The delivery package includes the actuator itself, parts 1
through 8 (see Fig. 2), the anti-rotation bracket screws, and
the SM mounting plate and screws.
Rotary Movement
The rotation direction (clockwise or counterclockwise) can be
selected using the rotation direction switch (see part 7 in Fig.
2), thus eliminating the need to re-wire. To ensure tight
closing of the dampers, the actuator has a total rotation stroke
8
of 95°.
As soon as operating power is applied, the actuator may start
to run. When power is removed, the actuator remains in
position. For actuator-controller wiring instructions, see
section "Wiring" on page 7.
EN0B-0320GE51 R0409 2
Rotation Direction Switch
SmartAct N2024 / N20230, N3424 / N34230
90 90
60
60
Dir
Service/Off
Rev
Fig. 3. Rotation Direction Switch
•Dir ("
") is the default shipping position. When the
rotation direction switch is set to this position, the actuator
internally switches the rotation direction control signals as
stated in section "Wiring Diagrams" on pages 5 and 6.
• "Service/Off": When the rotation direction switch is set to
this position, all actuator rotary movement is cancelled
and all control signals are ignored, thus enabling the
actuator to be manually operated (see section "Manual
Adjustment"). The user can then perform maintenance /
commissioning without having to remove power from the
actuator. To return to the control mode, simply move the
rotation direction switch to its former setting.
•Rev ("
"): When the rotation direction switch is set to this
position, the actuator follows signals as stated in section
"Wiring Diagrams" on pages 5 and 6.
Two-Position or Floating Control
The actuator is capable of being operated by either a twoposition (open/close) or (unless explicitly identified as a 2POS model) a floating (three-wire) controller. Refer to wiring
diagrams for correct connection.
Feedback Signal
Actuators equipped with a feedback potentiometer provide
position feedback via the potentiometer resistance value (see
Fig. 4).
30
30
00
Fig. 5. Position indication
Manual Adjustment
IMPORTANT
To prevent equipment damage, you must remove
power or set the rotation direction switch to the
"Service/Off" position before manual adjustment.
After removing power or setting the rotation direction switch to
the "Service/Off" position, the gear train can be disengaged
using the declutch button, permitting the actuator shaft to be
manually rotated to any position. The feedback signal will
then follow the new position.
Limitation of Rotation Stroke
Two adjustable mechanical end limits (20 Nm [177 lb-in]
models, only) are provided to limit the angle of rotation as
desired (see Fig. 6).
ENSURE
PROPER
MESHING
OF TEETH
P3
totally CCW
totally CW
= max.
totally CCW
= 0
Ω
Ω
= 0
Ω
P2
totally CW
= max.
P1
10 k
Ω
Ω
Fig. 4. Feedback signal settings
If, while the actuator is not rotating, the user declutches it and
manually repositions the shaft adapter, the feedback signal
will then follow the new position at which the shaft adapter
has been left.
Position Indication
The hub adapter indicates the rotation angle position by
means of the rotational angle scales (0...90° / 90...0°)
provided in the actuator plate (see Fig. 5).
3 EN0B-0320GE51 R0409
The mechanical end limits must be securely fastened in place
as shown in Fig. 7. Specifically, it is important that they
properly mesh with the rotational angle scales when the
screws are tightened.
Fig. 6. Mechanical end limits
SmartAct N2024 / N20230, N3424 / N34230
85°80
5°90°0°92.5°5°10°15
CORRECTINCORRECT
CORRECTINCORRECT
Fig. 7. Correct / incorrect tightening of end limits
Internal End Switches
NOTE: Only those actuators for which "-SW2" has been
specified when ordering (e.g.: "N2024-SW2") feature
internal end switches.
The internal end switches are set to switch from "common" to
"normally open" at angles of 5° and 85°, respectively, from the
totally counterclockwise position.
actuator scale: clockwise
5°10°15°92.5°0°90°-2.5°85°80°75°
CCW internal
end switch
end switch scale
5°10°15°0°90°85°80°75°
actuator scale: counterclockwise
°75°-2.
Fig. 8. Internal end switch triggering points
°
CW internal
end switch
INSTALLATION
These actuators are designed for single-point mounting.
IMPORTANT
In order to prevent equipment damage, you must
remove power or set the rotation direction switch to the
"Service/Off" position before manual operation.
Mounting Instructions
All information and steps are included in the Installation
Instructions supplied with the actuator.
Mounting Position
The actuators can be mounted in any position (no IP54 if
mounted upside down; see Fig. 9). Choose a mounting position permitting easy access to the actuator's cables and
controls.
IP54IP54IP54IP54
Fig. 9. Mounting for IP54
Mounting Bracket and Screws
If the actuator is to be mounted directly on a damper shaft,
use the mounting bracket and screws included in the delivery
package.
Self-Centering Shaft Adapter
The self-centering shaft adapter can be used for shafts
having various diameters (10...27 mm [3/8...1-1/16"]) and
shapes (square or round).
In the case of short shafts, the shaft adapter may be reversed
and mounted on the duct side.
Stroke Limitation with Mechanical End Limits
The mechanical end limits (20 Nm [177 lb-in] models, only)
enable the stroke to be limited from 0...90° in increments of
3°.
EN0B-0320GE51 R0409 4
SmartAct N2024 / N20230, N3424 / N34230
Wiring Diagrams
N2024 / N2024-2POS / N3424
rotation
direction
3
3
TERMINAL STRIP 1
switch
2
24 Vac~
24 V
!
2
1
1
Connect via safety
isolating transformer!
TWO-POSITION CONTROL
Dir
Service/Off
Rev
M
~
24 Vac~
24 V
!
isolating transformer!
FLOATING CONTROL
(not applicable to N2024-2POS)
N2024-SW2
rotation
direction
3
3
TERMINAL STRIP 1
END SWITCHES
switch
2
24 Vac~
24 V
!
2
1
1
Connect via safety
isolating transformer!
TWO-POSITION CONTROL
Dir
Service/Off
Rev
M
~
24 Vac~
24 V
!
isolating transformer!
FLOATING CONTROL
NOTE: Internal end switches S1 and S4 must be connected to the same power source.
S2 normally closed
S3 normally open
S4 common
S5 normally closed
S6 normally open
P1 full clockwise
feedback potentiometer
P2 signal
P3 full counterclockwise
Dir
Service/Off
Rev
Dir
Service/Off
Rev
name
S1
S1
S2
M
~
END SWITCHES
M
~
totally CCW
totally CCW
S2
S3
S3
S4
S4
S5
S5
S6
S6
P3
totally CW
= max.
= 0
Ω
P2
totally CW
Ω
= 0
= max.
P1
FEEDBACK
POTENTIOMETER
Ω
Ω
10 k
Ω
EN0B-0320GE51 R0409 6
Wiring
Connecting to the Power Supply
In order to comply with protection class II, the power source of
24 V actuators must be reliably separated from the network
power supply circuits as per DIN VDE 0106, part 101.
Access Cover
To facilitate wiring the actuator to the controller, the access
cover can be detached from the actuator.
IMPORTANT
Remove power before detaching the access cover.
Once the access cover has been removed, please
take care to avoid damaging any of the parts now
accessible.
SmartAct N2024 / N20230, N3424 / N34230
S3
A
B
A
B
S6
S1
S2
0
90
C
S4
D
45
S5
90
0
C
D
The internal auxiliary switches are field-installable parts
providing two SPDT freely-adjustable switches.
Access Cover Kit
Order no.: WB20
For M20 outlets.
Contains:
• 1 access cover (with screw)
• 2 cable connectors
• 2 dust-protection caps
SPARE PARTS
Fig. 10. Access cover (N2024-SW2)
Depending upon the model, the access cover may have one
or two terminal strips, including a layout with a description for
each of the terminals.
Fig. 11. N2024-SW2 with access cover removed
OPTIONAL ACCESSORIES
The following optional accessories can be ordered separately.
Auxiliary Switch Kit
Order no.: SW2
Spare Parts Kit
Order no.: A7209.2071
The spare parts kit contains the following items:
• Anti-rotation bracket and screws
• SM Mounting plate and screws
• Access cover screw
• Plastic protective cap for protection standard IP54
• Mechanical end limit screw and retainer
Anti-Rotation Bracket Kit
Order no.: A7209.2073
The anti-rotation bracket kit can be ordered separately.
Contains:
• 10 anti-rotation brackets
• 20 screws
SM Mounting Plate Kit
Order no.: A7209.2072
The SM mounting plate kit can be ordered separately.
Contains:
• 10 SM mounting plates
• 20 screws
7 EN0B-0320GE51 R0409
SmartAct N2024 / N20230, N3424 / N34230
DIMENSIONS
100 mm (3-15/16”)
shaft
adapter
min. 60 mm (2-3/8”)
adapter (reverse)
20.6 mm
(1-3/16”)
shaft
223 mm (8-25/32”)
48 mm
(1-7/8”)
95°
90
60
30
0
92 mm (3-5/8”)
1000 mm (39”)
132 mm (5-3/16”)
230 mm [+/- 0.5 mm] (9-1/16” [+/-1/64”])
20 mm (25/32”)
2 mm (5/64”)
13 mm (1/2”)
7 mm (9/32”)
5 mm (+0.05, -0.10 mm)
25/128” (+0.002, -0.004”)
anti-rotation bracket
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich / Germany
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0320GE51 R0409
Loading...