Honeywell FSA-24 Quick Reference Guide

Honeywell FSA-24 Quick Reference Guide

FSA-24 Fire System Annunciator

Quick Reference Guide

RED LEDs

 

PRESS TO

TROUBLE

SILENCE

 

 

SILENCE / RESET

 

TEST

 

POWER

YELLOW LEDs

 

SILENCE / RESET SWITCH

First Press

Silences the FSA's local sounder.

Silences the FSA's local sounder and silences the Fire Partition's Notification Appliances.

KEYSWITCH MODULE (Optional)

FSA-002-V2

Second Press

Resets the Fire Partition.

No affect.

Note to Installer - Please check options enabled.

KEYSWITCH (not programmable):

First Activation - Silences the Fire Partition's Notification Appliances including the FSA's local sounder.

Second Activation - Resets the Fire Partition.

Indicators

LED

STATE

INDICATION

Green (POWER)

Steady

AC power applied.

 

Off

AC power loss.

Yellow (TROUBLE)

Off

Normal state.

 

Steady

System trouble detected or any fire-related trouble.

 

Flashing

Panel communication loss. Call for service immediately.

 

 

Zone or zone list in check or trouble. Flashes in sync with zone (red or yellow) LED.

Red (Zone) and

Off

Normal state.

Yellow (Fire

Steady

Zone or zone list faulted or in alarm.

Supervisory Zone)

Flashing

Zone or zone list in check or trouble. Flashes in sync with TROUBLE (yellow) LED.

Switches

SWITCH

FUNCTION

TEST

When pressed, sequentially lights all zone (red) LEDs to demonstrate operability.

SILENCE/RESET

When pressed, initiates sequence dependent upon programmed options. All options silence sounder for a period not to

 

exceed 24 hrs.

Sounder

CONDITION

INDICATION

Sound steadily

Zone or zone list in alarm. Sound remains until manually silenced, locally or remotely, by user.

Beep rapidly

System/Zone in trouble.

ÊK4267-1V3(Š

K4267-1V3 5/06 Rev. A