WARNING: Danger of electrical shock or injury. Turn
power OFF ahead of the device before installation or modification. Do not remove circuit protective devices until the power is OFF.
Introduction
These instructions cover the installation of the sealable, clear plastic cover for Spectra circuit breakers with microEntelliGuard shown in Figure 1.
Sealing the cover in accordance with the National Electrical Code, paragraph 240-6 exception and paragraph 240-82, allows an ampere rating equal to the adjusted long-time pickup setting (current setting) and therefore permits conductors to be sized to the setting. The cover also prevents removal and changing of the rating plug.
®
TM
trip units, as
Figure 1. Sealable trip unit cover installed on a Spectra® RMS circuit breaker
Two covers are available, as illustrated in Figure 2.
• SPCOV1C is the standard cover supplied with SG
TM
and SK frame breakers with microEntelliGuard
trip units. Four holes permit access to the arrow keys for viewing selected functions and settings. The ENTER key is not accessible, so settings cannot be changed without breaking the seal and removing the cover. A hole over the test kit jack allows connection with 24 Vdc control power for viewing the trip targets on a tripped breaker.
• SPCOV3C is an optional cover for Spectra RMS SG and SK breakers. It has no holes and must be removed to access the keypad for changing settings and to connect 24 Vdc control power at the test kit jack.
Installation
Press the screw insert into the hole in the center of the trip unit. Thread the flat-head Philips screw through the hole in the cover and into the insert in the breaker. Remove the protective film on the cover and seal as shown in Figure 3.
Seals And Sealing Wire
Sealing wire must be purchased separately. Use O.050­inch [1.25 mm] maximum diameter flexible wire or zip tie. To seal a trip unit use the method shown in Figure 3.
SPCOV1C
SPCOV3C
Figure 2. Sealable cover hole patterns
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.
Figure 3. Sealing method for the microEntelliGuard