GENERAL
The AQS51 and AQS61 sensor/controllers for room wall mounting measure the carbon dioxide (CO2) concentration and the temperature. They are used in ventilation and air conditioning systems to control the supply of fresh outside air to the occupants for acceptable indoor air quality and to reduce the unnecessary conditioning of outside air during low-occupancy periods.
This Demand Controlled Ventilation (DCV) is a cost-effective solution to conserve energy and to ensure that no more fresh outside air is supplied than is necessary to meet the actual requirements of the occupants at any given time.
The sensor/controllers offer separate 0(2)...10 Vdc or 0(4)...20 mA outputs for CO2 and temperature. In addition, a digital ON/OFF relay output with switching hysteresis and an output selectable as analog or open collector ON/OFF output are available. Both can be used for alarm or other purposes.
The UART interface (RS232) for serial communication allows a PC to be connected to perform maintenance checks or reconfigurations during normal operation.
If used as a controller, each of these outputs can be configured to provide a more complex ventilation strategy based on a mixture of CO2 plus temperature measurements and to assign a number of functions, including hierarchy.
For this analog output configuration, the software program STRATEGY is available, which is part of the User Interface Program Software package AQS-USP22 used for recalibration, changing the measurement range, or other service and set-up purposes.
AQS51/61
COMBINED CO2-/TEMPERATURE ROOM SENSOR/CONTROLLER
SPECIFICATION DATA
The switching setpoint and differential of the relay output for CO2 limit monitoring or plant/system ON/OFF control can be adjusted within the measurement range. This output or the open collector output (OUT4) can be used also as automatic fire threshold to switch off ventilation when the CO2 level exceeds normal limit of e. g. 2000 ppm in case of fire.
FEATURES
•CO2 measurement range 0...3000 ppm according to 0...0.3% CO2. Factory-calibrated 0...2000 ppm
•Multifunctional unit for temperatureand CO2- measurement or control
•State-of-the-art Non-Dispersion-Infrared (NDIR) technology to measure carbon dioxide gas
•Automatic drift correction (ABC-algorithm) based on a long term evaluation provides typical zero-drift check maintenance-intervals of up to 5 years
•Standard 0(2)...10 Vdc or 0(4)...20 mA output signals
for both CO2 and temperature measurement or control
•Programmable mixed controller signal output(s) provides ventilation control strategies to exactly match application requirements
•Digital ON/OFF relay output for CO2 limit monitoring
•Digital input with programmable delay time for external override function e. g. occupancy sensor, push button or switch
•RS232 interface for configuration, parameter setting or data transfer with a PC using Windows 95/98
•User interface program on diskette for service, recalibration, and changing measurement ranges
•Optional with 4-digit LCD display for selectable indication of:
-CO2 concentration / room temperature alternating
-Error code
-CO2 concentration (ppm)
-Temperature (°C)
-Analog Output 1
-Analog Output 2
-Analog Output 4
® U.S. Registered Trademark |
|
|
|
|
|
EN0B-0374GE51 R0102 |
|
|
|
||||
Copyright © 2002 Honeywell Inc. • All rights reserved |
|
|
|
|
|
|
|
|
|
|
|
|
|
AQS51/61 COMBINED CO2-/TEMPERATURE ROOM SENSOR/CONTROLLER
MODELS
|
Type |
Order Number |
|
CO2 |
and Temperature Room |
AQS51 |
|
Sensor without LCD display |
|||
|
|||
CO2 |
and Temperature Room |
AQS61 |
|
Sensor with 4-digit LCD display |
|||
|
|||
|
|
|
TECHNICAL DATA
ACCESSORIES
Description |
Order Number |
|
Service Software; 3.5” Diskette (for |
|
|
changing the sensing range, para- |
AQS-USP22 |
|
meterization, and post calibration) |
|
|
Test set (consisting of a portable gas |
|
|
generator for zero-point calibration, |
AQS-F0005 |
|
pump, packing, 3m tube, battery, and |
||
|
||
transformer) |
|
|
|
|
|
RS Cable with built-in electronics and |
AQS3/4 cable or |
|
adapters |
AQS31/41 cable |
|
|
|
|
Power supply |
24 Vac ± 20%; 50/60 Hz or 24 Vdc ± 20% |
|
|
Power consumption |
2 W |
|
|
Sensor life expectancy |
>15 years |
|
|
Maintenance interval |
5 years |
|
General |
Self diagnostics |
Complete power/sensor/analog outputs internal test |
|
Status LED indication |
Yellow = Maintenance required; Red = Relay activated |
||
|
|||
|
Power-up time |
≤ 60 s |
|
|
Ambient operating limits |
|
|
|
- Temperature |
0...50 °C |
|
|
- Humidity |
0...95% rh, non-condensing |
|
|
Operating principle |
Non-dispersive infrared (NDIR) |
|
|
Gas sampling mode |
Diffusion and 4 mm gas inlet on bottom of the wall plate |
|
|
Response time |
120 s (diffusion) or 10 s (0.2 ltr/min gas flow) |
|
|
Measurement range |
0...3000 ppm |
|
CO2 Measurement |
Converting range |
0...2000 ppm = 0...10 Vdc (factory setting) |
|
or 2...10 Vdc / 0...20 mA / 4...20 mA |
|||
|
|
||
|
Accuracy |
±1% of measurement range, ±5% of reading |
|
|
Pressure dependence |
+1.58% of reading per kPa deviation from the normal |
|
|
pressure of 100 kPa |
||
|
|
||
|
Annual zero drift |
<±1% of measurement range |
|
|
Operating principle |
Thermistor |
|
Temperature |
Measurement range |
−10...60°C |
|
|
0...50 °C = 0...10 Vdc (factory setting) |
||
Measurement |
Converting range |
||
|
|
or 2...10 Vdc / 0...20 mA / 4...20 mA |
|
|
Accuracy |
±0.2 K |
|
|
Settings and configuration with |
|
|
|
Service Software AQS-USP22 |
|
|
P control |
- Throttling range CO2 |
100...800 ppm |
|
|
- Throttling range temperature |
1...10 K |
|
|
- Reset time adjustment range |
2...500 s (factory setting: 300 s) |
|
|
|
|
EN0B-0374GE51 R0102 |
2 |
AQS51/61 COMBINED CO2-/TEMPERATURE ROOM SENSOR/CONTROLLER
|
For connection of potential-free |
Open > 40 kΩ |
|
Digital input 1 |
contact |
Closed < 100 Ω |
|
Power supply 5 Vdc |
|||
|
|||
|
|
||
|
Closed contact current 1 mA |
|
|
|
Output signal |
0...10 Vdc / 2...10 Vdc, impedance <100 Ω, |
|
|
load >5 kΩ or 0...20 mA / 4...20 mA, load ≤500 Ω |
||
|
|
||
|
Resolution |
10 mV (10 Bits) |
|
Analog outputs |
D/A conversion accuracy |
±2% of output voltage, +0.1 V |
|
±2% of output current, ±0.3 mA |
|||
|
|||
|
Protection |
PTC fuse (auto reset), short-circuit proof |
|
|
Customization of P controller |
Both outputs can be configured to any sensor mix (CO2 + |
|
|
temperature + digital input of 5 proportional ranges with |
||
|
|
priorities and offsets, using STRATEGY, Version 4.0) |
|
|
Single pole, Normally Open (NO), |
1 A / 50 Vac (50 VA) or 1 A / 24 Vdc (30 W) |
|
Digital relay output |
potential-free contact. |
|
|
Factory-adjusted switching setpoint |
Relay activated: ≥1000 ppm |
||
|
|||
|
and differential |
Relay deactivated: ≤900 ppm |
|
Analog output or digital |
Analog output signal |
0...10 Vdc, impedance <100 Ω, load >5 kΩ |
|
open collector output |
Digital open collector output |
Max. 0.5 A, 60 Vdc or 40 Vac (half-wave rectifier protection) |
|
Dimensions |
Housing (L x W x D) |
(120 x 82 x 30) mm |
|
|
|
By pressing the push button, one of the following display |
|
|
|
modes on the 4-digit display is selectable: |
|
|
|
- CO2 and temperature, alternating |
|
|
|
- Error code |
|
Push-button |
MENU |
- CO2 in ppm |
|
|
|
- Temperature in °C |
|
|
|
- Analog output 1 |
|
|
|
- Analog output 2 |
|
|
|
- Analog output 4 |
|
|
|
|
DIMENSIONS
Fig. 1. Dimensions (in mm)
3 |
EN0B-0374GE51 R0102 |