The FSL100 Series of flame detectors from Honeywell delivers robust, fast, and
reliable detection of flaming fires in a wide range of applications.
The range consists of UV, UV/IR and IR3 flame detectors.
All utilize sophisticated sensing and signal analysis to
detect fires quickly while also rejecting false alarms.
The FSL100 may be small and lightweight for
easy installation but it is designed to work in
tough indoor/outdoor environments, as well
as potentially explosive atmospheres.
With a large field of view it can
detect a range of different types
of fire including hydrocarbon
and non-hydrocarbon sources.
Available in UV, UV/IR and 3IR we
have your application covered.
Suitable for Many Applications
• UV, UV/IR and IR3 available
• Hydrocarbon and non-hydrocarbon sources
• Use in potentially explosive atmospheres
• Indoor and outdoor operation
• High visibility red or discrete white models available
Great Performance
• Approved to EN5410 and FM3260 flame
detector standards
• Comprehensive automatic self test
•Remote manual self test option
Fast & Reliable
• High speed sensors and microprocessor
• Sophisticated analysis algorithms
• Continuous health monitoring
• False alarm rejection
Reduced Life Cost
• Long life elements
• Pressure compensation to avoid contamination
• 2 year warranty
• Buy with confidence
Ease of Installation and Use
• Relay and mA outputs as standard
• Lightweight GRP housing
• Pre-formed knockouts
• Optional swivel mounting bracket
• Long range test lamp available
Page 3
FSL100-UV
• Suitable for indoor applications; for
example fume hoods and hydrogen
storage areas
• Effective solution for materials burning
with low temperatures, e.g. Sulphur
• Alarms to fires from heavy hydrocarbons (wood,
paper, petroleum, etc.), light hydrocarbons
(methanol, methane, etc.), and hydrogen
• Good resistance against the
influences of:
- Direct and reflected sunlight
- Artificial light, such as fluorescent
tubes and glass covered halogen lamps
Page 4
FSL100-UV/IR
• Analysis of the flame flicker-frequency
for improved false alarm rejection
• Dual sensing methodology enables
a wide range of hydrocarbon and
non-hydrocarbon fires to be
effectively detected
• Good resistance against the influences of:
- Direct and reflected sunlight
- Artificial light, such as fluorescent tubes
and glass covered halogen lamps
- Arcs and electric discharges (static
or from e.g. electric motors)
- The radiation from electric welding
provided that the electric welding takes
place at a distance more than 10 feet from
the flame detector (a welding rod
contains organic compounds which
may produce a small flame)
Page 5
FSL100-IR3
• Analysis of the flame flicker frequency
for improved false alarm rejection
• Particularly suited to liquid
hydrocarbon and dirty fires
• Affected less by window
contamination or smoky fires
• Good resistance against the
influences of:
- Direct and reflected sunlight
- Artificial light, such as fluorescent
tubes and glass covered halogen
lamps
- Arcs and electric discharges (static
or from e.g. electric motors)
- The radiation from electric welding
provided that the electric welding
takes place at a distance more
than 10 feet from the flame
detector (a welding rod contains
organic compounds which may produce a small flame)
• Especially suitable fires that emit
large amounts of smoke
Pressure compensating elementPCE (Pressure Compensating Element) avoids moisture build-up in the detector housing due to changes in ambient air-pressure
Dimensions4.9 x 3.15 x 2.25 in (125 x 80 x 57 mm)
Weight1.05 lb (465 g)
Ingress protectionIP65
Temperature, operating40 ˚F to +158 ˚F (40 ˚C to +70 ˚C)
Temperature, ambient ATEX and FM class 361113 ˚F to +158 ˚F (25 ˚C to +70 ˚C)
Continuous yellow: fault
Flashing yellow: Fault and guide to repeat self-test after a self-test failure
Continuous red: alarm
Standard available 420 mA (stepped, sinking, non-isolated)
• 0 mA power fault / microprocessor fault
• 2 mA optical fault
• 4 mA normal operation
• >20 mA alarm
De-energized during normal operation, no alarm, SPDT, 30 VDC – 2 A, 60 W max. Energised during normal operation, no fault,
SPDT, 30 VDC – 2 A, 60 W max.
Cable entry M20 clearance. Supplied with gland suitable for cable diameter from 0.2” (5.5mm) to 0.5”(13mm). Terminals
suitable for 0.5mm
• Fire control panels using end of line (EOL) and alarm resistors (current increase)
• Devices that operate via relay switched outputs
• PLCs with 420 mA inputs
To be adjusted to the fire control panel; free terminals are dedicated to the resistors
Note: the alarm and EOL resistor must be rated 2 W min. each and the total power dissipation of both alarm and EOL resistor
should not exceed 2 W
2
(20AWG) to 1.5mm2 (15AWG) wire
2
)n-heptane fire
Page 8
Honeywell Analytics Gas Detection
Honeywell Analytics is able to provide gas detection solutions to meet the requirements of all applications and industries.
Contact us in the following ways:
HEADQUARTERS
Europe , Middle East , Africa
Life Safety Distribution GmbH
Javastrasse 2
8604 Hegna u
Switzerland
Tel: +41 (0)44 943 4300
Fax: + 41 (0)44 943 4398
gasdetection@honey well.com
Customer Service:
Tel: 00800 333 222 44 ( Freephone numb er)
Tel: +41 44 943 4380 (A lternative nu mber)
Fax: 0 0800 333 222 55
Middle East Tel: +971 4 450 5800 (Fixe d Gas Detection)
Middle East Tel: +971 4 450 5852 (Portab le Gas Detect ion)
Honeywell Analytic s Distribution Inc.
405 Barclay Blvd.
Lincol nshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honey well.com
RAE System s by Honeywell
Phone: 408.952.8200
Toll Free: 1 .888.723.4 800
Fax: 408.952.8480
Asia Pacific
Honey well Analy tics Asia P acific
7F SangA m IT Tower,
434, Worldcupbuk-ro, Mapo-gu,
Seoul 03922,
Korea
Tel: +82 (0) 2 6909 0300
Fax: + 82 (0) 2 2025 0328
India Tel: +91 124 4752700
China Tel: +86 10 5885 8788 3000
analytics.ap@honey well.com
www.honeywellanalytics.com
www.raesystems.com
Pleas e Note:
While ev ery effor t has been made to ensure ac curacy in this publicat ion, no
responsibili ty can be accepted for e rrors or omis sions. Data may c hange, as well
as legislation , and you are stro ngly advised t o obtain copies of the most recent ly
issue d regulation s, standards , and guideline s. This public ation is not inten ded to
form the basis of a contrac t.