Honeywell AQS51, AQS61 User Manual

GENERAL

The AQS51 and AQS61 sensor/controllers for room wall mounting measure the carbon dioxide (CO2) concentration and the temperature. They are used in ventilation and air conditioning systems to control the supply of fresh outside air to the occupants for acceptable indoor air quality and to reduce the unnecessary conditioning of outside air during low-occupancy periods.

This Demand Controlled Ventilation (DCV) is a cost-effective solution to conserve energy and to ensure that no more fresh outside air is supplied than is necessary to meet the actual requirements of the occupants at any given time.

The sensor/controllers offer separate 0(2)...10 Vdc or 0(4)...20 mA outputs for CO2 and temperature. In addition, a digital ON/OFF relay output with switching hysteresis and an output selectable as analog or open collector ON/OFF output are available. Both can be used for alarm or other purposes.

The UART interface (RS232) for serial communication allows a PC to be connected to perform maintenance checks or reconfigurations during normal operation.

If used as a controller, each of these outputs can be configured to provide a more complex ventilation strategy based on a mixture of CO2 plus temperature measurements and to assign a number of functions, including hierarchy.

For this analog output configuration, the software program STRATEGY is available, which is part of the User Interface Program Software package AQS-USP22 used for recalibration, changing the measurement range, or other service and set-up purposes.

AQS51/61

COMBINED CO2-/TEMPERATURE ROOM SENSOR/CONTROLLER

SPECIFICATION DATA

The switching setpoint and differential of the relay output for CO2 limit monitoring or plant/system ON/OFF control can be adjusted within the measurement range. This output or the open collector output (OUT4) can be used also as automatic fire threshold to switch off ventilation when the CO2 level exceeds normal limit of e. g. 2000 ppm in case of fire.

FEATURES

CO2 measurement range 0...3000 ppm according to 0...0.3% CO2. Factory-calibrated 0...2000 ppm

Multifunctional unit for temperatureand CO2- measurement or control

State-of-the-art Non-Dispersion-Infrared (NDIR) technology to measure carbon dioxide gas

Automatic drift correction (ABC-algorithm) based on a long term evaluation provides typical zero-drift check maintenance-intervals of up to 5 years

Standard 0(2)...10 Vdc or 0(4)...20 mA output signals

for both CO2 and temperature measurement or control

Programmable mixed controller signal output(s) provides ventilation control strategies to exactly match application requirements

Digital ON/OFF relay output for CO2 limit monitoring

Digital input with programmable delay time for external override function e. g. occupancy sensor, push button or switch

RS232 interface for configuration, parameter setting or data transfer with a PC using Windows 95/98

User interface program on diskette for service, recalibration, and changing measurement ranges

Optional with 4-digit LCD display for selectable indication of:

-CO2 concentration / room temperature alternating

-Error code

-CO2 concentration (ppm)

-Temperature (°C)

-Analog Output 1

-Analog Output 2

-Analog Output 4

® U.S. Registered Trademark

 

 

 

 

 

EN0B-0374GE51 R0102

 

 

 

Copyright © 2002 Honeywell Inc. • All rights reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

AQS51/61 COMBINED CO2-/TEMPERATURE ROOM SENSOR/CONTROLLER

MODELS

 

Type

Order Number

CO2

and Temperature Room

AQS51

Sensor without LCD display

 

CO2

and Temperature Room

AQS61

Sensor with 4-digit LCD display

 

 

 

 

TECHNICAL DATA

ACCESSORIES

Description

Order Number

Service Software; 3.5” Diskette (for

 

changing the sensing range, para-

AQS-USP22

meterization, and post calibration)

 

Test set (consisting of a portable gas

 

generator for zero-point calibration,

AQS-F0005

pump, packing, 3m tube, battery, and

 

transformer)

 

 

 

RS Cable with built-in electronics and

AQS3/4 cable or

adapters

AQS31/41 cable

 

 

 

Power supply

24 Vac ± 20%; 50/60 Hz or 24 Vdc ± 20%

 

Power consumption

2 W

 

Sensor life expectancy

>15 years

 

Maintenance interval

5 years

General

Self diagnostics

Complete power/sensor/analog outputs internal test

Status LED indication

Yellow = Maintenance required; Red = Relay activated

 

 

Power-up time

≤ 60 s

 

Ambient operating limits

 

 

- Temperature

0...50 °C

 

- Humidity

0...95% rh, non-condensing

 

Operating principle

Non-dispersive infrared (NDIR)

 

Gas sampling mode

Diffusion and 4 mm gas inlet on bottom of the wall plate

 

Response time

120 s (diffusion) or 10 s (0.2 ltr/min gas flow)

 

Measurement range

0...3000 ppm

CO2 Measurement

Converting range

0...2000 ppm = 0...10 Vdc (factory setting)

or 2...10 Vdc / 0...20 mA / 4...20 mA

 

 

 

Accuracy

±1% of measurement range, ±5% of reading

 

Pressure dependence

+1.58% of reading per kPa deviation from the normal

 

pressure of 100 kPa

 

 

 

Annual zero drift

<±1% of measurement range

 

Operating principle

Thermistor

Temperature

Measurement range

−10...60°C

 

0...50 °C = 0...10 Vdc (factory setting)

Measurement

Converting range

 

 

or 2...10 Vdc / 0...20 mA / 4...20 mA

 

Accuracy

±0.2 K

 

Settings and configuration with

 

 

Service Software AQS-USP22

 

P control

- Throttling range CO2

100...800 ppm

 

- Throttling range temperature

1...10 K

 

- Reset time adjustment range

2...500 s (factory setting: 300 s)

 

 

 

EN0B-0374GE51 R0102

2

Honeywell AQS51, AQS61 User Manual

AQS51/61 COMBINED CO2-/TEMPERATURE ROOM SENSOR/CONTROLLER

 

For connection of potential-free

Open > 40 kΩ

Digital input 1

contact

Closed < 100 Ω

Power supply 5 Vdc

 

 

 

 

Closed contact current 1 mA

 

 

Output signal

0...10 Vdc / 2...10 Vdc, impedance <100 Ω,

 

load >5 kΩ or 0...20 mA / 4...20 mA, load ≤500 Ω

 

 

 

Resolution

10 mV (10 Bits)

Analog outputs

D/A conversion accuracy

±2% of output voltage, +0.1 V

±2% of output current, ±0.3 mA

 

 

Protection

PTC fuse (auto reset), short-circuit proof

 

Customization of P controller

Both outputs can be configured to any sensor mix (CO2 +

 

temperature + digital input of 5 proportional ranges with

 

 

priorities and offsets, using STRATEGY, Version 4.0)

 

Single pole, Normally Open (NO),

1 A / 50 Vac (50 VA) or 1 A / 24 Vdc (30 W)

Digital relay output

potential-free contact.

 

Factory-adjusted switching setpoint

Relay activated: ≥1000 ppm

 

 

and differential

Relay deactivated: ≤900 ppm

Analog output or digital

Analog output signal

0...10 Vdc, impedance <100 Ω, load >5 kΩ

open collector output

Digital open collector output

Max. 0.5 A, 60 Vdc or 40 Vac (half-wave rectifier protection)

Dimensions

Housing (L x W x D)

(120 x 82 x 30) mm

 

 

By pressing the push button, one of the following display

 

 

modes on the 4-digit display is selectable:

 

 

- CO2 and temperature, alternating

 

 

- Error code

Push-button

MENU

- CO2 in ppm

 

 

- Temperature in °C

 

 

- Analog output 1

 

 

- Analog output 2

 

 

- Analog output 4

 

 

 

DIMENSIONS

Fig. 1. Dimensions (in mm)

3

EN0B-0374GE51 R0102