase. These tests
ensure that the Q520A Wiring Subbase is wired correctly, and
that the external controllers, limits, interlocks, actuators,
valves, transformers, motors, and other devices are operating
properly.
Equipment Required
The power to the white leadwires must be 120 Vac; this is the
power supply for the operation of the self-checking shutter.
The 120V for the shutter is applied automatically at terminal
17 of the R4140 through switching action within the plug-in
R7247C Flame Signal Amplifier.
General Instructions
Using Redundant Parallel C7012E or F Detectors
For a flame that is difficult to sight, using two parallel C7012E
or F Flame Detectors reduces nuisance shutdowns. If only
one of the parallel detectors loses the flame signal, the other
continues to indicate the presence of the flame and keeps the
burner running. A flame simulating failure in either detector
causes the burner to shut down. Two C7012E detectors can
be wired in parallel to the same terminals on any R4140 (if
the voltage ratings match). Two C7012F Detectors can be
wired in parallel only on 120V models. To avoid exceeding the
rating of the solid state shutter switch in the R7247C Flame
Signal Amplifier, do not connect more than two C7012E or F
Detectors in parallel.
Static Checkout (See Table 2)
WARNING
1.Use extreme care while performing these tests;
line voltage is present on most subbase terminals
when power is on.
2.Open the master switch before installing or
removing a test jumper.
3.Be sure to remove the test jumper(s) after
completing each test before continuing to the
next test.
4.Replace all external devices not operating
properly. Do not bypass external devices.
5.Close all manual fuel shutoff valves before
starting these tests.
1. Voltmeter (W136A or equivalent) set on 0 to 300 Vac
scale.
2. Jumper wires (2) of No. 14 wire, insulated, 12 in.
(304.8 mm) long, with alligator clips at both ends.
Perform all applicable tests in Table 2, in the order
listed.
Make sure all manual fuel shutoff valves are closed.
Perform only those tests designated for the specific
programmer model being tested.
Raise the setpoint of the burner controller to simulate a
call for heat.
For each test, open the master switch and install the
jumper wire(s) between the subbase wiring terminals
listed in the Test Jumpers column.
Close the master switch before observing operation.
Read the voltage between the subbase wiring terminals
listed in the Voltmeter column.
If there is no voltage or if operation is abnormal, check
the circuits and external devices as described in the
last column.
Check all wiring in the circuits for correct connections,
tight terminal screws, correct wire, and proper wiring
techniques. Replace all worn or incorrectly sized wires.
valves, transformers, motors, and other devices, as
required.
쐈 Normal operation must be obtained for each required
test before continuing the checkout.
쐉 Be sure to remove the test jumper(s) after completing
each test before continuing on to the next test.
Table 2. Static Tests of External Devices.
Test
No.
R4140
Models
Test
Jumpers Voltmeter
Normal
Operation
If Operation is Abnormal,
Check the Items Listed Below
WARNING
Make sure all manual fuel shutoff valves are closed.
1All modelsNoneL1-L2Line voltage at terminal L1.1. Master switch is closed.
2. Power is connected to the master switch.
3. OverIoad protection (fuse, circuit breaker
etc.) has not opened the power line.
2Models with
Preignition
Interlocks
Models with
Start
Interlocks
60-0770—2
None4-L2Line voltage at terminal 4.IMPORTANT
Low fuel pressure limits, if used, could be
open. Bypass them with jumpers for the
remaining Static Tests (if required).
None16-L2Line voltage at terminal 16.1. Limits are closed. If open, determine
cause(s) and correct the condition(s).
2. Burner controller contacts are closed (call for
heat).
4
(Continued)
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
Table 2. Static Tests of External Devices
Test
No.
3Models with
4All modelsL1-83-L21. Burner motor (fan or blower)
R4140
Models
Preignition
Interlocks
Models with
Start
Interlocks
Test
Jumpers Voltmeter
None16-L2Line voltage at terminal 16.1. Preignition interlocks are closed. If open,
None4-L2Line voltage at terminal 4.1. Start interlock(s), if used, is closed. If open,
starts.
2. Line voltage at terminal 3
within 12 seconds.
Normal
Operation
(Continued).
If Operation is Abnormal,
Check the Items Listed Below
determine cause(s) and correct the
condition(s).
determine cause(s) and correct the
condition(s).
2. If start interlock(s) is not used, jumper is
installed between terminals 4 and 16.
1. Burner motor circuit:
a. Manual switch of burner motor is closed.
b. Burner motor power supply, overload
protection, and starter are OK.
c. Burner motor is OK.
2. Running or Iockout interlocks (including the
Airflow switch) are closed.
WARNING
Make sure all manual fuel shutoff valves are closed.
5Models with
5 second
ignition
6All modelsL1-5—1. Ignition spark (if ignition
7All modelsL1-6—Same as test no. 6 for
L1-18—Ignition spark (if ignition
transformer is connected to
terminal 18).
transformer is connected to
terminal 5).
2. Automatic pilot valve opens
(if connected to terminal 5).
NOTE: Refer to wiring diagram
of the programmer being
tested.
connections to terminal 6. (If
using direct spark ignition,
check the first stage fuel
valve(s) instead of the pilot
valve.)
1. Watch for spark or listen for buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is OK.
1. Watch for spark or listen for buzz:
a. Ignition electrodes are clean.
b. ignition transformer is OK.
2. Listen for click or feel head of valve for
activation.
a. Actuator (if used) is OK.
b. Pilot valve is OK.
Same as test no. 6. (If using direct spark
ignition, check the first stage fuel valve(s)
instead of the pilot valve.)
WARNING
Make sure all manual shutoff valves are closed.
8All modelsL1-7—Automatic main fuel valve(s)
9All modelsL1-9—Alarm (if used) turns on.1. Alarm is OK.
10All R4140L
modeIs
11All R4140G
modeIs
12All R4140L
models
L1-8 and
10-11
L18 and
14-11
L1-8 and
14-11
13-L2Firing rate motor drives open;
13-L2Firing rate motor drives closed;
15-L2Firing rate motor drives open;
opens. (If using direct spark
ignition on a model with
intermittent pilot/ignition on
terminal 6, check the optional
second stage fuel valve, if
used.)
zero volts at terminal 13 after
motor starts driving open.
line voltage at terminal 13 after
motor closes.
line voltage at terminal 15 after
motor opens.
1. Listen for and observe operation of the main
fuel valve(s) and actuator(s).
2. Valve(s) and actuator(s) are OK.
1. Low Fire switch is open.
2. Firing rate motor and transformer are OK.
1. Low Fire switch is closed.
2. Firing rate motor and transformer are OK.
1. High Fire switch is closed.
2. Firing rate motor and transformer are OK.
(Continued)
5
60-0770—2
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
Test
No.
R4140
Models
13All R4140L
modeIs
14All R4140L
models
15All R4140G
and R4140L
models
16R4140M
models with
open damper
contacts
17R4140M
models with
open damper
contacts
Final All models
Table 2. Static Tests of External Devices
Test
Jumpers Voltmeter
L18 and
13-L2Firing rate motor drives closed;
14-11
line voltage at terminal 13 after
Normal
Operation
motor closes.
L1-15
and
14-11
13-L2Firing rate motor drives closed;
line voltage at terminal 13 after
motor closes.
12-11—1. Raise setpoint of Series 90
Controller—firing rate motor
should drive toward open.
2. Lower setpoint of Series 90
Controller—firing rate motor
should drive toward closed.
L1-10—If damper control is used,
actuator drives damper open.
L1-813-L2If damper control is used,
spring return drives actuator
and damper closed; line
voltage at terminal 13 after
actuator closes.
CAUTION
After completing these tests, open the master switch and remove all test jumpers from the
subbase terminals. Also remove bypass jumpers from the low fuel pressure limits (if used).
(Continued).
If Operation is Abnormal,
Check the Items Listed Below
1. Low Fire switch is connected between
terminals 8 and 13. If not, proceed to test
no. 14.
2. Low Fire switch is closed.
3. Firing rate motor and transformer are OK.
1. Low Fire switch is connected between
terminals 15 and 13. If not, proceed to test
no. 15.
2. Low Fire switch is closed.
3. Firing rate motor and transformer are OK.
1. Series 90 Controller is OK.
2. Firing rate motor and transformer are OK.
1. Jumper wire is installed between
terminals 11 and 12.
2. Damper actuator is OK.
1. Low Fire switch is closed.
2. Damper actuator is OK.
Installing the Programmer (Fig. 3)
Open the master switch.
Make sure no subbase wiring is projecting out beyond
the terminal blocks. Tuck in wiring against the back of
the subbase so it does not interfere with the contacts.
Grasp the handle of the programmer chassis and
engage the chassis hinge brackets with the pivot pins
at the bottom of the subbase.
Swing the chassis inward until the spring connectors
engage the knife-blade contacts. Push in until the
contacts are fully engaged.
Tighten the chassis retaining screw securely.
Removing the Programmer
Open the master switch.
Loosen the chassis retaining screw.
Pull outward on the handle.
Disengage the chassis hinge brackets from the
subbase pivot pins.
WIRING
SUBBASE
KNIFE-BLADE
CONTACTS (20)
PIVOT PIN (2)
SPRING
CONNECTORS
HINGE
BRACKET (2)
CHASSIS
RETAINING
SCREW
PROGRAMMER
CHASSIS
M7965
HANDLE
Fig. 3. Mounting the programmer on the subbase.
60-0770—2
6
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
Removing and Replacing the Relay/Timer
Cover (Fig. 4)
CAUTION
If the programmer is mounted on the subbase, open
the master switch before removing or replacing the
relay/timer cover.
The relay/timer cover must be removed to install a plug-in
flame signal amplifier, to observe relay and timer operation, or
to inspect the contacts.
Removing the Cover
Grasp the relay/timer cover and squeeze until the V-notch
on the cover slides free of the stud on the handle.
Rotate the cover down and out to disengage the two tabs
from the slot in the bottom of the programmer chassis.
Pull out the cover.
Replacing the Cover
Insert the two tabs on the bottom of the cover between
the timer and the programmer chassis and engage
them with the slot in the bottom of the chassis. Make
sure the tabs are not jammed in the slot.
Rotate the cover up and in so the V-notch slides along
the stud on the handle. If the cover does not rotate
easily, the tabs are jammed.
Make sure the spring clip on the cover fits over the
plug-in amplifier.
Push in on the cover until the V-notch snaps into place
on the stud.
V-NOTCH
ON COVER
STUD ON
HANDLE
SPRING CLIP
ON COVER
HANDLE
NOTE: If installing a small amplifier, align its ends with
the two scribe marks alongside the receptacle
on the programmer.
Push in the amplifier until the circuit board is fully
inserted into the receptacle.
Make sure the amplifier is firmly in place, then replace
the relay/timer cover. Make sure the spring clip on the
cover fits over the amplifier.
NOTE: For further information about a self-checking
amplifier, refer to the Instructions packed
with the amplifier (form 60-2358 for an
R7247B or C, form 60-2357 for an R7248B, or
form 95-8270 for an R7476A).
ALIGNMENT
SCRIBE MARKS
FOR SMALL
AMPLIFIER
KEYED
RECEPTACLE
HONEYWELL
MONOGRAM
HONEYWELL
MONOGRAM
PROGRAMMER
CHASSIS
CIRCUIT
BOARD
AMPLIFIER
AMPLIFIER
TIMER
TIMER DIAL
PLUG IN
AMPLIFIER
TIMER
DIAL
TIMER
RELAY/
TIMER COVER
SLOT IN
CHASSIS
TABS (2)
ON COVER
BOTTOM OF
PROGRAMMER
CHASSIS
M7967
Fig. 4. Removing and replacing the relay/timer cover.
Installing a Plug-in Flame Signal Amplifier
(Fig. 5)
Remove the relay/timer cover.
Make sure the Honeywell monogram is on the outside,
then align the circuit board with the keyed receptacle on
the programmer.
KEYED
RECEPTACLE
CIRCUIT
BOARD
PROGRAMMER
CHASSIS
M7961
Fig. 5. Installing a plug-in flame signal amplifier.
Installation Instructions for Special Features
Some TRADELINE® models and international models (rated
for other than 120V, 60 Hz) can have one (or both) of the
following special features.
7
60-0770—2
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
Installing Jumper on Back of Programmer (Fig. 6)
Some R4140G, L, and M models have provisions for
extending the main burner flame-establishing period
(MBFEP) at terminal 6 by installing a jumper on the back of
the programmer. If you are installing one of these models,
A system can be upgraded from on-off to modulating by
replacing an R4140M with an R4140G (Fig. 7). A system can
be upgraded to meet Factory Mutual and Industrial Risk
Insurers (formerly FlA) requirements by replacing an R4140M
or an R4140G with an R4140L (Fig. 8).
determine the required MBFEP. If you need the longer period
provided at terminal 6, install the jumper (included in a bag
assembly with the R4140) between the terminals labeled
JUMPER TO EXTEND MAIN IGN. TRIAL on the back of the
programmer. If you do not need the longer period, leave the
jumper off.
NOTE: Some R4140 models for use in Australia have
jumper terminals on the back of the programmer for
safety shutdown alarm options; these jumpers
cannot be used to extend the MBFEP. These R4140
models are shipped with a jumper link between the
N.O. screw terminals on the back of the
programmer. This results in alarm operation on
Requirements
UL On-OffStart and
UL On-Off (with
2-stage firing)
UL modulating
(with low highlow prepurge)
safety shutdown. N.C. screw terminals are provided
for an external auxiliary safety shutdown circuit.
Refer to the R4140 Specifications for these models.
FM/IRl
modulating (with
low-high-low
JUMPER TO
EXTEND MAIN
5
L1
6
7
8
18
L2
17
16
12
IGN. TRIAL
JUMPER
2
3
4
9
10
prepurge and
proven high fire
purge)
FM Factory Mutual requirements.
IRl Industrial Risk Insurers (formerly FlA) requirements.
UL Underwriters Laboratories Inc. requirements.
Table 3. R4140 Applications.
Application
Interlock
Circuits
Firing Rate
Switching
None R4140M
running
Start,
running, and
low fire
Start or
1-wirea (open
damper
contacts)
4-wireR4140G
pre-ignition,
running, and
low fire
Preignition,
4-wire R4140L
lockout, high
fire, and low
fire
a
Firing rate motor must close by itself (spring-return)
when power is removed.
Applicable
R4140
Several
R4140Ms
G
1
AN R4140L IS SHOWN; R4140G AND R4140M PROGRAMMERS HAVE
FEWER SPRING CONNECTORS. TERMINAL NUMBERS ARE NOT ON
THE PROGRAMMER, BUT ARE SHOWN FOR REFERENCE.
2
INSTALL JUMPER (INCLUDED IN BAG ASSEMBLY) TO OBTAIN THE
LONGER MAIN BURNER FLAME-ESTABLISHING PERIOD AVAILABLE
AT TERMINAL 6.
15
13
14
F
1
11
C8346
Fig. 6. Installing jumper to extend main burner flame-
establishing period.
Upgrading Systems
Conveniently, the R4140 family was developed in models of
varying complexity to allow the user to choose the simplest
programmer that meets their application requirements (Table 3).
IMPORTANT
Before replacing an R4140, make sure the
replacement model has the required:
— prepurge time.
— pilot/ignition timing on terminal 6.
— 5-second ignition on terminal 18 (if required).
— interlock circuits.
— safety features.
— electrical ratings.
— temperature ratings.
— approvals.
60-0770—2
8
R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
REPLACING AN R4140M WITH AN R4140G
TO
L2
WIRING SUBBASE
TERMINAL STRIP (4)
3
2
4
9
10
HIGH FIRE
COMMON
11
FOR DIRECT SPARK IGNITION (OIL OR GAS)
ON MODELS WITH INTERRUPTED
PILOT/IGNITION ON TERMINAL 6
START OR
PREIGNITION
INTERLOCKS
BURNER
CONTROLLER
120V ALARM
DAMPER
CONTROL
IGNITION
TRANSFORMER
MAIN FUEL
VALVE(S)
1
LIMITS
4
4
L1
L2
12
13
5
JUMPER
6
7
RUNNING
INTERLOCKS
(INCL. AIRFLOW
SWITCH)
2
FOR DIRECT SPARK IGNITION (OIL OR GAS)
ON MODELS WITH INTERMITTENT
PILOT/IGNITION ON TERMINAL 6
IGNITION
TRANSFORMER
TO
L2
18
17
16
2
15
1ST STAGE
FUEL VALVE
2ND STAGE
FUEL VALVE
(OPTIONAL)
5 SECOND IGNITION
(EARLY SPARK
TERMINATION)
10 SECOND
INTERRUPTED
PILOT/IGNITION
PILOT/IGNITION
MAIN FUEL
VALVES(S)
BURNER MOTOR
(BLOWER)
LOW FIRE
SWITCH
7
9
6
5
6
7
5
8
6
7
8
G
5
B
R
W
SERIES 90
CONTROLLER
1
120V, 60 HZ
POWER
SUPPLY
1
LEAVE INTERLOCKS CONNECTED BETWEEN TERMINALS 4 AND 16. (IF
INTERLOCKS ARE NOT USED, INSTALL A JUMPER WIRE BETWEEN
TERMINALS 4 AND 16.)
2
IF THE R4140G REPLACEMENT MODEL HAS "START" INTERLOCKS,
CONNECT THE BURNER CONTROLLER TO TERMINAL 16.
3
IF THE R4140G REPLACEMENT MODEL HAS "PREIGNITION" INTERLOCKS,
CONNECT THE BURNER CONTROLLER TO TERMINAL 4.
4
IF REPLACING AN R4140M WITH OPEN DAMPER CONTACTS, REMOVE
DAMPER CONTROL FROM TERMINALS 10 AND L2, AND REMOVE JUMPER
WIRE FROM TERMINALS 11 AND 12.
B
R
W
L1 (HOT)
L2
MODULATE
LOW FIRE
SERIES 90
FIRING RATE
MOTOR
MASTER
SWITCH
F
Fig. 7. Sample block diagram of field wiring for replacing an R4140M with an R4140G.
14
BLUE
BLUE
WHITE
WHITE
L2
L1
L2
5
ADD SERIES 90 CONTROLLER AND SERIES 90 FIRING RATE MOTOR.
5 SECOND IGNITION IS NOT AVAILABLE ON SOME MODELS.
6
REFER TO SPECIFICATIONS OF THE SPECIFIC R4140G MODEL TO
7
DETERMINE THE PILOT/IGNITION TIMING AVAILABLE ON TERMINAL 6.
FOR DIRECT SPARK IGNITION (OIL OR GAS), CONNECT THE
8
IGNITION TRANSFORMER AND FUEL VALVE(S) AS SHOWN IN THE
APPROPRIATE INSET.