Honeywell SP3000, PT3000 Data Sheet

31-00132-02
SP3000, PT3000 Sensors
5/8 (16)
1-1/4 INCH (32) HEAT SHRINK
M37070
2 (51)
Ø1/4 (6)
60 (1524) ±1 (25)
ELECTRICAL RATING: 30 Vac maximum.
TEMPERATURE SENSOR RESISTANCE:
(see Fig. 3)
Temperature °C -10 0 10 20 30 40
Temperature °F 14 32 50 68 86 104

APPLICATION

The SP3000 Temperature Sensors are for use with electronic controllers where linear PTC sensors are required (T7075, Series 1000, W7100, W7600, W7620, R7380J,L) in immersion or strap-mounted discharge applications.

FEATURES

• Requires no settings or calibration.
• Platinum positive temperature coefficient (PTC) sensing element.
• Resistance range is 2900 to 4400 ohms.
• Suitable for mounting in immersion well.
• Can be strapmounted to discharge pipe of boiler or chiller.
Resistance in ohms—SP3000
SENSING ACCURACY: +/-2° F [1.1° C].
AMBIENT TEMPERATURE RANGES:
Operating and Shipping:
For SP3000-2 and SP3000-15: -40 to +302° F
(-40 to +150° C)
For SP3000-WR: -40 to +248° F (-40 to +120° C)
DIMENSIONS: See Fig. 1 and 2.
Ø1/4 (6)
2 (51)
Fig. 1. Approximate dimensions of SP3000-2 and
SP3000-15 Encapsulated Temperature Sensor in in.
3,178 3,266 3,353 3,440 3,527 3,613
ITEM NUMBER
TABLE A
SP3000-2
SP3000-15
SEE TABLE A
(mm).
PRODUCT DATA
LEAD LENGTH
INCHES (MM)
24 (610)
180 (4572)
M37069

SPECIFICATIONS

IMPORTANT:
The specifications given in this publication do not include normal manufacturing tolerances. There­fore, an individual unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed.
Fig. 2. Approximate dimensions of SP3000-WR
Encapsulated Temperature Sensor in in. (mm).
SP3000, PT3000 SENSORS
CAUTION
RESISTANCE (OHMS)
4200
4000
3800
3600
3400
3200
20 40
60
80 100 120
140 160
180 200 220
-7
0
10
20 30
40 50
60
70 80 90
100
F
C
3484 ± 6.5 OHMS AT 77¡F (25¡C)
M2829A
TEMPERATURE (DEGREES)

INSTALLATION

When Installing This Product…

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage.

Location and Mounting

The SP3000 Encapsulated Temperature Sensor can be installed by strapping the sensor to the outside of a boiler or chiller output pipe, or by placing the sensor in the fluid of a boiler or chiller using an immersion well. Instructions for both types of installations follow.
Strapping The SP3000 To A Boiler Or Chiller Output Pipe
Some applications require that the sensor be strapped to the outside of a pipe. Strap-on mounting avoids the need for an immersion well and pipe fittings, and also eliminates the system draining, refilling, and bleeding necessary to install the immersion well.
2. Clean the pipe surface for good sensor-to-pipe con-
tact. Apply heat conductive compound to the pipe at the selected location.
3. Press the sensor bulb into the heat conductive com-
pound and fasten to the discharge pipe with 105900 Pipe Clamp, duct hanger wire or with metal hose clamps.
IMPORTANT:
Erratic temperature readings from a sensor can be caused by the wiring practices described below. These must be avoided to assure proper operation. Use shielded cable to reduce interference if rerouting of sensor wiring is not possible.
1. Do not route temperature sensor wiring with build­ing power wiring, next to control contactors or near light dimming circuits, electric motors or welding equipment.
2. Avoid poor wiring connections.
3. Avoid intermittent or missing building earth ground. Do not mount sensor in incorrect environ­ment.
Resistance in the SP3000 Sensor wiring positively offsets the temperature sensed by 1 degree F for every 4.8 ohms [8.6 ohms/°C] of resistance. Use larger gauge wire when longer lengths are necessary.

OPERATION AND CHECKOUT

External mounting of the sensor produces a slight offset in the temperature control point. The control temperature could be increased up to 5° F [2.8° C] with a bare sensor strapped to the discharge pipe. Use a heat conductive compound and apply insulation around the SP3000 and pipe to decrease the temperature offset. Obtain any necessary straps, clamps and insulation locally.
The sensor bulb should be located at a point on the discharge pipe approximately 3 ft [1 m] from the boiler or chiller.
1. Remove any insulation on the pipe, leaving about 6
Home and Building Technologies
In the U.S.:
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
in. [15 cm] of the pipe exposed. With care, most insu­lating materials may be able to be reused to cover the sensor when the installation is complete.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
® U.S. Registered Trademark © 2020 Honeywell International Inc. 31-00132—02 M.S. Rev. 04-20 Printed in United States
Fig. 3. SP3000 temperature/resistance curve.
Loading...