GE Industrial Solutions SDCTBA22C User Manual

GE Energy
Industrial Solutions
GEH-706 Installation Instructions
Distribution Cable Terminal Block
For Spectra® RMS Molded-Case Circuit Breakers
TM
with microEntelliGuard
Trip Units
For Catalog Number SDCTBA11C, SDCTBA22C
Circuit Breaker Accessory
• Neutral current sensor - black (for equipment ground
• Neutral current sensor - white (for equipment ground
Spectra® RMS Breaker with microEntelliGuardTM using Terminal Block 22C
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• reduced energy let-through (RELT O +)
Overview
The General Electric Distribution Cable Terminal Block is a modular attachment primarily used to provide an alternate means of input to Spectra Circuit Breakers with microEntelliGuard terminal block input/output connections are as follows:
®
Spectra Terminal Block 11C
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• reduced energy let-through (RELT O +)
• ground fault alarm (GFA O +)
• ground fault alarm/ reduced energy let-through (RELT/GFA O –)
• reduced energy let-through (RELT I +)
• reduced energy let-through (RELT I –)
1
Neutral current sensor input is required for 3Ø /4W or 1Ø /3W systems. For 3Ø /3W systems, do not make any connections.
RMS Breaker with microEntelliGuardTM using
®
RMS Molded-Case
TM
• ground fault alarm (GFA O +)
• ground fault alarm/ reduced energy let-through
• reduced energy let-through (RELT I +)
• reduced energy let-through (RELT I –)
• Neutral current sensor - black (for equipment ground
• Neutral current sensor - white (for equipment ground
• zone select interlock (ZSI I +)
• zone select interlock (ZSI I –)
• zone select interlock (ZSI O +)
• zone select interlock (ZSI O –)
• breaker position (Aux. Switch [RED] )
• breaker position (Aux. Switch [WHITE] )
• voltage A (must be from Voltage Module or Voltage
• voltage B (must be from Voltage Module or Voltage
• voltage C (must be from Voltage Module or Voltage
1
fault)
1
fault)
(RELT/GFA O –)
1
fault)
1
fault)
Conditioner Plate or Voltage Conditioner Assembly)
Conditioner Plate or Voltage Conditioner Assembly)
Conditioner Plate or Voltage Conditioner Assembly)
GEH-706 Installation Instructions
The Distribution Cable Terminal Block is used to carry a variety of electronic signals between Spectra® RMS Molded
TM
Case Circuit Breakers with microEntelliGuard
Trip Units. These breakers are interconnected via daisy-chained
terminal blocks with common power, communication wiring, and voltage wiring (SDCTBA22C only).
TM
Figures 1 and 2 show how the Distribution Cable Terminal Block is used in a typical microEntelliGuard
system.
Figure 1. Typical microEntelliGuardTM system utilizing the 11C Distribution Cable Terminal Block.
GEH-706 Installation Instructions
Figure 2. Typical microEntelliGuardTM system utilizing the 22C Distribution Cable Terminal Block.
Figure 3 shows the individual breaker input connector pinout for the Distribution Cable Terminal Blocks.
Figure 3. End view of Distribution Cable Terminal Block cable detailing available breaker pinout connections.
Loading...