Honeywell N10230-2POS, N0524, N05230-2POS, N1024 PRODUCT DATA

N0524/N1024, N05230-2POS/N10230-2POS
NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR
FLOATING AND 2-POSITION CONTROL
PRODUCT DATA
SPECIFICATIONS
Supply voltage
N0524/N1024 24 Vac/dc -15%/+20%, 50/60 Hz
This non-spring return direct-coupled damper actuator provides floating and two-position control for:
air dampers,
VAV units,
air handlers,
ventilation flaps,
louvers, and
reliable control for air damper applications with up to
2
/ (5 Nm) and 2 m2 (10 Nm) (seal-less damper
1 m blades; air friction-dependent).
FEATURES
Declutch for manual adjustment
Adjustable mechanical end limits
Removable access cover for direct wiring
Mountable in any orientation
Rotation direction and service/OFF switch
N05230-2POS/N10230-2POS
Nominal voltage N0524/N1024 24 Vac/dc, 50/60 Hz
N05230-2POS/N10230-2POS
All values stated hereinafter apply to operation under nominal voltage conditions.
Power consumption N0524/N1024 5 VA / 2 W N05230-2POS 22 VA / 2 W at 50 Hz 25 VA / 2 W at 60 Hz N10230-2POS 22 VA / 2 W at 50 Hz 25 VA / 2 W at 60 Hz
Ambient limits
Ambient operating limits -20...+60 °C (-5...+140 °F) Ambient storage limits -30...+80 °C (-22...+176 °F) Relative humidity 5...95%, non-condensing
Safety
Protection standard IP54 Protection class II as per EN 60730-1 Overvoltage category II
Lifetime
Full strokes 60000 Repositions 1.5 million
Mounting
Round damper shaft 8...16 mm Square damper shaft 6...13 mm; 45° steps Shaft length min. 41 mm
End switches (when included) Rating 5 A (resistive), 3 A (inductive) Triggering points 5° / 85°
Torque rating 5 Nm / 10 Nm Runtime for 90°
N0524 / N1024 90 sec (dc / 60 Hz ac) N0524 / N1024 110 sec (50 Hz ac) N05230-2POS 65...110 s (60/50 Hz) N10230-2POS 65...140 s (60/50 Hz)
Rotation stroke 95° ± 3° Dimensions see "Dimensions" on page 6 Weight (without cables) 450 g Noise rating 35 dB(A) max. at 1 m;
40 dB(A) for 230 Vac at 65 sec runtime
230 Vac -15%/+20%, 50/60 Hz
230 Vac, 50/60 Hz
® U.S. Registered Trademark EN0B-0477GE51 R0408 Copyright © 2008 Honeywell Inc. • All rights reserved
N0524/N1024 AND N05230-2POS/N10230-2POS DAMPER ACTUATORS FOR FLOATING/2-POSITION CONTROL
PRODUCT IDENTIFICATION SYSTEM
N = non-spring return S = spring return
05 = 5 Nm 10 = 10 Nm
N
5
SmartAct
Fig. 1. Product Identification System
0
010 = modulating + floating 24 = 24 V floating + ON/OFF 230 = 230 V ON/OFF
2
equipped with two
end switches
S
W
-
+ ON/OFF
24
Contents of Package
The delivery package includes the actuator and parts 1 through 6 (see Fig. 2), plus two cable grommets and a spare cable grommet.
RUN MODES
The function selection switch (see Fig. 3) can be used to place the actuator into either of two different modes:
Service/Off; or
the floating/2-position run mode ("Dir" for CCW-closing
dampers or "Rev" for CW-closing dampers).
floating/2-position
Dir
MODELS
order no. supply voltage end switches torque
N05024 -­N05024-SW2 2 N1024 -­N1024-SW2 N05230-2POS 5 Nm N10230-2POS
24 Vac/dc
2
230 Vac --
BASIC FEATURES
1
2
5 Nm
10 Nm
10 Nm
Power-Off Behavior
If power is removed, the shaft adapter remains in position.
Service/Off
If the function selection switch is set to the "Service/Off" position, then all rotary movement is cancelled, and all control signals are ignored, thus allowing the actuator to be manually operated safely.
Floating/2-Position Run Mode
N0524
3
Dir
4
Service/Off
Rev
5
6
Fig. 2. Setting units and control elements
Legend for Fig. 2:
1) Universal shaft adapter
2) Mechanical end limits (manually adjustable)
3) Declutch button
4) Function selection switch
5) Removable access cover
6) Anti-rotation bracket
If the function selection switch has been set to one of the two floating/2-position control settings – and if the actuator is wired correspondingly (see Fig. 8, Fig. 9, and Fig. 10) – then as soon as operating power is applied, the shaft adapter will run according to the control signals applied.
Table 1 describes the behavior ("stops," rotates "CCW," or rotates "CW") of the N0524 / N1024 in dependence upon the control signals (switch "open" or "24 Vac/dc") applied to terminals 3 and 4, the function selection switch setting, and the manner in which the actuator is wired (either for floating mode: see Fig. 8; or for 2-position mode: see Fig. 9).
wiring
float.
2-pos.
Table 2 describes the behavior ("stops," rotates "CCW," or rotates "CW") of the N05230-2POS / N10230-2POS in dependence upon the control signals (switch "open" or "230 Vac") applied to terminals 1 and 3 and the function
Service/Off
Rev
Fig. 3. Function selection switch
Table 1. Behavior of N0524/N1024
control signal at switch setting
term. 3 term. 4 Dir Service/Off Rev
open open stops stops stops
open 24Vac/dc CCW stops CW 24Vac/dc open CW stops CCW 24Vac/dc open CW stops CCW 24Vac/dc 24Vac/dc CCW stops CW
Service / Off
Dir
Service/Off
Rev
EN0B-0477GE51 R0408