INSTRUCTIONS FOR THE INSTALLER
This label below should be attached
to the inside surface of the trim or
enclosure where it will be visible.
Test each GFCI circuit breaker in this panel ONCE A
B
ON
TRIP
OFF
PUSH
TO
TEST
1) To minimize false tripping: Do not connect to swimming
pool equipment installed before adoption of the 1965
National Electrical Code.
2) 30 milliampere ground fault equipment protection circuit
breakers (yellow TEST button) are NOT intended, and
are NOT suitable, for ground fault protection of personnel
coming in contact with electrical parts. Use 5 milliampere
GFCI circuit breakers for this application.
3) 5 milliampere GFCI circuit breakers (red TEST button)
and 30 milliampere ground fault equipment protection
circuit breakers (yellow TEST button) are intended for use
on 120Vac circuits (1-pole circuit breaker) or 120/240 or
208Y/120Vac (2-pole circuit breaker), 60 Hz circuits only.
MONTH.
1) With handle (B) in “ON” position, press “PUSH TO
T” button (A).
TES
2) Handle (B) should move to “TRIP” position to
20
indicate GFCI circuit breaker has opened the circuit.
3) To restore power move handle to “OFF” position (to
reset mechanism), then to “ON”.
IMPORTANT - If handle does not move to “TRIP”
position when test button is pres
breaker protection is not operating properly and an
electrician should be IMMEDIATELY notified.
A
GENERAL g ELECTRIC
Install GFCI Circuit Breakers
on Grounded Power Supply
Circuits only
CLASS A
sed, the GFCI circuit
g
GE Industrial Systems
_______________________________
General Electric Company
41 Woodford Ave, Plainville, CT 06062
GEZ-5805 R4 1201 2001 General Electric Company
C