D146 Differential Pressure Regulators
Used to eliminate excessive pump head pressure when most radiator valves are closed due to reduced demand.
• Install between supply and return sides of a hydronic system to stabilize pressure differential and reduce the effects of demand changes.
• Control maintains a constant differential between the two sides by opening a bypass whenever the difference between supply and return reaches the setpoint.
• Provides silent, trouble-free service.
• Easy installation; requires no electrical hookup.
• Easy adjustment of pressure by turning regulating cap.
• Built-in differential pressure indicator.
• Brass valve body with thermoplastic and stainless steel parts.
• Diaphragm of EPDM.
D146 Capacities
Controls
Hydronic
Maximum Inlet Pressure Rating (psi): 85 Psi Outlet Pressure Adjustment Range (psi): 0-17 psi Pipe Connection:
Angle type, female threaded NPT
Pipe Size
Product Number
D146M1032 3/4 in. DN20 18 gpm;
D146M1040 1 1/4 in. DN32 50 gpm;
Capacity
120,000 Btu/hr
395,000 Btu/hr
Temperature Range: 230 F (110 C) Materials: Brass (body), Stainless steel and engineered thermoplastics.
EPDM diaphragm.
Dimensions, Approximate
6 1/4 in. high x 3 3/8 in. wide
8 1/2 in. high x 4 1/4 in. wide
160 mm high x 86 mm wide
213 mm high x 109 mm wide
70-6910 217
Description Includesinch DN inch mm
Differential Pressure Regulator, 3/4 in.
Differential Pressure Regulator, 1 1/4 in.
Built-in differential pressure indicator
Built-in differential pressure indicator