
TB7100A1000 MultiPRO™
Multispeed and Multipurpose Thermostat
FOR CONVENTIONAL, HEAT PUMP, FAN COIL AND PTAC SYSTEMS
GUIDE SPECIFICATION
GENERAL
A. OVERVIEW: The contractor shall furnish, install, and place in operating condition an HVAC control system
described herein. All units shall be located in accordance with the plans.
B. TYPE OF SYSTEM: System Requirements:
C. CODES AND
STANDARDS:
a. Control up to 1 heating and 1 cooling stage for gas heat, electric heat or conventional
rooftops. Up to 2 heat and 1 cool for heat pump, fan coil (2 or 4 pipe), and PTAC.
b. Up to 3 fan speeds for fan coil and 2 fan speeds for PTAC applications
c. Remote setback capability for occupancy sensors and timeclocks (optional)
d. Changeover input for 2 pipe fan coil systems.
e. Fan ramping and fan reset algorithms for fan coil and PTAC applications.
f. Provide minimum 2 year clock backup.
g. Provide two Occupied and two Unoccupied periods per day.
h. Offer automatic heat/cool changeover with 2°F minimum deadband.
i. Provide cumulative override capability for a 1 to 12 hour installer-adjustable period.
j. Include a comfort adjust feature to modify setpoints for the override duration.
k. Provide Proportional plus Integral (P + I) temperature control.
l. Display room temperature in °F or °C.
m. Use multiple remote sensors (optional).
n. Provide five levels of keypad lockout - none, schedule / system, schedule / system /
fan, schedule / system / fan / setpoint, and complete.
o. Provide Holiday Override, 1-365 days.
p. Provide separate configurable recovery ramps for heating and cooling.
q. Provide separate configurable cycle rates for heating and cooling response.
r. Programmable or non-programmable modes.
System Components:
a. Seven day programmable thermostat with subbase.
b. Wall mount temperature sensors (optional).
The system shall comply with applicable provisions of ASHRAE 90-75.
These specifications are based on equipment from Honeywell to set a standard for design and
quality.
D. WIRING: All wiring shall meet National Electrical Codes and local electrical codes.
E. TESTING
GUARANTEE
SERVICE:
— Prior to installation, the contractor shall provide copies of submittals.
— The contractor is responsible for assuring that conduit and wire quantity, size, and type are
suitable for the equipment supplied.
— Upon completion, the contractor shall conduct a total system test for the owner and
engineer.
— All components, parts, and assemblies supplied by the manufacturer shall be guaranteed
against defects in materials and workmanship for 2 years.
— Warranty service shall be performed by the contractor.

TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
SEQUENCE OF OPERATIONS
The heating and cooling setpoints shall be individually adjustable for both the Occupied and Unoccupied periods. The thermostat
shall have a minimum deadband of 2°F (no mechanical heating or cooling shall operate within this deadband). Space
temperature deviation above the cooling setpoint or below the heating setpoint shall generate a demand signal to control the
system as follows:
A. HEATING: The thermostat shall control the heating output based on the demand signal communicated from
the thermostat program, taking into account both space temperature deviation (proportional
gain), the duration of that temperature deviation (integral gain).
The thermostat shall energize heating equipment when space temperature falls below heating
setpoint.
B. COOLING: The thermostat shall control the cooling output based on the demand signal communicated from
the thermostat program, taking into account both space temperature deviation (proportional
gain), the duration of that temperature deviation (integral gain).
The thermostat shall energize cooling equipment when space temperature exceeds cooling
setpoint.
C. HEATING SETBACK
AND COOLING
SETUP:
D. SETPOINT
RECOVERY
FROM UNOCCUPIED
TO OCCUPIED:
E. FAN OPERATION: For Heat pump or Conventional modes:
Initiation of heating setback or cooling setup for each of 7 days shall be provided by a
programmed time schedule manually entered into the thermostat. When all or a portion of a
manually programmed schedule is unavailable, the thermostat shall control to the default
program as shown in Table 1.
Table 1. Default Program.
Heating Setpoints 70°F (21°C) 55°F (13°C)
Cooling Setpoints 75°F (24°C) 85°F (29°C)
The thermostat shall incorporate a ramping feature that gradually changes the space setpoints.
During recovery operation, the setpoint changes at a rate in degrees per hour (defined in the
Installer Setup Menu).
a. On: Fan operates continuously in Occupied mode, and during a call for heat or cool in
the Unoccupied mode. Uses the G fan relay.
b. Auto: Fan is energized with calls for heating and cooling. Uses the G fan relay.
For PTAC and Fan coil modes:
a. Lo, Med, Hi (Fan Coil), Lo, Hi (PTAC): Fan operates continuously in Occupied mode,
and during a call for heat or cool in the Unoccupied mode. Uses the G, G2, G3, fan
relays.
b. Auto: Fan is energized with calls for heating and cooling. Auto uses the fan ramping
algorithm to automatically select the correct fan speed
c. PTAC and Fan Coil modes can be configured for Auto only, constant fan speed only
(Lo, Med, Hi), or both.
d. Auto Fan Reset: Set the fan from a constant fan speed (Lo, Med, Hi) to Auto after 2 or
4 hour time period. Saves energy and fan usage. (optional feature)
Occupied Unoccupied
F. MINIMUM STAGE
OPERATION TIME:
G. P O WE R
INTERRUPTION:
H. OVERRIDES: a. The Override button can be used when the thermostat is in Unoccupied mode. It shall
63-2676—03 2
a. Minimum On: Heat - 1 minute; Cool - 3 minutes.
b. Minimum Off: Cool & Heat Pump - 1 minute.
a. On loss of power, the thermostat shall maintain programmed times and temperatures
for 10 years.
b. Clock and day information shall be retained for a minimum of 2 years.
switch to the Occupied mode for an installer-configured number of hours.
b. The Holiday Override shall fix the schedule to operate in Unoccupied mode for a num-
ber of days (between 1 and 365) without changing programming saved in memory.
c. Pressing “Cancel” or “Run Schedule” shall cancel the overrides and return to the
program.
d. Remote Setback input terminals can be used to operate the thermostat in either Occu-
pied or Unoccupied mode (non-programmable mode only).