FSA-24 Fire System Annunciator
Quick Reference Guide
RED LEDs |
|
|
PRESS TO |
TROUBLE |
|
SILENCE |
||
|
||
|
SILENCE / RESET |
|
|
TEST |
|
|
POWER |
|
YELLOW LEDs |
|
SILENCE / RESET SWITCH
First Press
Silences the FSA's local sounder.
Silences the FSA's local sounder and silences the Fire Partition's Notification Appliances.
KEYSWITCH MODULE (Optional)
FSA-002-V2
Second Press
Resets the Fire Partition.
No affect.
Note to Installer - Please check options enabled.
KEYSWITCH (not programmable):
First Activation - Silences the Fire Partition's Notification Appliances including the FSA's local sounder.
Second Activation - Resets the Fire Partition.
Indicators
LED |
STATE |
INDICATION |
Green (POWER) |
Steady |
AC power applied. |
|
Off |
AC power loss. |
Yellow (TROUBLE) |
Off |
Normal state. |
|
Steady |
System trouble detected or any fire-related trouble. |
|
Flashing |
Panel communication loss. Call for service immediately. |
|
|
Zone or zone list in check or trouble. Flashes in sync with zone (red or yellow) LED. |
Red (Zone) and |
Off |
Normal state. |
Yellow (Fire |
Steady |
Zone or zone list faulted or in alarm. |
Supervisory Zone) |
Flashing |
Zone or zone list in check or trouble. Flashes in sync with TROUBLE (yellow) LED. |
Switches
SWITCH |
FUNCTION |
TEST |
When pressed, sequentially lights all zone (red) LEDs to demonstrate operability. |
SILENCE/RESET |
When pressed, initiates sequence dependent upon programmed options. All options silence sounder for a period not to |
|
exceed 24 hrs. |
Sounder
CONDITION |
INDICATION |
Sound steadily |
Zone or zone list in alarm. Sound remains until manually silenced, locally or remotely, by user. |
Beep rapidly |
System/Zone in trouble. |
ÊK4267-1V3(Š