GE Energy
Industrial Solutions
GEH-706 Installation Instructions
Distribution Cable
Terminal Block
For Spectra® RMS Molded-Case Circuit Breakers
TM
with microEntelliGuard
Trip Units
For Catalog Number SDCTBA11C, SDCTBA22C
Circuit Breaker Accessory
• Neutral current sensor - black (for equipment ground
• Neutral current sensor - white (for equipment ground
Spectra® RMS Breaker with microEntelliGuardTM using
Terminal Block 22C
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• reduced energy let-through (RELT O +)
Overview
The General Electric Distribution Cable Terminal Block
is a modular attachment primarily used to provide an
alternate means of input to Spectra
Circuit Breakers with microEntelliGuard
terminal block input/output connections are as follows:
®
Spectra
Terminal Block 11C
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• reduced energy let-through (RELT O +)
• ground fault alarm (GFA O +)
• ground fault alarm/ reduced energy let-through
(RELT/GFA O –)
• reduced energy let-through (RELT I +)
• reduced energy let-through (RELT I –)
1
Neutral current sensor input is required for 3Ø /4W or 1Ø /3W systems. For 3Ø /3W systems, do not make any connections.
RMS Breaker with microEntelliGuardTM using
®
RMS Molded-Case
TM
Trip Units. The
• ground fault alarm (GFA O +)
• ground fault alarm/ reduced energy let-through
• reduced energy let-through (RELT I +)
• reduced energy let-through (RELT I –)
• Neutral current sensor - black (for equipment ground
• Neutral current sensor - white (for equipment ground
• zone select interlock (ZSI I +)
• zone select interlock (ZSI I –)
• zone select interlock (ZSI O +)
• zone select interlock (ZSI O –)
• breaker position (Aux. Switch [RED] )
• breaker position (Aux. Switch [WHITE] )
• voltage A (must be from Voltage Module or Voltage
• voltage B (must be from Voltage Module or Voltage
• voltage C (must be from Voltage Module or Voltage
1
fault)
1
fault)
(RELT/GFA O –)
1
fault)
1
fault)
Conditioner Plate or Voltage Conditioner Assembly)
Conditioner Plate or Voltage Conditioner Assembly)
Conditioner Plate or Voltage Conditioner Assembly)

GEH-706 Installation Instructions
The Distribution Cable Terminal Block is used to carry a variety of electronic signals between Spectra® RMS Molded
TM
Case Circuit Breakers with microEntelliGuard
Trip Units. These breakers are interconnected via daisy-chained
terminal blocks with common power, communication wiring, and voltage wiring (SDCTBA22C only).
TM
Figures 1 and 2 show how the Distribution Cable Terminal Block is used in a typical microEntelliGuard
system.
Figure 1. Typical microEntelliGuardTM system utilizing the 11C Distribution Cable Terminal Block.

GEH-706 Installation Instructions
Figure 2. Typical microEntelliGuardTM system utilizing the 22C Distribution Cable Terminal Block.
Figure 3 shows the individual breaker input connector pinout for the Distribution Cable Terminal Blocks.
Figure 3. End view of Distribution Cable Terminal Block cable detailing available breaker pinout connections.

GEH-706 Installation Instructions
Dimensions and Wiring Diagrams
A Distribution Cable Terminal Block dimensioned drawing is provided in Figures 4 & 5, for the SDCTBA11C
and SDCTBA22C respectively, to assist in mounting the accessory.
Figure 4. Dimensioned drawing of the Distribution Cable Terminal Block 11C (dimensions shown in inches).
Figure 5. Dimensioned drawing of the Distribution Cable Terminal Block 22C (dimensions shown in inches).

GEH-706 Installation Instructions
Figure 6 shows a point-to-point wiring diagram for a Distribution Cable Terminal
®
Block SDCTBA11C connected to a Spectra
TM
microEntelliGuard
Trip Unit. Figure 7 shows a point-to-point wiring diagram for a Distribution
Cable Terminal Block SDCTBA22C connected to a Spectra
TM
with a microEntelliGuard
Trip Unit.
RMS Molded-Case Circuit Breaker with a
®
RMS Molded-Case Circuit Breaker
NOTE: Use Terminal Block SDCTBA11 (refer back to Figures 1 and 2) to connect the SDCTBA11C
or SDCTBA22C to the Voltage Module if required.
Figure 6. Wiring connections to the Distribution Cable Terminal Block 11C.

GEH-706 Installation Instructions
Figure 7. Wiring connections to the Distribution Cable Terminal Block 22C.

GEH-706 Installation Instructions
Connections
The screw terminals on the Distribution Cable Terminal
Block are labeled by function for clarity. The terminal
strip pocket will accommodate a spade lug or ring
terminal with a tongue width up to 0.320 inches. The
terminal screw size is 10-32. To make the connection,
attach an appropriate spade lug or ring terminal to the
wire, slip the fastener beneath the terminal screw and
tighten.
The Distribution Cable Terminal Block contains a cable
with a 20-pin plug connector. To connect the end of the
®
Distribution Cable Terminal Block to a Spectra
Molded-Case Circuit Breaker with a microEntelliGuard
RMS
TM
Trip Unit, insert the breaker cable plug into the terminal
block connector until the interlocks latch into the notch
and hold the plug in place (See Figure 8).
Figure 8. Side view of breaker cable-terminal block insertion and
attachment.
Additional Information
Refer to these other user’s manuals for mpre details:
®
GEH-5934 MicroVersaTrip
PM Trip Units in Spectra
Plus and MicroVersaTrip®
®
RMS Molded-
Case Circuit Breakers
®
GEH-700 Spectra
G Breaker w/
microEntelliGuard™ Trip Unit
®
GEH-701 Spectra
K Breaker w/
microEntelliGuard™ Trip Unit
GEH-702 microEntelliGuard™ Trip Unit Users Manual
DEH-41318 Universal Rating Plug
GEH-6250 Voltage Module
GEH-6251 Power Supply Plate
GEH-6252 Voltage Conditioner Plate
GEH-6253 Power Supply Assembly
GEH-6254 Voltage Conditioner Assembly
GEH-703 MET Battery Pack Adapter
GEH-704 MET Advanced Distribution Cable
Junction Box
DEH-006 Distribution Cable Junction Box
GEH-705 MET Distribution Cable Extension (20-pin)
GEH-6256 Distribution Cable Extension (12-pin)
GEH-6255 Distribution Cable Harness (12-pin)
GEH-6257 Distribution Cable Terminal Block (11 point)
GEH-6491 POWER LEADER™ Modbus Concentrator
GEH-6502 POWER LEADER™ PMCS 5.0 Network
Architecture Guide
GEH-707 MET Sealable Cover kits
DEH-4568 GTU digital test kit (GTUTK20)
GEH-5551 Shunt Trip and UVR instructions
GEH-5593 Aux switch and bell alarm
GEK-64467 TIM-1 Zone Selective Interlock Module

Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and
microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they
provide for every possible contingency that may be met in connection with installation,
operation, or maintenance. Should further information be desired or should particular
problems arise that are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to the GE Company.
GE Energy
41 Woodford Avenue, Plainville, CT 06062
www.geelectrical.com
© 2012 General Electric Company
imagination at work