Honeywell D06FH Product specification sheet

Pressure reducing valve with balanced seat
Construction
The pressure reducing valve comprises:
• Threaded male connections (options A & B)
• Valve insert complete with diaphragm and valve seat
• Fine filter with 0.16 mm mesh
• Spring bonnet with adjustment knob
•Filter bowl
• Adjustment spring
• Pressure gauge not included (see accessories)
Materials
• Dezincification resistant brass housing
• Brass threaded connections
• High-quality synthetic material valve insert
• Stainless steel fine filter mesh
• High-quality synthetic material spring bonnet with adjustment knob and setting scale
EN0H-1003GE23 R1109 • Subject to change
• Brass filter bowl
• Spring steel adjustment spring
• Fibre-reinforced NBR diaphragm
• NBR seals
D06FH
High pressure pattern
Product specification sheet
Application
Pressure reducing valves of this type protect installations against excessive pressure from the supply. They can be used for household, industrial or commercial applications within the range of their specification.
By installing a pressure reducing valve, pressurisation damage is avoided and water consumption is reduced.
The set pressure is also maintained constant, even when there is wide inlet pressure fluctuation.
Reduction of the operating pressure and maintaining it at a constant level minimizes flow noise in the installation.
Special Features
• The outlet pressure is set by turning the adjustment knob
• The adjustment spring is not in contact with the potable water
• The valve insert is of high quality synthetic material and can be fully exchanged
• Integral fine filter
• Also available without fittings
• Easily retrofittable to convert valve to a reverse-rinsing filter combination
• Can be retrofitted with an inlet non-return valve
• Inlet pressure balancing - fluctuating inlet pressure does not influence outlet pressure
• Light weight
• Reliable and proven
• Meets KTW recommendations for potable water
Range of Application
Medium Water, compressed air* and nitrogen* in
consideration of valid standards (e.g. DIN EN 12502)
Inlet pressure max. 25 bar
Outlet pressure 1.5 - 12 bar (preset to 5 bar)
Technical Data
Operating temperature max. 70°C
Minimum pressure drop 1 bar
Connection size
*
As part of an installation being approved according to PED requirements, this
product must also be certified.
1
/2" - 2"
www.honeywell.com 27
D06FH Pressure reducing valve with balanced seat
Method of Operation
Spring loaded pressure reducing valves operate by means of a force equalising system. The force of a diaphragm operates against the force of an adjustment spring. If the outlet pressure and therefore diaphragm force fall because water is drawn, the then greater force of the spring causes the valve to open. The outlet pressure then increases until the forces between the diaphragm and the spring are equal again.
The inlet pressure has no influence in either opening or closing of the valve. Because of this, inlet pressure fluctuation does not influence the outlet pressure, thus providing inlet pressure balan­cing.
Options
D06FH-... B = With threaded male connection, brass filter bowl -
up to 70 °C Special Versions available on request
Connection size
Connection size R Nominal size
DN 15 20 25 32 40 50
1
/2"
3
/4"1"1
1
/4"1
1
/2"2"
diameter Weight ca. kg 0.8 1.0 2.2 2.4 3.4 5.1 Dimensions mm
L 140 160 180 200 225 255
l 80 90 100 105 130 140
H 96 96 140 140 172 172
h56567777113113
D545472728282
-value 2.4 3.1 7.6 9.1 12.6 12.0
k
vs
Accessories
FN09S-AM HABEDO ® Retrofit filter
6
4
8
2
r
ba
0
10
Reverse-rinsing filter with red bronze filter cup for retro-conversion of a pressure reducing valves to a filter combination unit
M07M Pressure gauge
M07M
ZR06K
Housing diameter 63 mm, rear connection thread
1
G
/4". Ranges: 0 - 4, 0 - 10, 0 - 16 or 0 - 25 bar. Please indicate upper value of pressure range when ordering
FN09S-AM
28 www.honeywell.com
VST06-A
RV277
VST06-B
ZR06K Double ring wrench
For removal of spring bonnet and filter bowl
RV277 Inlet check valve
Available in sizes R
1
VST06-A Connection set
Threaded connections
VST06-B Connection set
Solder connections
/2" - 2"
EN0H-1003GE23 R1109 • Subject to change
Installation Example
D06FH Pressure reducing valve with balanced seat
Connection size R
1
/2"3/4"1"11/4"11/2"2"
DN 15 20 25 32 40 50
W* mm 55 55 60 60 70 70
* Minimum distance from wall to centre line of pipework
Installation Guidelines
• Install in horizontal pipework with filter bowl downwards.
• Install shutoff valves
• The installation location should be protected against frost and be easily accessible
o Pressure gauge can be read off easily o Simplified maintenance and cleaning
• Install downstream of the filter or strainer
o This position ensures optimum protection for the pressure
reducing valve against dirt
• Provide a straight section of pipework of at least five times the nominal valve size after the pressure reducing valve (in accor­dance with DIN 1988, Part 5)
Typical Applications
Pressure reducing valves of this type are suitable for household, industrial and commercial applications within the range of their specifications.
Pressure reducing valves should be installed:
• If the static pressure exceeds the maximum permissible value for the system
• If several pressure zones are required when a pressurisation system is used (pressure reducers on each storey of a buil­ding)
• If pressure fluctuations in the downstream system must be avoided
Flow Diagram
EN0H-1003GE23 R1109 • Subject to change
www.honeywell.com 29
D06FH Pressure reducing valve with balanced seat
Spare Parts
Pressure Reducing Valve D06FH, from 1997 onwards
No. Description Dimension Part No.
1 Valve insert complete1/2" + 3/4"D06FA-1/2
(without filter) 1" + 1
1
/4"D06FA-1A
1
1
/2" + 2" D06FA-11/2
2 Union seal washer1/2" 0901443
(10 pcs.)
3
/4" 0901444
1" 0901445
3
1
1
1
/4" 0901446
1
1
/2" 0901447
2" 0901448
2
3 Blanking plug
with O-ring R
1
/4"
S06K-1/4
(5 pcs.)
4 Replacement filter
insert 1" + 1
5 O-ring
1
4
5
6
(10 pcs.) 1" + 1
6 Brass filter bowl with 1/2" + 3/4" SM06T-1/2
O-ring 1" + 1
1
/2" + 3/4" ES06F-1/2A
1
/4" ES06F-1A
1
1
/2" + 2" ES06F-11/2A
1
/2" + 3/4" 0901246
1
/4" 0901247
1
1
/2" + 2" 0901248
1
/4" SM06T-1A
1
1
/2" + 2" SM06T-11/2
Automation and Control Solutions
Honeywell GmbH Hardhofweg D-74821 Mosbach Phone: (49) 6261 810 Fax: (49) 6261 81309 http://europe.hbc.honeywell.com www.honeywell.com
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorised Repre­sentative Honeywell GmbH
EN0H-1003GE23 R1109 Subject to change without notice © 2009 Honeywell GmbH
Loading...