Honeywell L482A Installation Guide

L482A
Low Limit Controller
INSTALLATION INSTRUCTIONS
BEFORE INSTALLATION
No special tools are required to install the L482A Low Limit Controller. Refer to the job drawings for specific wiring and installation information.
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Mounting
IMPORTANT
1. The controller operates from the lowest temperature
along the entire 20 feet of the sensing element.
2. Locate controller case and bellows where ambient
temperature is always warmer than the set point.
3. For settings above the scale range midpoint it can be
necessary to locate the controller case close to a steam pipe or other warm surface and make sure the element does not extend across a cold surface.
Controller
Surface mount the controller (Fig. 1) vertically on any convenient location (including the duct itself). Orient the case with the bellows positioned on the bottom.
SETPOINT SCALE
20 FT BY 1/8 INCH SENSING ELEMENT
3/8 X 3/16 (10 X 5) DIAMETER ELONGATED MOUNTING HOLE
1-1/8 (29)
1 (25)
MOUNTING HOLES (2) 10-32 UNF-2B THREAD
5/16 (8)
1-7/8
(48)
4 (101)
SETPOINT ADJUSTMENT SCREW
3-1/4 (83)
7/8 (22) HOLE FOR 1/2 CONDUIT WITH 1-3/32 (28) KNOCKOUT RING FOR 3/4 CONDUIT
3/16 (5) DIAMETER MOUNTING HOLE
PUSH TO RESET
4-11/16
(119)
2-3/32
(53)
5/16
(8)
C606A
Fig. 1. L482A Low Limit Controller dimensions in in. (mm).
® U.S. Registered Trademark Copyright © 2004 Honeywell International Inc. All Rights Reserved
95-7432-1
996-496 Rev. A
L482A LOW LIMIT CONTROLLER
IF
Sensing Element
IMPORTANT
• The maximum allowable sensing element tempera-
ture is 250°F (121°C).
• Uncoil only the amount of element required for the
application.
• Bend element carefully and only as much as neces-
sary. Bends require a minimum radius of one inch (25 mm).
• Bend only some distance from the controller.
• Pulling on the element damages it.
• For elements subject to vibration, provide protection
from any surface which the element contacts.
• Mount element horizontally as shown in Fig. 2 and 3.
1. Locate the sensing element where it can sense the temperature of the air to be controlled.
NOTE: Locate the element away from hot or cold air
inlets.
2. Punch or drill a 1/4 in. hole in the duct and install CCT1802 Grommet (Fig. 2) to protect the capillary.
3. Carefully insert the element through the grommet into the duct. Use as much element as possible to provide maximum protection.
4. Mount the element inside the duct or fasten to the coil if freezing can occur. a. Duct mounting: Use CCT2600 Clip (Fig. 2). b. Coil fastening: Use perforated metal straps (Fig. 3).
GROMMET
ELEMENT
USE NO. 10
SHEET METAL
SCREWS
OPERATION
On a temperature drop to setpoint, LINE 1 to M1 contacts close and LINE 2 to M2 contacts open. Reset to the normal state is manual.
WIRING
WARNING
Electrical Shock Hazard. Can cause severe injury, death or equipment damage.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
IMPORTANT
– All wiring must agree with applicable codes,
ordinances and regulations.
– When switching both ac line voltage and an
automation input (Fig. 4), the input wires must run no more than three feet in the same conduit. See Fig. 6.
For typical L482A wiring, see Fig. 4 and 5.
NOTES:
Screw terminals are provided for wiring
connections.
Maximum wire size is 12 AWG. – Use 8-32 x 1/4-inch screws for replacement if
necessary. Longer screws can interfere with the switch mechanism and damage the switch.
CLIP
DETAIL
BEND HERE
NECESSARY
Fig. 2. Element mounted to duct with CCT2600 Clips.
PERFORATED METAL STRAPS
WIRE FASTENINGSELEMENT
Fig. 3. Element mounted in duct with
perforated metal straps.
C789
C790
LINE 2 LINE 1
M1
C791
L1
(HOT)
L2
TO STATUS
OR ALARM
INPUT OF
AUTOMATION
SYSTEM
M2
FAN RELAY
Fig. 4. Typical wiring diagram with automation input.
95-7432–1 2 996-496 Rev. A
Loading...
+ 2 hidden pages