Honeywell PP901, PP902 Catalog Page

Pneumatic Pressure Controllers
PP901; PP902 Pressure Reducing Valves
Used to control the pressure of the air delivered to pneumatic control systems. Models available for single-pressure systems or two-pressure systems (Day/Night or Summer/Winter) requiring two independently regulated pressure settings. Dual-pressure units switch from the lower settings to the higher settings when main air is applied to the pilot port. Models also available including a sub­micron filter assembly and pressure gauges. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman and older Honeywell pressure reducing valves.
• Built-in adjustable safety relief valve for limiting downstream pressure.
• For two-pressure models: Pressure changes accomplished with manual switch or automatically with electric pneumatic switch.
• Adjustable stops for desired settings.
Application Type: Pressure Reducing Connection Size: Inlet and out air: 1/4 in. NPT (female) Air gage: 1/8
in. NPT (female)
Mounting: Bracket furnished
Accessories:
305917-2 in. diameter, 1/4 NPT center stem back mount Pressure
Indicating gauge (0 to 160 psi scale) with ±3% accuracy
804191E-2-1/2 in. diameter, panel-mounted Pneumatic Pressure
Indicating Gauge (0 to 160 psi), 1/8 in. NPT connection, +/-3% accuracy
305965-1-1/2 in. diameter, 1/8 NPT center stem back mount Pressure
Indicating gauge (0 to 30 psi scale) with ±4% accuracy
Inlet Pressure Range Output Pressure Range
Product Number
PP901A1004/U 45 to 150
PP901B1002/U 45 to 150
PP902C1009/U 45 to 150
PP902D1007/U 45 to 150
psi
psi
psi
psi
310 to 1034 kPa
310 to 1034 kPa
310 to 1034 kPa
310 to 1034 kPa
primary pressure: adj.0 to 25 psi.
primary pressure: adj.0 to 25 psi; secondary pressure: adj. 0 to 5 psi above primary rating
primary pressure: adj.0 to 25 psi
primary pressure: adj.0 to 25 psi; secondary pressure: adj. 0 to 5 psi above primary rating
primary pressure: adj.0 to 172 kPa.
primary pressure: adj.0 to 172 kPa; secondary pressure: adj. 0 to 34kPa above primary setting.
primary pressure: adj.0 to 172 kPa.
primary pressure: adj.0 to 172 kPa; secondary pressure: adj. 0 to 34kPa above primary setting.
Replacement Parts:
316203A-Pressure Regulator Valve Assembly for PP901A; PP902A, C 316134B-PP901A & B Diaphragm Repair Kit 14004203-001-Filter cartridge kit for PP902C and PP902D. 14004205-002-Filter Station Assembly for PP901, PP902A or B 14003121-002-Filter for PP902A or B
Description Includes(psi) (kPa) (psi) (kPa)
High Pressure Diaphragm Operated Reducing Valve with Built-in Adjustable Relief Valve for Single Pressure Systems. Includes Mounting Bracket and Gage Taps But No Gages.
High Pressure Diaphragm Operated Reducing Valve with Built-in Adjustable Relief Valve for Dual Pressure Systems. Includes Mounting Bracket and Gage Taps But No Gages.
Pressure Reducing Valve for Single Pressure Systems, consists of a PP901A Valve, a sub­micron filter station, 2 psig gages, Interconnecting Pipe Fittings, and a Mounting Bracket
Pressure Reducing Valve for Dual Pressure Systems, consists of a PP901B Valve, a sub­micron filter station, 2 psig gages, Interconnecting Pipe Fittings, and a Mounting Bracket
Gage tapping to measure the regulated pressure.
Gage tapping to measure the regulated pressure.
Submicron filter assembly and two psig gages.
Submicron filter assembly and two psig gages.
Pneumatic