Honeywell N20230, N34230, N3424, N2024 PRODUCT DATA

DAMPER ACTUATORS 20/34 Nm (177/300 lb-in)
FOR FLOATING / 2-POSITION CONTROL
These direct-coupled damper actuators provide two-position and floating control for:
air dampers,
VAV units,
air handlers,
ventilation flaps,
louvers, and
reliable control for air damper applications with up to
FEATURES
New self-centering shaft adapter
Access cover to facilitate connectivity
Declutch for manual adjustment
Mechanical end limits
Field-installable auxiliary switches
Rotation direction selectable by switch
Mountable in any orientation (no IP54 if upside down)
Mechanical position indicator
2
4.6 m
/ 50 sq.ft. (20 Nm / 177 lb-in) or 7.8 m2 / 85 sq. ft. (34 Nm / 300 lb-in) (seal-less dampers; air friction­dependent).
N2024 / N20230 N3424 / N34230
PRODUCT DATA
SPECIFICATIONS
Supply voltage
N2024 / N3424 24 Vac ±15%, 50/60 Hz N20230/N34230 230 Vac ±15%, 50/60 Hz
Nominal voltage
N2024 / N3424 24 Vac, 50/60 Hz N20230/N34230 230 Vac, 50/60 Hz
All values stated hereinafter apply to operation under nominal voltage conditions.
Power consumption
N2024 6 VA / 6 W N20230 8 VA / 8 W N3424 9 VA / 9 W N34230 13 VA / 10 W
Ambient limits
Ambient operating limits -20...+60 °C (-5...+140 °F) Ambient storage limits -40...+80 °C (-40...+175 °F) Relative humidity 5...95%, non-condensing
Safety
Protection standard IP54 as per EN 60529 Protection class II as per EN 60730-1 Overvoltage category III
Lifetime
Full strokes 60000 Repositions 1.5 million
Mounting
Round damper shaft 10...27 mm (3/8...1-1/16") Square damper shaft 10...18 mm (3/8...11/16"); 45° steps Shaft length min. 22 mm (7/8")
End switches (when included)
Rating 5 A (resistive) / 3 A (inductive) Triggering points 5° / 85° Torque rating N2024 / N20230 20 Nm (177 lb-in) N3424 / N34230 34 Nm (300 lb-in)
Runtime 110 sec (50 Hz) / 95 sec (60 Hz) Rotation stroke 95° ± 3° Dimensions see "Dimensions" on page 8 Weight (without cables) 1.45 kg (3 lbs. 3 oz.) Noise rating 40 dB(A) max. at 1 m
® U.S. Registered Trademark EN0B-0320GE51 R0409 Copyright © 2009 Honeywell Inc. • All rights reserved
SmartAct N2024 / N20230, N3424 / N34230
MODELS
order number supply voltage end switches feedback power consumption torque
N2024 / N2024-2POS 24 Vac -- --
N2024-SW2 24 Vac 2 --
N2024-P10K 24 Vac -- 10 k
N20230 / N20230-2POS 230 Vac -- --
N20230-SW2 230 Vac 2 --
N20230-P10K 230 Vac -- 10 k
N3424 24 Vac -- -- 9 VA / 9 W
N34230 230 Vac -- -- 13 VA / 10 W
Product Identification System
N = non-spring return S = spring return
20 = 20 Nm (177 lb-in) 34 = 34 Nm (300 lb-in)
010 = modulating
24 = 24 V floating+ON/OFF
230 = 230 V floating+ON/OFF
6 VA / 6 W
20 Nm
(177 lb-in)
8 VA / 8 W
34 Nm
(300 lb-in)
SmartAct
OPERATION / FUNCTIONS
1
60
90
90
60
30
0
2
3
4
5
6
7
Fig. 2. Setting units and control elements
30
0
N
0
2
Fig. 1. Product Identification System
X
320
Legend for Fig. 2:
1 Self-centering shaft adapter 2 Retainer clip 3 Rotational angle scales (0...90° / 90...0°) 4 Mechanical end limits (20 Nm [177 lb-in] models, only) 5 Declutch button 6 Anti-rotation bracket 7 Rotation direction switch 8 Access cover
Contents of Package
The delivery package includes the actuator itself, parts 1 through 8 (see Fig. 2), the anti-rotation bracket screws, and the SM mounting plate and screws.
Rotary Movement
The rotation direction (clockwise or counterclockwise) can be selected using the rotation direction switch (see part 7 in Fig.
2), thus eliminating the need to re-wire. To ensure tight closing of the dampers, the actuator has a total rotation stroke
8
of 95°.
As soon as operating power is applied, the actuator may start to run. When power is removed, the actuator remains in position. For actuator-controller wiring instructions, see section "Wiring" on page 7.
EN0B-0320GE51 R0409 2
Rotation Direction Switch
SmartAct N2024 / N20230, N3424 / N34230
90 90
60
60
Dir
Service/Off
Rev
Fig. 3. Rotation Direction Switch
Dir ("
") is the default shipping position. When the rotation direction switch is set to this position, the actuator internally switches the rotation direction control signals as stated in section "Wiring Diagrams" on pages 5 and 6.
"Service/Off": When the rotation direction switch is set to this position, all actuator rotary movement is cancelled and all control signals are ignored, thus enabling the actuator to be manually operated (see section "Manual Adjustment"). The user can then perform maintenance / commissioning without having to remove power from the actuator. To return to the control mode, simply move the rotation direction switch to its former setting.
Rev ("
"): When the rotation direction switch is set to this position, the actuator follows signals as stated in section "Wiring Diagrams" on pages 5 and 6.
Two-Position or Floating Control
The actuator is capable of being operated by either a two­position (open/close) or (unless explicitly identified as a 2­POS model) a floating (three-wire) controller. Refer to wiring diagrams for correct connection.
Feedback Signal
Actuators equipped with a feedback potentiometer provide position feedback via the potentiometer resistance value (see Fig. 4).
30
30
00
Fig. 5. Position indication
Manual Adjustment
IMPORTANT
To prevent equipment damage, you must remove power or set the rotation direction switch to the "Service/Off" position before manual adjustment.
After removing power or setting the rotation direction switch to the "Service/Off" position, the gear train can be disengaged using the declutch button, permitting the actuator shaft to be manually rotated to any position. The feedback signal will then follow the new position.
Limitation of Rotation Stroke
Two adjustable mechanical end limits (20 Nm [177 lb-in] models, only) are provided to limit the angle of rotation as desired (see Fig. 6).
ENSURE PROPER MESHING OF TEETH
P3
totally CCW
totally CW
= max.
totally CCW
= 0
= 0
P2
totally CW
= max.
P1
10 k
Fig. 4. Feedback signal settings
If, while the actuator is not rotating, the user declutches it and manually repositions the shaft adapter, the feedback signal will then follow the new position at which the shaft adapter has been left.
Position Indication
The hub adapter indicates the rotation angle position by means of the rotational angle scales (0...90° / 90...0°) provided in the actuator plate (see Fig. 5).
3 EN0B-0320GE51 R0409
The mechanical end limits must be securely fastened in place as shown in Fig. 7. Specifically, it is important that they properly mesh with the rotational angle scales when the screws are tightened.
Fig. 6. Mechanical end limits
SmartAct N2024 / N20230, N3424 / N34230
85°80
5°90°0°92.5°5°10°15
CORRECT INCORRECT
CORRECT INCORRECT
Fig. 7. Correct / incorrect tightening of end limits
Internal End Switches
NOTE: Only those actuators for which "-SW2" has been
specified when ordering (e.g.: "N2024-SW2") feature internal end switches.
The internal end switches are set to switch from "common" to "normally open" at angles of 5° and 85°, respectively, from the totally counterclockwise position.
actuator scale: clockwise
10° 15° 92.5° 90°-2.5° 85°80°75°
CCW internal
end switch
end switch scale
10° 15° 90°85°80°75°
actuator scale: counterclockwise
°75°-2.
Fig. 8. Internal end switch triggering points
°
CW internal
end switch
INSTALLATION
These actuators are designed for single-point mounting.
IMPORTANT
In order to prevent equipment damage, you must remove power or set the rotation direction switch to the "Service/Off" position before manual operation.
Mounting Instructions
All information and steps are included in the Installation Instructions supplied with the actuator.
Mounting Position
The actuators can be mounted in any position (no IP54 if mounted upside down; see Fig. 9). Choose a mounting posi­tion permitting easy access to the actuator's cables and controls.
IP54 IP54IP54 IP54
Fig. 9. Mounting for IP54
Mounting Bracket and Screws
If the actuator is to be mounted directly on a damper shaft, use the mounting bracket and screws included in the delivery package.
Self-Centering Shaft Adapter
The self-centering shaft adapter can be used for shafts having various diameters (10...27 mm [3/8...1-1/16"]) and shapes (square or round).
In the case of short shafts, the shaft adapter may be reversed and mounted on the duct side.
Stroke Limitation with Mechanical End Limits
The mechanical end limits (20 Nm [177 lb-in] models, only) enable the stroke to be limited from 0...90° in increments of 3°.
EN0B-0320GE51 R0409 4
SmartAct N2024 / N20230, N3424 / N34230
Wiring Diagrams
N2024 / N2024-2POS / N3424
rotation
direction
3
3
TERMINAL STRIP 1
switch
2
24 Vac~
24 V
!
2
1
1
Connect via safety
isolating transformer!
TWO-POSITION CONTROL
Dir
Service/Off
Rev
M
~
24 Vac~
24 V
!
isolating transformer!
FLOATING CONTROL
(not applicable to N2024-2POS)
N2024-SW2
rotation
direction
3
3
TERMINAL STRIP 1
END SWITCHES
switch
2
24 Vac~
24 V
!
2
1
1
Connect via safety
isolating transformer!
TWO-POSITION CONTROL
Dir
Service/Off
Rev
M
~
24 Vac~
24 V
!
isolating transformer!
FLOATING CONTROL
NOTE: Internal end switches S1 and S4 must be connected to the same power source.
N2024-P10K
rotation
direction
3
3
TERMINAL STRIP 1
FEEDBACK POTENTIOMETER
switch
2
24 Vac~
24 V
!
2
1
1
Connect via safety
isolating transformer!
TWO-POSITION CONTROL
Dir
Service/Off
Rev
M
~
24 Vac~
24 V
!
isolating transformer!
FLOATING CONTROL
connecting cable terminal
supply and signal lines
(must be equipped with spark suppressors)
1 24 Vac ⊥ 24 Vac 2 24 Vac (clockwise) 24 Vac 3 24 Vac (counterclockwise) 24 Vac control signal
S1 common
CCW (left) 5°
end switches
(when included)
CW (right) 85°
S2 normally closed S3 normally open S4 common S5 normally closed S6 normally open P1 full clockwise
feedback potentiometer
P2 signal P3 full counterclockwise
rotation
direction
3
3
switch
2
2
1
1
Connect via safety
rotation
direction
3
3
switch
2
2
1
1
Connect via safety
rotation
direction
3
3
switch
2
2
1
1
Connect via safety
floating two-position
Dir
Service/Off
Rev
Dir
Service/Off
Rev
Dir
Service/Off
Rev
name
M
~
S1
S1
S2
M
~
END SWITCHES
M
~
totally CCW
= max.
totally CCW
S2
S3
S3
S4
S4
S5
S5
S6
S6
P3
totally CW
= 0
P2
totally CW
= 0
POTENTIOMETER
= max.
P1
FEEDBACK
10 k
5 EN0B-0320GE51 R0409
SmartAct N2024 / N20230, N3424 / N34230
N20230 / N20230-2POS / N34230
rotation
3
3
direction
switch
2
230 Vac~
2
Dir
Service/Off
Rev
rotation
3
3
direction
switch
2
M
~
230 Vac~
2
Dir
Service/Off
Rev
M
~
TERMINAL STRIP 1
1
230 V
!
1
Connect via safety switch/connector
for all-pole disconnection > 3 mm!
TWO-POSITION CONTROL
230 V
!
1
1
Connect via safety switch/connector
for all-pole disconnection > 3 mm!
FLOATING CONTROL
(not applicable to N20230-2POS)
N20230-SW2
TERMINAL STRIP 1
END SWITCHES
rotation
direction
3
3
switch
Service/Off
230 Vac~
230 V
!
2
2
1
1
Connect via safety switch/connector
for all-pole disconnection > 3 mm!
TWO-POSITION CONTROL
Rev
Dir
M
~
230 Vac~
230 V
!
FLOATING CONTROL
rotation
direction
3
3
switch
2
2
1
1
Connect via safety switch/connector
for all-pole disconnection > 3 mm!
NOTE: Internal end switches S1 and S4 must be connected to the same power source.
N20230-P10K
TERMINAL STRIP 1
FEEDBACK POTENTIOMETER
rotation
direction
3
3
switch
Service/Off
230 Vac~
230 V
!
2
2
1
1
Connect via safety switch/connector
for all-pole disconnection > 3 mm!
TWO-POSITION CONTROL
Rev
Dir
M
~
230 Vac~
230 V
!
FLOATING CONTROL
rotation
direction
3
3
switch
2
2
1
1
Connect via safety switch/connector
for all-pole disconnection > 3 mm!
connecting cable terminal
supply and signal lines
(must be equipped with spark suppressors)
1 230 Vac ⊥ 230 Vac 2 230 Vac (clockwise) 230 Vac 3 230 Vac (counterclockwise) 230 Vac control signal
floating two-position
S1 common
CCW (left) 5°
end switches
(when included)
CW (right) 85°
S2 normally closed S3 normally open S4 common S5 normally closed S6 normally open P1 full clockwise
feedback potentiometer
P2 signal P3 full counterclockwise
Dir
Service/Off
Rev
Dir
Service/Off
Rev
name
S1
S1
S2
M
~
END SWITCHES
M
~
totally CCW
totally CCW
S2
S3
S3
S4
S4
S5
S5
S6
S6
P3
totally CW
= max.
= 0
P2
totally CW
= 0
= max.
P1
FEEDBACK
POTENTIOMETER
10 k
EN0B-0320GE51 R0409 6
Wiring
Connecting to the Power Supply
In order to comply with protection class II, the power source of 24 V actuators must be reliably separated from the network power supply circuits as per DIN VDE 0106, part 101.
Access Cover
To facilitate wiring the actuator to the controller, the access cover can be detached from the actuator.
IMPORTANT
Remove power before detaching the access cover. Once the access cover has been removed, please take care to avoid damaging any of the parts now accessible.
SmartAct N2024 / N20230, N3424 / N34230
S3
A B
A
B
S6 S1 S2
0
90
C
S4
D
45
S5
90
0
C
D
The internal auxiliary switches are field-installable parts providing two SPDT freely-adjustable switches.
Access Cover Kit
Order no.: WB20 For M20 outlets. Contains:
1 access cover (with screw)
2 cable connectors
2 dust-protection caps
SPARE PARTS
Fig. 10. Access cover (N2024-SW2)
Depending upon the model, the access cover may have one or two terminal strips, including a layout with a description for each of the terminals.
Fig. 11. N2024-SW2 with access cover removed
OPTIONAL ACCESSORIES
The following optional accessories can be ordered separately.
Auxiliary Switch Kit
Order no.: SW2
Spare Parts Kit
Order no.: A7209.2071 The spare parts kit contains the following items:
Anti-rotation bracket and screws
SM Mounting plate and screws
Access cover screw
Plastic protective cap for protection standard IP54
Mechanical end limit screw and retainer
Anti-Rotation Bracket Kit
Order no.: A7209.2073 The anti-rotation bracket kit can be ordered separately.
Contains:
10 anti-rotation brackets
20 screws
SM Mounting Plate Kit
Order no.: A7209.2072 The SM mounting plate kit can be ordered separately.
Contains:
10 SM mounting plates
20 screws
7 EN0B-0320GE51 R0409
SmartAct N2024 / N20230, N3424 / N34230
DIMENSIONS
100 mm (3-15/16”)
shaft
adapter
min. 60 mm (2-3/8”)
adapter (reverse)
20.6 mm (1-3/16”)
shaft
223 mm (8-25/32”)
48 mm
(1-7/8”)
95°
90
60
30
0
92 mm (3-5/8”)
1000 mm (39”)
132 mm (5-3/16”)
230 mm [+/- 0.5 mm] (9-1/16” [+/-1/64”])
20 mm (25/32”)
2 mm (5/64”)
13 mm (1/2”)
7 mm (9/32”)
5 mm (+0.05, -0.10 mm)
25/128” (+0.002, -0.004”)
anti-rotation bracket
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich / Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany
EN0B-0320GE51 R0409
Loading...