Honeywell FSA-8 Quick Reference Guide

FSA-8 Fire System Annunciator
Quick Reference Guide
KEYSWITCH MODULE
(Optional)
PRESS TO
SILENCE
YELLOW LEDs
TROUBLE
SILENCE / RESET
TEST
POWER
FSA-001-V2
SILENCE / RESET SWITCH First Press
Silences the FSA's local sounder.
Silences the local sounder and silences the System Notification Appliances.
Second Press
Resets the Control Panel, Smoke Detectors, and Notification Appliances.
No affect.
Note to Installer - Please check options enabled.
KEYSWITCH (not programmable): First Activation - Silences the System Notification Appliances including the FSA's local sounder.
Second Activation - Resets the Control Panel, Smoke Detectors, and Notification Appliances.
Indicators
LED STATE INDICATION
Steady AC power applied. Green
(POWER) Yellow
(TROUBLE)
Off AC power loss. Off Normal state. Steady System trouble detected or any fire-related trouble. Flashing Panel communication loss. Call for service immediately.
Zone or zone list in check or trouble. Flashes in sync with zone (red or yellow) LED. Red (Zone) and Yellow (Fire Supervisory Zone)
Off Normal state. Steady Zone or zone list faulted or in alarm. Flashing Zone or zone list in check or trouble. Flashes in sync with TROUBLE (yellow) LED.
Switches
SWITCH FUNCTION TEST When pressed, sequentially lights all zone (red) LEDs to demonstrate operability. SILENCE/RESET When pressed, initiates sequence dependent upon programmed options. All options silence sounder
for a period not to exceed 24 hrs.
Sounder
CONDITION INDICATION Sound steadily Zone or zone list in alarm. Sound remains until manually silenced, locally or remotely, by user. Beep rapidly System/Zone in trouble.
ÊK4267V3mŠ
K4267V3 5/06 Rev. A