FSA-24 Fire System Annunciator
RED LEDs
Quick Reference Guide
KEYSWITCH MODULE
(Optional)
PRESS TO
SILENCE
YELLOW LEDs
TROUBLE
SILENCE / RESET
TEST
POWER
FSA-002-V2
SILENCE / RESET SWITCH
First Press
Silences the FSA's local sounder.
Silences the FSA's local sounder and silences the Fire Partition's Notification Appliances.
Second Press
Resets the Fire Partition.
No affect.
Note to Installer - Please check options enabled.
KEYSWITCH (not programmable):
First Activation - Silences the Fire Partition's Notification Appliances including the FSA's local sounder.
Second Activation - Resets the Fire Partition.
Indicators
LED STATE INDICATION
Steady AC power applied. Green (POWER)
Off AC power loss.
Yellow (TROUBLE)
Off Normal state.
Steady System trouble detected or any fire-related trouble.
Flashing Panel communication loss. Call for service immediately.
Zone or zone list in check or trouble. Flashes in sync with zone (red or yellow) LED.
Red (Zone) and
Yellow (Fire
Supervisory Zone)
Off Normal state.
Steady Zone or zone list faulted or in alarm.
Flashing Zone or zone list in check or trouble. Flashes in sync with TROUBLE (yellow) LED.
Switches
SWITCH FUNCTION
TEST When pressed, sequentially lights all zone (red) LEDs to demonstrate operability.
SILENCE/RESET When pressed, initiates sequence dependent upon programmed options. All options silence sounder for a period not to
exceed 24 hrs.
Sounder
CONDITION INDICATION
Sound steadily Zone or zone list in alarm. Sound remains until manually silenced, locally or remotely, by user.
Beep rapidly System/Zone in trouble.
ÊK4267-1V3(Š
K4267-1V3 5/06 Rev. A