Honeywell 3355 User Manual

Page 1
MagicStat®/3355
Programmable Thermostat by Honeywell
OWNER’S GUIDE
Weekday/Weekend (5-day/ 2-day)
Low Voltage (20 to 30 Vac)
Thermostat and Mounting Plate
Model CT3355
1
69-1012
69-1012
Page 2
Welcome to the world of comfort and energy savings with your new Honeywell MagicStat® Programmable Thermostat.
Your new thermostat will automatically control the temperature in your home, keeping you comfortable while saving energy when pro­grammed according to the instructions in this manual.
RECYCLING THERMOST A T
If this thermostat is replacing a thermo­stat that contains mercury in a sealed tube, see Fig. 1, do thermostat in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of your old thermostat.
not
place your old
Direct any questions concerning the application of this thermostat to Honeywell Customer Assistance at 1-800-468-1502, Monday-Friday 7:00 a.m.-5:30 p.m., Central time.
If you have questions, call Honeywell Inc. at 1-800-468-1502.
Fig. 1. Typical location of a mercury switch in a thermostat.
2
MERCURY SWITCH
M3701
69-1012
Page 3
Table of Contents
Step 1: Prepare For Installation ..................................................................................................... 4
Step 2: Remove Old Thermostat ................................................................................................... 6
Step 3: Install Batteries .................................................................................................................. 8
Step 4: Program Thermostat........................................................................................................ 10
Personal Programming Chart ...................................................................................................... 12
Step 5: Adjust Fan Operation Switch, as Required ................................................................... 18
Step 6: Adjust System On-Time,
Step 7: Mount Thermostat Mounting Plate ................................................................................. 21
Step 8: Wire Thermostat Terminals............................................................................................. 23
Step 9: Mount Thermostat............................................................................................................ 27
Step 10: Check Thermostat Operation After Programming and Installing.............................. 28
Step 11: Set Fan and System Switches ..................................................................................... 30
Troubleshooting Guide................................................................................................................. 32
Limited One-Year Warranty ................................................................................. Inside Back Cover
°F/C°, as Required ................................................................. 18
3
69-1012
Page 4
Step 1: Prepare for Installation
Check Table 1 to make sure this thermostat is compatible with your system. If not, return to the
retailer. For more information, call Honeywell Customer Assistance, toll-free 1-800-468-1502.
Table 1. Compatibility Chart.
System Type Compatible With CT3355
Gas—Standing Pilot Yes Gas—Electronic Ignition Yes Gas-Fired Boilers Yes
Gas—Millivolt
Oil-Fired Boilers Yes Oil-Fired Furnace Yes Electric Furnace Yes Electric Air Conditioning Yes
Baseboard Electric (120/240 Line Volt) Heat Pumps/Multistage Equipment
Not compatible with any 120/240 volt circuit.
a
Compatible with 2-wire Honeywell Zone Valves. Isolating relay required for 3-wire thermostats for zone valves. Not compatible with 2-wire White-Rodgers no. 1361 Valves.
b
Compatible with systems.
hot water
baseboard systems. Will not work efficiently on steam or gravity
4
No
No No
a, b
a, b
69-1012
Page 5
Acquire tools and items below as needed. Also purchase two AA alkaline batteries; we recom-
mend Energizer® batteries.
CROSS-RECESSED SCREWDRIVER
HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED TO DRILL HOLES IN WALL
WIRE CUTTER/STRIPPER OR SHARP KNIFE, IF NEEDED TO STRIP WIRES
LEVEL, IF NEEDED TO LEVEL THERMOSTAT FOR APPEARANCE
MASKING TAPE, IF  NEEDED TO LABEL WIRES  AS DISCONNECTED FROM OLD THERMOSTAT
5
M878B
69-1012
Page 6
Step 2: Remove Old Thermostat
Test to make certain that your heating and
cooling systems are working properly. If either does not work, contact your local heating/air conditioning dealer. To avoid compressor damage, do not operate the cooling system when outdoor temperature is below 50°F (10°C).
TURN OFF POWER to system at the
furnace, or at the fuse/circuit breaker panel.
Carefully unpack your new thermostat and
mounting plate; save package of screws, instructions and receipt.
Remove the cover from the old thermostat.
If it does not snap off when pulled firmly from the bottom, check for a screw used to lock on the cover.
Loosen screws holding thermostat to
subbase, wallplate or wall, and lift away.
Disconnect wires from the old thermostat or
subbase. As you disconnect each wire, use masking tape to label it with the old terminal designation. If there are only two wires, they do not need to be labeled. If there is an extra wire that is not connected to your old thermostat, you will
also
not be connecting it to your new thermostat. Wrap wires as shown to keep them from falling back into the wall.
WIRES THROUGH WALL OPENING
M5136
6
69-1012
Page 7
Replacing a Clock Thermostat that has C or C1 Clock Terminals?
If you are replacing a Honeywell Chronotherm® Thermostat, you can find one or two wires that go to the C or C1 clock terminals on the Chronotherm® Thermostat wiring wallplate. Do not allow them to touch, or you may damage your transformer. Disconnect the wires and wrap them separately , using electrical tape.
wrap them together
do not interfere with the operation of the new thermostat. Record the colors and terminal designation labels of the remaining wires.
. Place the wires where they
Do not
Six or more wires?
If there are six or more wires (excluding clock wires attached to terminals), you probably have a variation of a heat pump or multistage system. The thermostat is
not
compatible with
such systems so return the product to the place of purchase. If you would like information about which programmable thermostats work with your system, call Honeywell Customer Assistance at 1-800-468-1502.
Three thermostat wires?
If you have three wires for heating only and can operate the fan using the fan ON switch, this thermostat works with your system. However, some hot water (zoned) heating systems have three thermostat wires. The thermostat does not work without installing an isolating relay on these systems. For details, call Honeywell Customer Assistance at 1-800-468-1502.
7
69-1012
Page 8
Step 3: Install Batteries
IMPORTANT
Batteries must be installed for programming and operation of the thermostat and heating/cooling system.
Purchase two AA alkaline batteries; non-
alkaline batteries do not last as long, and can leak, causing damage to the thermostat or the wall surface. We recommend Energizer® batteries.
Make sure the thermostat is set to the OFF
position.
Use a coin to remove the battery door.
Install the fresh batteries as shown, making
sure positive and negative terminals are oriented correctly.
Replace the battery door.
REMOVING  BATTERY
M1719C
As the batteries are running low, a
DOOR
bAt Lo
indicator flashes for one or two months before batteries run out completely. Replace the batteries as soon as possible after the indicator starts flashing. If you do not replace the batteries sometime while
8
bAt Lo
is flashing, the
69-1012
Page 9
indicator eventually stops flashing.
bAt Lo
stays on without flashing, indicating the
thermostat and heating/cooling system have stopped working when the batteries are almost completely dead.
After the batteries are completely dead, the
bAt Lo
indicator disappears, leaving a com-
pletely blank display.
INSTALL TWO AA ALKALINE  BATTERIES AS SHOWN
Press down on the left ends of the batteries to remove. If you insert the new batteries within 20 to 30 seconds of removing the old ones, you do not have to reprogram the thermostat. However, if the display is blank, the batteries are dead or incorrectly installed and you must reprogram. See pages 14 and 15 to reprogram.
IMPORTANT
Although the thermostat has a low battery indicator, replace the batteries once a year to prevent the thermostat and heating/cooling system from shutting down due to lack of battery power.
As a precaution, when leaving home for longer than a month, change batteries before you leave to prevent the system from shutting down due to lack of battery power.
M1713
9
69-1012
Page 10
Step 4: Program Thermostat
After the batteries are installed, the thermostat can be easily programmed in your hand, before it is installed on the wall.
If you prefer to program the thermostat after it is installed on the wall, skip to page 18, and return later to this programming section.
The following Personal Programming Chart (pages 12 and 13) can be helpful for planning your program schedule of time and tempera­ture settings for various times of the day.
Four time periods are available during week­days — WAKE, LEAVE, RETURN, and SLEEP. These periods can be seen individually on the display as you press the SET SCHEDULE key.
WAKE is the time period you want the house at a comfortable temperature when you get up and
while you get ready for work or school. When deciding what time to set for your WAKE period, include extra lead time, depending on the outside temperature and your furnace response time, to give the furnace a head start to heat the house before you get up. (This will be a higher temperature during heating season, or a lower temperature during cooling season.)
LEAVE is the time period you can set for an energy-saving temperature while you are away at work or school. (This will be a lower tem­perature during heating season, or a higher temperature during cooling season.)
RETURN is the time period you want the house at a comfortable temperature for activities before bedtime. When deciding what time to set for your RETURN period, include extra lead time, depending on the outside temperature and your furnace response time,
10
69-1012
Page 11
to give the furnace a head start to heat the house before you arrive home. (Again, this is higher heating or lower for cooling.)
SLEEP is the time period you can set for an energy-saving temperature while you are sleeping. (Again, this is lower for heating or higher for cooling. For more comfortable sleeping, some people choose not to raise the cool temperature during the night.)
You will set one schedule for weekdays and another for weekends, because your require­ments will probably be different for each. Also, during weekends, only the WAKE and SLEEP time periods are available.
Fill in the times and temperatures you desire for weekdays and weekends. If you decide not to program the thermostat, it will automatically control heating at 68°F (20°C), and cooling at 78°F (26°C), 24 hours a day. Also, you do not
need to enter a time and temperature program for all periods if your schedule does not require it. For example, a house that is occupied during weekdays would only require programs for WAKE and SLEEP.
If no program is entered for the weekends, the thermostat will operate on the weekday SLEEP program all weekend.
Before programming, remove the clear plastic overlay covering the display.
When pressing the keys, use the ball of your finger or a soft pencil eraser. Using sharp fingernails or pencil points can damage the keypad.
If you make an error at any time during programming, just press the RUN PROGRAM key, and continue again at the step where you left off.
11
69-1012
Page 12
Personal Programming Chart
Heating Program
Weekdays Start Time Heating Temperature
WAKE
1
LEAVE RETURN
1
SLEEP
Weekends
WAKE
1
SLEEP
WAKE and RETURN start times should include extra lead time based on outside temperature
1
and furnace response time, to give your furnace a head start to heat the house.
2
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).
12
69-1012
2
Page 13
Cooling Program
Weekdays Start Time Heating Temperature
WAKE
1
LEAVE RETURN
1
SLEEP
Weekends
WAKE
1
SLEEP
WAKE and RETURN start times should include extra lead time based on outside temperature
1
and furnace response time, to give your furnace a head start to heat the house.
2
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).
2
NOTE: If you decide not to program the thermostat, it automatically controls heating at 68°F
(20°C), and cooling at 78°F (26°C), 24 hours a day.
13
69-1012
Page 14
This guide can be used for programming your new thermostat. NOTE: Batteries are required for operation and programming. When inserting batteries, set
system switch to OFF. Remove the battery door (on the thermostat left side) using a coin at the bottom. Follow instructions on pages 8 and 9.
Time
Set Current Time/Day
To set the time, press and release once, then press until current time shows; to set the day,
press and release again, then press until current day shows; then press .
Set
Clock/Day
Heating Program
With system switch at HEAT, press and release once. WAKE, Mon-Fri and SET appear on
Set
Clock/Day
Time
Ahead
Back
Weekday Schedule
Ahead
Back
Run
Program
the display.
14
69-1012
Page 15
p
Time Temp
Ahead
Warmer
Press to program WAKE time and press to program WAKE temperature for
Back
Mon-Fri. Repeat sequence for LEAVE, RETURN, and SLEEP.
Weekend
Press until SAT SUN, WAKE and SET appear on the display. Press to program
Schedule
WAKE time and to program WAKE temperature for Sat-Sun. Repeat sequence for SLEEP.
Temp
Warmer
Cooler
Cooler
Time
Ahead
Back
Cooling Program
With system switch at COOL, follow the same instructions as for the Heating Program. After programming, adjust the fan and system switches, as desired. Press and release to
start the program.
Run
Program
15
69-1012
Page 16
A quick guide for operating or making changes follows:
p
NOTE: System switch must be set to Heat or Cool to perform the following.
Temp
Temporarily Change temperature
for current period only
— press ;
shows on display; canceling itself at the next scheduled change, or to cancel sooner press .
Hold a temperature indefinitely (such as when on vacation)— press , then press ; HOLD appears on the display; to cancel, press .
Check Current Temperature Setting— press . (When using TEMPORARILY CHANGE or
Run
Program
Present
Setting
Warmer
Cooler
Hold
Temp
TEMPORARY indicator
Run
Program
Temp
Warmer
Cooler
HOLD, pressing this cancels your change.)
16
69-1012
Page 17
Check Programs— press , repeatedly to view each time and temperature; then
Run
Program
press .
Run
Program
Cancel a program— press , until program to cancel shows; then press .
Weekday Schedule
Weekday Schedule
Weekend Schedule
Weekend Schedule
Clear
Check Usage — Press for length of time heat or air conditioning has been running today
Usage
since midnight; press again for yesterday’s usage, press again for cumulative; press to clear cumulative reading, if desired; then press .
Clear
Permanently Change a program—Repeat steps in Heating Program section or Cooling Program section (pages 14 through 16), as applicable.
Return to normal program or start program — press .
Run
Program
Questions?
Call Honeywell Customer Assistance 1-800-468-1502.
17
69-1012
Page 18
Step 5: Adjust Fan Operation Switch, as Required
The thermostat fan operation switch,
labeled FUEL SWITCH (see illustration on page 20) is factory-set in the F position. This is the correct setting for most systems. If
your system is an electric heat system, set the switch to E. The E setting allows the fan to turn on immediately with the heating or cooling in a system where the G terminal is connected.
Step 6: Adjust System On-Time, °F/C°, as Required
The system on-time is factory-set for a warm
air, gas or oil heating system. If you are installing it on another type of system, adjust the on-time accordingly by setting screws A and B on the back of the thermostat. Use the heating system table shown in the illustration (page 20) as a guide. Optimize the system on-time according to the type of system to
minimize room temperature swings. Setting the screw screw approximately 360° counterclockwise, or about one complete turn.
In the unlikely event that you want a longer system on-time, readjust screws A and/or B as follows:
out one turn
means turning the
18
69-1012
Page 19
First, turn in both screws completely, then adjust for system type:
• Warm Air Furnace—Set at the Hot Water setting (A—out one turn, B—leave in).
• Electric Furnace—Leave at the Warm Air Furnace setting (A—leave in, B—leave in).
IMPORTANT
When using a high efficiency furnace such as a 90% or greater AFUE (Average Fuel Utilization Efficiency) unit, adjust screw A out one turn and leave screw B in.
NOTE: This thermostat does not have a
setting for steam/gravity air. Cycles would not be long enough for accu­rate temperature control.
The thermostat is set to read the tempera-
ture in degrees Fahrenheit. If readings are desired in degrees Celsius, adjust screw C out one turn, as shown in illustration.
19
69-1012
Page 20
THERMOSTAT BACK
DISPLAY °F
C–IN
DISPLAY °C
C–OUT 1 TURN
FOR HIGH EFFICIENCY FURNACE (90%+ AFUE) ADJUST: SCREW A–OUT ONE TURN
SCREW B–IN FUEL SWITCH – F POSITION
FUEL SWITCH
F
A C
B D
E
20
ADJUST SCREWS THROUGH HOLES TO SELECT OPERATION DESIRED
HEATING SYSTEM
WARM AIR
A–IN
FURNACE
HOT WATER
A–OUT
BOILER
1 TURN
ELECTRIC 
A–IN
FURNACE
W Y G
B–IN  B–IN  B–OUT 1 TURN 
FUEL SWITCH
POSITION
F
F
E
R
Rc
M8796
69-1012
Page 21
Step 7: Mount Thermostat Mounting Plate
Position the mounting plate on the wall. Use
a level to make sure the mounting plate is level. Use a pencil to mark the two mounting holes.
Remove the mounting plate from the wall,
and drill 3/16-inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill 7/32-inch holes. Gently tap anchors (provided) into drilled holes until flush with the wall.
Reposition mounting plate over the holes,
pulling wires through the wiring opening. Loosely insert two mounting screws into the holes.
WALL
WIRES THROUGH WALL OPENING
WALL ANCHORS (2)
MOUNTING SCREWS (2)
MOUNTING PLATE
M1718
21
69-1012
Page 22
Level for appearance only; thermostat
functions properly even when not level. Tighten the mounting screws.
LEVEL
M1714A
22
69-1012
Page 23
Step 8: Wire Thermostat Terminals
NOTE: All wiring must comply with local
codes and ordinances. If unsure about household wiring procedures, call your local heating/air conditioning contractor.
Refer to masking tape labels you placed on the wires when you removed your old thermostat.
Match the letter of your old thermostat wire
with the terminal of the corresponding letter on the back of your new thermostat. Refer to illustrations on pages 25 and 26. Hold the thermostat as shown to minimize need for wire extenders. If wires are still too short, use wire connectors (purchased locally) to extend wires. See illustration for guidelines on using wire extenders.
In 5-wire installations only, be sure to
remove the factory-installed jumper connecting terminals R and Rc.
METHOD TO INCREASE WIRE LENGTH
M1715A
23
WIRE NUT SIZE FOR  TWO 18-GAUGE WIRES
WIRE  FROM WALL
6 IN. (152 MM)  OF 18-GAUGE  THERMOSTAT  WIRE. MATCH INSULATION  COLORS  OR MARK  WIRE ENDS.
69-1012
Page 24
Loosen the terminal screws and slip each
wire beneath its matching terminal. See illustration (lower right) for wire insertion technique. Securely tighten the terminals.
Plug the hole in the wall with insulation to
help prevent drafts from adversely affecting the thermostat operation.
JUMPER (FACTORY-
R
INSTALLED) REMOVE  IF 5-WIRE SYSTEM
R
5/16 in.  (8 mm) STRIP
INSERT STRAIGHT  UNDER  SCREW HEAD
c
END OF WIRE  VISIBLE HERE
WY G
M1712A
24
M3002A
69-1012
Page 25
2-WIRE HEAT-ONLY (JUMPER INTACT)
A C
B D
W Y G
JUMPER
4-WIRE HEAT/COOL (JUMPER INTACT)
A C
B D
W Y G
JUMPER
R
HEATING RELAY OR VALVE COIL
L1 (HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Rc
HEATING RELAY OR
1
M8793
VALVE COIL
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
COOLING CONTACTOR COIL
FAN RELAY
R
25
Rc
L1 (HOT)
L2
M8794
69-1012
Page 26
5-WIRE HEAT/COOL (JUMPER REMOVED)
A C
B D
W Y G
3-WIRE COOL-ONLY (JUMPER INTACT)
A C
B D
W Y G
JUMPER
R
HEATING RELAY OR VALVE COIL
COOLING
1 1
L1 (HOT)
CONTACTOR COIL
FAN RELAY
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Rc
L1 (HOT)
L2
M8795
26
R
COOLING CONTACTOR COIL
FAN RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Rc
L1 (HOT)
L2
M8792
69-1012
Page 27
Step 9: Mount Thermostat
NOTE: To remove the thermostat from the
wall, first pull out at the bottom of the thermostat, then remove the top.
A.
ENGAGE TABS AT TOP OF 
THERMOSTAT AND MOUNTING PLATE.
B.
PRESS LOWER EDGE 
OF CASE TO LATCH.
SWING OPEN COVER 
C.
TO CHECK  OPERATION.
M1734A
27
69-1012
Page 28
Step 10: Check Thermostat Operation after Programming and Installing
Heating
Do
not
check heating system operation by jumpering thermostat terminals at the primary control such as the gas valve, zone valve, or oil burner control. This damages the thermostat, instead, jumper R and W wires at the thermostat.
Auto On
Warmer
Cooler
28
HeatCool Off
Move the system switch to HEAT and the fan switch to AUTO.
Press key until the setting is about 10°F (6°C) above room tempera­ture. Heating should start and the fan should run after a short delay (immediately if fan operation switch is set in E position).
Press key until setting is about 10°F (6°C) below room temperature. The heating equipment should shut off.
69-1012
Page 29
Cooling
To avoid possible compressor damage, do not operate the cooling system when outside temperature is below 50°F (10°C). See compres­sor manufacturer instructions for further information.
NOTE: When cooling setting is
changed, thermostat may delay up to five minutes before turning on the air conditioner. This delay protects the compressor.
Auto On
Warmer
Cooler
Auto On
HeatCool Off
Move the system switch to COOL and the fan switch to AUTO.
Press key until setting is about 10°F (6°C) below room tempera­ture. The cooling equipment and fan should start.
Press key until the setting is about 10°F (6°C) above room tempera­ture. The cooling equipment and fan should stop.
HeatCool Off
Move the system switch to OFF, with the fan switch at AUTO. The system and fan should be off.
29
69-1012
Page 30
Step 11: Set Fan and System Switches
Auto On
Auto On
First set the fan switch.
FAN AUTO: Normal setting for most homes. A
single-speed fan turns on automatically with the air conditioner or furnace. A two-speed fan usually runs on high with the air conditioner and on low with the furnace. Exception: If the fan operation switch on the
back of the thermostat is set to the E position (see page 20), the fan operates only with the furnace.
FAN ON: The fan runs continuously. Use for
improved air circulation during special occa­sions or for more efficient electronic air cleaning. (In a heat-only system, fan runs continuously only if the fan relay is connected to the thermostat.)
30
69-1012
Page 31
Then set the system switch.
HeatCool Off
HeatCool Off
HeatCool Off
COOL: The thermostat controls your air
conditioning system.
OFF: Both the heating and air conditioning
systems are off.
HEAT: The thermostat controls your heating
system.
31
69-1012
Page 32
Troubleshooting Guide
If… Then… Display will not come on. Set the system switch to OFF. Remove batteries. Insert
backward for at least five seconds to reset thermostat. Replace batteries correctly. Display should come on.
Make sure batteries are fresh and installed correctly.
Gently clean battery contacts using a soft pencil eraser.
Do not use anything abrasive on the clips.
Temperature display will not go lower than 45°F (7°C) or higher than 88°F (31°C) during programming.
Temperature change occurs at the wrong times.
Heating will not come on. Check that the switch on the thermostat is set to HEAT.
You have reached the temperature setting limit. The setting range is 45°F to 88°F (7°C to 31°C).
Check the program times for the period in question. Be sure that AM and PM indications are correct. Make sure
the current day and time are correct. Reprogram if necessary.
Check the system fuse or circuit breaker and replace or reset if necessary.
Check for correct wiring and good connections.
32
69-1012
Page 33
Heating will not come on. (Continued)
Jumper wires R and W. If heat does not come on, contact your heating dealer.
If display is blank or shows
bAt Lo
, install fresh batteries.
If temperature setting is higher than current temperature, and the display shows HEAT, contact Honeywell
Customer Assistance at 1-800-468-1502.
Cooling will not come on. Check that the switch on the thermostat is set to COOL.
Check the system fuse or circuit breaker and replace or
reset if necessary.
Check for correct wiring and good connections.
Jumper wires Rc and Y. If cooling does not come on,
contact your cooling dealer.
If display is blank or shows
bAt Lo
, install fresh batteries.
The thermostat has a built-in time delay on cooling. Allow five to ten minutes after changing the setting before the
air conditioner starts.
Make sure the outdoor disconnect is energized (on).
33
69-1012
Page 34
Cooling will not come on. (Continued)
If temperature setting is lower than the current temperature, and the display shows COOL, move the
system switch from COOL to OFF for ten minutes. After ten minutes, return the switch to the COOL position. If the air conditioner comes on, compressor may have reached its high limit temperature protection and shut down. If the air conditioner does not come on after the ten minutes and the display shows COOL, contact Honeywell Customer Assistance at 1-800-468-1502.
If 2- or 4-wire installation, verify R-Rc jumper is installed.
The house is too warm or too cool. ■ Press PRESENT SETTING key to check the current
temperature setting.
If desired, change the temperature setting. See page 16.
SYSTEM ON indicator is lit, but no heat is coming from the registers.
Allow time for the furnace to heat up and the fan to come on before checking for heat at the register. (Check to
make sure system on-time is set correctly according to page 18 and 19.)
34
69-1012
Page 35
The furnace cycles too frequently or the system cycle length is too short or too long.
The thermostat's current setting does not match the display temperature to within ±1°.
Incorrect room temperature showing on thermostat display.
bAt Lo
remains on display after
fresh batteries are installed.
Readjust system on-time according to instructions on pages 18 and 19.
Check that the wiring hole in the wall behind the wallplate was plugged with insulation to prevent drafts that might
adversely affect the thermostat operation.
Be aware that it is normal for the current setting and display temperature to differ on occasion.
During recovery from setback or setup, setting and display temperatures may differ for up to 30 minutes after
recovery period.
Make sure the hole behind the thermostat is plugged with insulation to help prevent drafts from adversely affecting
the thermostat operation.
The thermostat is factory-calibrated, and cannot be adjusted.
Remove the batteries. Wait one hour. Install fresh alkaline batteries.
35
69-1012
Page 36
TYPICAL ENERGY SAVINGS FOR REPRESENTATIVE CITIES IN THE U.S. AND CANADA
Savings for Once-A-Day 10°F (5°C) decrease
30% 28% 26% 24% 22% 20% 18% 16% 14% 12% 10%
8% 6%
Approximate percentage of energy cost savings
4%
2%
Minneapolis St. Paul Montreal Ottawa Toronto
Edmonton Regina Winnipeg
Calgary
Halifax Vancouver Denver Moncton North Bay Quebec St. John's
Buffalo Cleveland Milwaukee
Savings for Twice-A-Day 10°F (5°C) decrease*
Boston
Des Moines 
Chicago
Omaha
Detroit
Salt Lake
Pittsburgh
City
Indianapolis
*Based on 10°F (5°C) decrease—(5°F [3°C] decrease gives approximately 55 percent of these savings).
Cincinnati Kansas City St. Louis Columbus
New York Philadelphia Seattle
Savings for 5°F (3°) summer increase 
Louisville
San 
Portland
Francisco
Wash., D C
36
Dallas Atlanta
Los Angeles
San Diego
M2416A
69-1012
Page 37
37
69-1012
Page 38
38
69-1012
Page 39
Limited One-Year Warranty
Honeywell warrants this product, excluding battery, to be free from defects in the workmanship or materials, under normal use and service, for a period of one (1) year from the date of purchase by the consumer. If, at any time during the warranty period, the product is defective or malfunctions, Honeywell shall repair or replace it (at Honeywell’s option) within a reasonable period of time.
If the product is defective,
(i) return it, with a bill of sale or other dated proof of purchase, to the retailer from which you purchased it, or (ii) package it carefully, along with proof of purchase (including date of purchase) and a short description of the malfunction, and mail it,
postage prepaid, to the following address:
Honeywell Inc. in Canada: Honeywell Limited/Honeywell Limitée Return Goods Department Product Services ON30 1050 Berkshire Lane 155 Gordon Baker Road Plymouth, MN 55441-4437 North York, Ontario M2H 2C9
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Honeywell that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer.
Honeywell’s sole responsibility shall be to repair or replace the product within the terms stated above. HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE ONE YEAR DURATION OF THIS WARRANTY. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. This warranty gives you specific legal rights, and you may have other rights which vary from state to state. If you have any questions concerning this warranty, please write our Customer Assistance Center, Honeywell Inc., P.O. Box 524, Minneapolis, MN 55440-0524 or call 1-800-468-1502, Monday-Friday, 7:00 a.m. to 5:30 p.m., Central time. In Canada, write Retail Products ON30, Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 2C9
39
69-1012
Page 40
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 2C9
Helping You Control Your World
69-1012 6-96 J.S. Printed in U.S.A. Copyright © 1996 Honeywell Inc. All Rights Reserved ® U.S. Registered Trademark
40
Printed on recycled paper containing at  least 10% post-consumer paper fibers.
69-1012
Loading...