Warning notices are used in this publication to emphasize that hazardous voltages, currents, or
other conditions that could cause personal injury exist in this equipment or may be associated
with its use.
Warning notices are also used for situations in which inattention or lack of equipment
knowledge could cause either personal injury or damage to equipment.
Caution notices are used for situations in which equipment might be damaged if care is not
taken.
Notes call attention to information that is especially significant to understanding and operating
the equipment.
This document is based on information available at the time of its publication. While efforts
have been made to ensure accuracy, the information contained herein does not cover all details
or variations in hardware and software, nor does it provide for every possible contingency in
connection with installation, operation, and maintenance. Features may be described herein that
are not present in all hardware and software systems. GE Industrial Systems assumes no
obligation of notice to holders of this document with respect to changes subsequently made.
REFERENCES
GE Industrial Systems makes no representation or warranty, expressed, implied, or statutory,
with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or
usefulness of the information contained herein. No warrantees of merchantability or fitness for
purpose shall apply.
For details of the Modbus RTU protocol, refer to PI-MBUS-300 Rev. E from Modicon/AEG
Schneider Automation. For details of RS-485 communications, refer to the EIA-485 standard.
POWER LEADER™ is a trademark of General Electric Company.
Modbus RTU® is a registered trademark of AEG Schneider Automation.
Modbus® is a registered trademark of Modicon Inc.
Windows and Windows NT are registered trademarks of Microsoft Corporation.
Theory of Operation..................................................................................................................................................................2
Monitor operation with PMCS .............................................................................................................................................3
Control Power Connections....................................................................................................................................................10
Groups ................................................................................................................................................................................21
Communication Timeout Setting........................................................................................................................................22
Port Configuration Settings.................................................................................................................................................22
Read Files from a Monitor..................................................................................................................................................22
Write Files to a Monitor .....................................................................................................................................................24
PC to Monitor Connection......................................................................................................................................................25
Monitor Setup Menu ...............................................................................................................................................................26
Program Upgrade................................................................................................................................................................26
Set Password.......................................................................................................................................................................27
RS-485 Port Configuration.................................................................................................................................................27
Auto-Detection for SLT......................................................................................................................................................27
Set Date & Time.................................................................................................................................................................27
Main Menu...............................................................................................................................................................................29
Look at a Device.................................................................................................................................................................30
Look at the Local Event Log...............................................................................................................................................32
Notes on Password Protection.................................................................................................................................................30
Using the Modbus Monitor with PMCS ................................................................................................................................33
Step 1: Define a New Device Type..........................................................................................................................................41
Step 2: Define the Device Type as Hybrid or Generic .........................................................................................................42
Step 3: Create the Device Type’s Register Map...................................................................................................................42
Utilized Register Block List (URBL)......................................................................................................................................43
Step 4. Customize the Display.................................................................................................................................................44
Notes on Hybrid/Generic Device Types .................................................................................................................................45
Special Handling Registers.................................................................................................................................................45
Defining Hybrid and Generic Device Types.......................................................................................................................46
Defining the Register Set....................................................................................................................................................46
Message Framing and Timing.................................................................................................................................................50
Data Conventions.....................................................................................................................................................................51
Format for Floating Point and Long Integer Data Types ....................................................................................................51
APPENDIX B: MODBUS MONITOR REGISTER MAP
APPENDIX C: REGISTER DATA FORMATS SUPPORTED BY THE MODBUS MONITOR
APPENDIX D: SUPPORTED FIRMWARE REVISIONS FOR TID’S
GLOSSARY
ii
49
53
55
51
60
POWER LEADER Modbus Monitor
List of Figures and Tables
List of Figures
Figure 1. POWER LEADER Modbus Monitor. ...............................................................................................................1
Figure 6. Front view of Monitor, showing dimensions.....................................................................................................7
Figure 7. Side view of the Monitor, showing dimensions and connections.....................................................................7
Figure 9. Cutout pattern for mounting the Monitor........................................................................................................10
Figure 10. RS-485 port and RS-485 connector pinouts..................................................................................................11
Figure 13. Removing the cooling fan filter.....................................................................................................................13
Figure 14. Configuration Tool main screen....................................................................................................................16
Figure 16. New Configuration screen.............................................................................................................................17
Figure 17. Port Configuration screen..............................................................................................................................17
Figure 24. Configuration Tool Group Configuration screen..........................................................................................21
Figure 25. Add New Group screen. ................................................................................................................................21
Figure 26. Modify Groups screen...................................................................................................................................22
Figure 32. PC to Monitor RS-232 connection. ...............................................................................................................25
Figure 33. Monitor Main menu.......................................................................................................................................25
Figure 36. Monitor Main menu (details).........................................................................................................................29
Figure 38. Device Groups screen....................................................................................................................................30
Figure 40. Device Data screen........................................................................................................................................31
Figure 41. Monitor View Devices menu structure..........................................................................................................32
Table 1. Devices supported by the Monitor. ....................................................................................................................5
Table 5. Device firmware revisions supported by the Modbus Monitor........................................................................59
iv
POWER LEADER Modbus Monitor
Chapter 1
Introduction
Chapter 1 – Introduction
Overview
The GE POWER LEADER Modbus Monitor, shown in
Figure 1, is a microprocessor-based device that connects
to an industry-standard Modbus RTU network,
implemented on RS-485 wiring. The Monitor tracks
metering and status information collected by GE
POWER LEADER power management devices and a
variety of third-party power management devices. The
Monitor provides a convenient station for viewing of
data from remote devices.
Figure 1. POWER LEADER Modbus Monitor.
Modbus RTU networks are designed on a master-slave
architecture. Only one master per network is permitted.
The master queries the slaves when it needs their data,
and slave devices may only communicate on the network
in response to a request from the master.
The Monitor can operate in either of two roles. First, it is
capable of acting as a master on one or two Modbus
segments of power management devices, collecting data
from the devices for local display, as shown in Figure 4.
Second, it is capable of behaving as a “second-incommand” to GE’s Power Management Control System
(PMCS), as shown in Figure 5. In this role, the Monitor
resides on the RS-485 network with other POWER
LEADER devices, performing its monitoring duties but
behaving as a slave device to the PMCS master.
However, if the master is disabled for some reason,
perhaps a computer problem or a power failure at the
host PC, the Monitor will immediately and transparently
assume the role of master to the other devices.
NOTE: The POWER LEADER Modbus Monitor is
compatible only with GE Power Management Control
System software, version 5.1, version 6.0 or greater. It is
not certified to be compatible with any other host
software.
Once installed and wired to control power and network
connections, the Monitor must be configured for
communications (Modbus address, baud rate, etc.) on the
RS-485 network. It must also be configured with the
identity and type of the other network devices. This
configuration is performed using a software application,
the Modbus Monitor Configuration Tool, running on a
PC. When you are ready to download the configuration
to a Monitor, you’ll connect the PC to the
communications port on the Monitor’s front panel using
an RS-232 straight-through cable (provided with
Monitor).
NOTE: In this manual, the term SEGMENT or
MODBUS SEGMENT will refer to a single RS-485
communications network operating under the Modbus
protocol. A Monitor may be connected to one or two
Modbus segments, depending on whether it is a single or
dual port version.
1
POWER LEADER Modbus Monitor
Chapter 1 – Introduction
Theory of Operation
As mentioned previously, the POWER LEADER
Modbus Monitor has two modes of operation. It can
operate as a stand-alone master to one or two Modbus
segments of compatible devices or it may operate in
conjunction with the GE Power Management Control
System (PMCS) software. In this second mode, the
Monitor collects the data it needs to display and also
watches for the PMCS to go off-line. If for some reason
the Monitor does not sense the PMCS being online as
Modbus master, the Monitor will immediately and
transparently assume the role of master on the Modbus
segment(s).
We’ll explain briefly how PMCS operates, and then the
relationship of the Monitor to the PMCS, and finally the
operation of the Monitor independent of PMCS.
PMCS operation
The GE Power Management Control System consists of
four basic parts: (1) power management devices, (2) an
RS-485 network (“Modbus segment”) connecting these
devices to (3) a host computer running GE’s Power
Management Control System software and a Dynamic
Data Exchange (DDE) server, which monitors the
devices for data requested by (4) client software
programs, and feeds this data back to the clients
requesting it.
The power management devices vary in complexity and
intended use, but in general their function is similar: they
collect data on specific electrical metered, status and
event parameters (volts, amps, power consumption,
peaks, trips, etc.). The various information they monitor
is recorded in specific memory locations called registers.
Registers are organized by address. The complete list of
a devices’ registers, their addresses and their contents is
referred to as a register map.
PMCS has been preprogrammed with the register maps
of a variety of GE and third party devices. When the user
configures PMCS with the details of what devices are
connected to his network, the software automatically
associates the appropriate register map with the given
device type. This enables the software to locate
information in a device based on its type.
PMCS operates using a client-server architecture called
DDE - Dynamic Data Exchange. DDE is a means of
exchanging information between software programs
operating on a PC. Client programs request information
from a Server program; the Server program fills these
requests. In the case of the PMCS DDE Server, these
requests are for power management information being
gathered by physical power management devices on
Modbus segments connected to the PC. An example of
PMCS DDE communications is shown in Figure 2.
30&6IXOILOOV&OLHQWV
UHTXHVWFRPSOHWLQJWKH''(WUDQVDFWLRQ
30&6
6HUYHU
'HYLFHUHSOLHV
WR6HUYHUVUHTXHVWIRUGDWD
Figure 2. PMCS DDE communications cycle.
&OLHQW
''(
'HYLFH
&OLHQWLQLWLDWHV''(
WUDQVDFWLRQE\UHTXHVWLQJGDWDIURPWKH''(6HUYHU
30&6
''(
6HUYHU
6HUYHUUHTXHVWVGDWD
IURPGHYLFHRYHU56QHWZRUN
Client software such as the PMCS Event Logger or
Waveform Capture is used to analyze particular data
from devices. Each client program needs particular
pieces of data from particular devices. The client sends a
DDE request to the Server, the Server queries the
devices for the requested information, and when it has
received the information from the devices, it replies to
the client’s request with the desired information.
An important aspect of DDE is its ‘dynamic’ nature;
once a client has requested information from the Server,
a ‘DDE link’ to that data is established. The Server will
continue to monitor that information and, if any changes
occur, will forward the new data to the client.
2
Monitor operation with PMCS
POWER LEADER Modbus Monitor
Chapter 1 – Introduction
The Proxy’s role in assisting the Monitor in DDE
communications is shown in Figure 3.
The Monitor’s place in this scenario is as a backup
device to the PMCS software on the host computer, and
also as a remote monitor, enabling viewing of PMCS
device data at locations other than the host PC.
When the PMCS DDE Server is present on a network,
Monitors on the network operate as slaves to the PMCS
system acting as master. Because Modbus networks
operate on a master-slave architecture, which allows
only the master device to initiate communications, a
Monitor cannot directly request information from the
devices it needs to track. A special client application
called the Monitor Proxy provides the means for a
Modbus Monitor to obtain the data it requires from
network devices. The Proxy runs on the host PC
alongside the PMCS DDE Server.
When the Monitor Proxy application is launched, its first
task is to query the PMCS DDE Server, checking for any
Monitor devices on the segment. If Monitor devices are
found, the Proxy records their device names and then
asks the DDE Server for each Monitor’s request list
information. The Monitor’s request list is a listing of all
devices and specific data the Monitor needs to display.
The Monitors send their request lists back to the Server,
which passes this information on to the Monitor Proxy,
completing the DDE transaction.
The Proxy now knows which devices each Monitor
needs to track for data and events. The Proxy uses the
information in the Monitor’s request lists to establish
DDE links with the Server for the devices and
corresponding registers. The Server begins polling these
devices for data and sending the data back to the Proxy.
As a slave device, the Monitor cannot initiate
communications or requests for data. However, there is
nothing to prevent the Monitor from ‘eavesdropping’ on
network traffic. The Monitor watches the segment for
requests to and responses from the devices it is supposed
to track and uses this information to update its displays.
The Proxy itself has no need for the data from the
devices, since its purpose is merely to create the
conversation so that the Monitor can eavesdrop on the
reply. The Proxy discards all device data received from
the DDE Server.
Figure 3. Monitor Proxy and PMCS DDE communications.
The Proxy can also send the PMCS event log to a
Monitor when requested. The Monitor can store the
latest 50 PMCS events if the PMCS Event Logger client
is running on the host PC with the DDE Server.
Monitor stand-alone operation
To a limited degree, the Monitor functions in a manner
very similar to the PMCS DDE Server, acting as master
to a network of power management devices.
The Monitor has been preconfigured with the register
maps of a variety of GE and third-party power
management devices. The user programs the Monitor
with the Modbus addresses and device types of the
devices on the segment(s), and tells the Monitor what
information he wishes to monitor from each device. The
Monitor will query the devices for the desired data and
display it on-screen.
Multiple Modbus Monitors
Up to two Modbus Monitors are permitted on a single
segment. In compliance with the Modbus master-slave
architecture, only one device may act as master at a
given time. However, while one Monitor is acting as
master, the second Monitor is constantly checking for
the master’s presence. Should the master go off-line, the
second Monitor will immediately assume the role of
master device.
3
POWER LEADER Modbus Monitor
Chapter 1 – Introduction
Supported Devices
The Modbus Monitor supports three classes of power
management devices: tightly integrated devices, generic
devices, and hybrid devices.
Tightly integrated devices are those device types which
are predefined in the Monitor. The Monitor has a copy of
these devices’ register maps in its memory, and knows
precisely where to find any data it needs from such a
device. The register maps of tightly integrated devices
may not be changed in any way. The display screens of
tightly integrated device types are also pre-defined and
may not be changed (see hybrid devices, below, for more
information on customizing displays).
Generic devices are user-defined. The Modbus Monitor
supports any power management device with registerbased Modbus RTU communications via RS-485. To set
up a generic device, the user must manually enter the
register map (or those parts of interest) into the Modbus
Monitor via the Monitor Configuration Tool (see
Chapter 7, Advanced Configuration). In contrast to the
tightly integrated devices, whose register maps have
already been programmed into the Monitor, the Monitor
knows nothing about a generic device until the user
enters this data. Event recording and special handling
registers are not supported for generic device types.
The third type of device supported by the Monitor is the
hybrid device. This device type is derived from a tightly
integrated device, but is not as loosely defined as a
generic device. A hybrid device type’s register map and
display screens are copied from the register map of a
tightly integrated device, but they may be modified like a
generic device. This allows some flexibility to be
supported by the Monitor without giving up the
convenience of pre-defined tightly integrated devices.
The display screens of tightly integrated devices may be
customized by creating a new hybrid device type based
on the tightly integrated device type in question, and
then modifying the display portion of the device type.
Chapter 7, Advanced Configuration, discusses the
creation and configuration of generic and hybrid device
types.
The Monitor supports up to 31 device types, including
the 21 tightly-integrated devices shown in Table 1. All
tightly integrated devices are fully supported by PMCS
6.0; a sub-set (devices indicated by an asterisk) is
supported by PMCS 5.1.
4
POWER LEADER Modbus Monitor
Chapter 1 – Introduction
DeviceName as displayed on Monitor
screen
POWER LEADER EPM*PL EPMMetering
POWER LEADER Meter*PL MeterMetering
EPM 3710*EPM 3710Metering
EPM 3720*EPM 3720Metering
MULTILIN Power Quality Meter (PQM)*Multilin PQMMetering
POWER LEADER MDP Overcurrent Relay*MDP RelayProtection
Spectra MicroVersaTrip™ *Spectra MVT PMProtection
Enhanced MicroVersaTrip™ C*Enhanced MVT PM (RMS9C)Protection
Enhanced MicroVersaTrip™ D*Enhanced MVT PM (RMS9D)Protection
Spectra ECM™ Electronic Control Module*Spectra ECMProtection/Control
MULTILIN 239 Motor Protection Relay*Multilin 239Protection/Control
MULTILIN 269 Plus Motor Management Relay*Multilin 269Protection/Control
MULTILIN SR469 Motor Management Relay*Multilin 469Protection/Control
MULTILIN SR489 Generator Management Relay*Multilin 489Protection/Control
MULTILIN 565 Feeder Management Relay*Multilin 565Protection/Control
MULTILIN 735 Feeder Relay*Multilin 735Protection/Control
MULTILIN SR745 Transformer Management Relay*Multilin 745Protection/Control
MULTILIN SR750 Feeder Management Relay*Multilin 750Protection/Control
MULTILIN SR760 Feeder Management RelayMultilin 760Protection/Control
System Monitor SM-3 Voltage RegulatorSM3Protection/Control
EPM 7300PML7300Protection/Control
Function
Table 1. Devices supported by the Monitor.
5
POWER LEADER Modbus Monitor
Chapter 1 – Introduction
Typical Network Configurations
0RGEXV0RQLWRU
0RGEXV0RQLWRU
DFWLQJDVPDVWHUWR
0RGEXVVHJPHQW
(30RU
0RGEXVVHJPHQWFRQQHFWV56QDWLYHGHYLFHV
MULT ILIN
)(('(50$1$*(0(175(/$<
565
0XOWLOLQ
DFWLQJDVVODYHZLOODVVXPHUROHRI
PDVWHULI0RQLWRUJRHVRIIOLQH
0LFUR9HUVD7ULS
WULSXQLWV
3720 ACM
32:(5/($'(5
0RGEXV&RQFHQWUDWRU
32:(5/($'(5
0HWHU
&RPPQHWVHJPHQWVWR32:(5/($'(5&RPPQHWGHYLFHV
Figure 4. Monitor acting as master to a network of POWER LEADER devices.
Figure 6 and Figure 7 show the dimensions of the
Monitor. The important features of the Monitor are listed
below:
• The Monitor’s front panel display is used for viewing
device data and event messages during operation, for
diagnostics purposes, and for some very limited
configuration capabilities.
• The keypad is located directly beneath the display. Ten
keys are used for navigating the menus of the Monitor.
LQ
32:(5/($'(5
0RGEXV0RQLWRU
POWER LEADER Modbus Monitor
Chapter 1 – Introduction
• A set of three terminals for AC or DC control power
input are provided on the side of the case.
• A grounding screw is provided above the control power
connection.
• Two five-terminal connectors on the side of the case
provide daisychained RS-485 input and output
connections to one or two Modbus segments.
• The on/off switch for the Monitor is located on the side of
the case above the RS-485 connectors.
32:(5/($'(5
0RGEXV0RQLWRU
70
LQ
LQ
LQ
',63/$<
Figure 6. Front view of Monitor, showing dimensions.
NH\PHPEUDQHNH\SDG
563RUW
0RGEXV6HJPHQW
LQ
127(
1RWWRVFDOH
,1287,1287
%
0RGEXV6HJPHQW
$
66
*5281'
&RQWURO3RZHU,QSXW
+1*1'
LQ
&RPPXQLFDWLRQV
)URQW
LQ
Figure 7. Side view of the Monitor, showing dimensions and
connections.
7
POWER LEADER Modbus Monitor
Chapter 1 – Introduction
Specifications
The specifications of the Modbus Monitor are listed in
Table 2.
ParameterValue
Control power100–240 Vac, 50, 60 Hz;
125–250 Vdc;
30 W min
Current draw for fusingUse 1.5A – 3.0A slow-blow fuse
Modbus communications Two RS-485 ports, 1200 baud, 2400 baud, 4800
Device types supportedThe Monitor supports up to 32 device types,
Devices per Modbus
segment
Compatible Modbus RTU
Host Software
Bare wire, AWG #12–24
CSA: C22.2 No. 14, File No. LR-77871-25
including the 21 Tightly Integrated Device types
and the Modbus Monitor device type itself.
Per the Modbus standard, up to 32 total ‘drops’
(devices) per segment,
applicable) PMCS host.
Up to 215 commnet devices may be supported via
Modbus Concentrators.
See GEH-6502,
Guide
, for details.
GE Industrial Systems
Power Management Control System, version 5.1 or
greater
including
Monitors and (if
PMCS Network Architecture
Environmental
The environmental requirements of the Monitor are
listed in Table 3.
ParameterValue
Operating temperature0° C to +65° C
Storage temperature–20° C to +80° C
Relative humidity5% to 95% noncondensing
Environmental exposureNEMA 12
Vibration response and
Two versions of the Monitor are available: a single RS485 port version and a dual RS-485 port version. Catalog
numbers for each version are shown in Table 4.
DescriptionCatalog Number
Monitor, single RS-485 portPLMNTR1
Monitor, dual RS-485 portPLMNTR2
Table 4. Monitor catalog numbers.
Table 2. Monitor specifications.
8
Chapter 2
Installation
The installation of a Monitor is straightforward and
relatively simple. The device is mounted in an
appropriate cutout in switchgear or a panelboard, control
power and grounding connections are made, and the RS485 connections to one or two Modbus segments are
made. Software necessary to configure the Monitor must
be installed on a PC. Finally, if the Monitor is to be used
as part of a PMCS system, a special client software
package called the Modbus Monitor Proxy must be
installed on the host PC where PMCS runs. This chapter
presents the instructions for each of these procedures.
Valid Network Architectures
There are only four permissible network architectures
with which the Modbus Monitor may be used. Select the
architecture appropriate for the network you have
designed. Refer to GEH-6502, the POWER LEADERPMCS Network Architecture Guide for information on
designing RS-485 networks. These are shown in Figure
8, below.
0RGEXV
6HJPHQW$
0RGEXV
6HJPHQW$
([DPSOH%
0RGEXV
6HJPHQW%
0RQLWRU
([DPSOH'
0RGEXV
6HJPHQW%
0RQLWRU
0RQLWRU
([DPSOH$
0RGEXV
6HJPHQW$
0RQLWRU
([DPSOH&
0RGEXV
6HJPHQW$
0RQLWRU
0RQLWRU
POWER LEADER Modbus Monitor
Chapter 2 – Installation
DUAL PORT MONITOR USERS:
DO NOT CONNECT THE MONITOR’S TWO RS-485
PORTS TO THE SAME MODBUS SEGMENT. This
will cause communications errors and misoperation of
the Monitor.
Example A shows a single Modbus Monitor wired to a
single Modbus segment. Example B shows the same
monitor in a dual-port version, wired to two different
Modbus segments.
Examples C and D illustrate fully loaded Modbus
segments - no more than 2 Monitors are permitted on a
given Modbus segment.
Example C illustrates a pair of Monitors connected to a
single Modbus segment. In this example, the Monitors
may be either single port or dual-port versions, provided
both are the same. You may not mix single-port and
dual-port Monitors on a Modbus segment (see note
below.)
Example D shows the same pair of Monitors wired to a
second Modbus segment.
IMPORTANT: With regard to Example C (two Monitors
on a single RS-485 segment) it is NOT permissible to
mix different models of Monitors on a segment.
Monitors #1 and #2 MUST be of the same model, either
both single-port or both dual-port.
The nature of the other network architectures makes this
concern irrelevant for examples A, B and D, since in
Example A you could have either a single or a dual port
Monitor, and in Examples B and D, you may only use a
dual-port monitor(s).
WARNING: Any other wiring of the Modbus Monitor
may result in incorrect operation and errors.
Mounting
The hole pattern for mounting the Monitor in switchgear
is shown in Figure 9. Insert the Monitor through the
mounting hole, being careful to line up the six faceplate
studs with the six holes drilled in the panel. From the
9
POWER LEADER Modbus Monitor
Chapter 2 – Installation
back of the panel, apply the lock washers and mounting
nuts (included with the Monitor) to the studs. Hand
tighten them with a small wrench.
Be sure to allow clearance behind the unit so that the fan
can operate effectively and along the bottom of the unit
where the ventilation vents are located. A minimum of
0.25 inch must be allowed.
GLD
LQ
LQ
LQ
NOTE: Failure to properly connect earth ground to
the Monitor may result in inconsistent or noisy
network communications.
WARNING: Failure to properly connect earth
ground may result in voltages hazardous to
personnel and equipment being present at the
Monitor enclosure.
RS-485 Connection(s)
LQ
LQ
LQ
Figure 9. Cutout pattern for mounting the Monitor.
Control Power Connections
Control power connections are made on the side of the
case. The connectors are labeled H+, N-, and GND. The
appropriate power cable terminations are spade lugs on
AWG #12–18 wire. See Table 2 for control power
voltage ranges. Hand-tighten connection screws with a
Phillips head screwdriver.
On the side of the Monitor case are two five-pin
connectors labeled Modbus Segment A and Modbus
Segment B.
NOTE:
Both connectors are present and labeled
regardless of whether the individual Monitor is a single
or dual port version. In the single port version, the
Segment B connector is disabled.
Mating connectors (one for each segment) are included
with the Monitor for customer connection. The pinout
for assembling the mating connector is shown in Figure
10. If the Monitor is to be the first or last device on the
RS-485 network, it must be terminated using the
enclosed terminating resistor. Place the resistor between
the appropriate + and - connections on the mating
connector. (See below for details on RS-485
termination).
Grounding
The Monitor chassis should be connected to earth
ground for personnel safety reasons. Connect earth
ground to the green-colored grounding screw on the side
of the Monitor enclosure. Earth ground connection
requires #14 AWG or thicker wire and a ring or spade
lug.
10
POWER LEADER Modbus Monitor
Chapter 2 – Installation
When the assembly is complete, plug the connector into
port labeled Segment A on the side of the Monitor, as
shown in Figure 10.
,1
6KLHOG
,Q
2XW
287
Figure 10. RS-485 port and RS-485 connector pinouts.
The connectors labeled
should be wired to the cable
IN
coming from the host (or previous device), or should be
terminated if the Monitor is the first device on the
Modbus segment. The
RS-485 IN
connector of the next Modbus device, or
connectors are wired to the
OUT
terminated if the Monitor is the final device on the
Modbus segment. Please study and follow the RS-485
grounding considerations and termination rules below to
ensure the correct operation of your Modbus segments.
If the Monitor is to be connected to a second Modbus
segment, follow the procedures outline above to wire the
connector, and plug it into the port labeled
Segment B
on the side of the Monitor. Note that
Modbus
termination considerations are independent for each
segment; i.e., the Monitor may need to be terminated for
one or both RS-485 segments, or for neither, if it is
positioned in the middle of the segment(s).
Figure 11 illustrates appropriate termination of an RS485 segment at the Modbus Monitor
Per the EIA485 standard, every RS-485 network must be
terminated at both ends. If the Modbus Monitor is the
first device, place the supplied 120-ohm, 1/2-watt
resistor between the + and - connectors of the
port. If the Modbus Monitor is the last device, place the
supplied 120-ohm, 1/2-watt resistor between the + and connectors of the
RS-485 OUT
port.
RS-485 IN
11
POWER LEADER Modbus Monitor
Chapter 2 – Installation
RS-485 Grounding Considerations
Figure 12 illustrates correct wiring for communications
and shield grounding. By following this example, a
secure grounding point will be provided for each device
on the network. Any surge will dissipate locally without
being carried up or down the network to other devices,
thus minimizing the chance for damage to devices due to
surge or EMI.
PD\EHDQ56FDUG5656FRQYHUWHU
1HWZRUN&RQQHFWLRQV6KLHOG
0RGEXV
0RGEXV
*1'
0RGEXV0RQLWRUVKLHOGFRQQHFWHGWR*1'VFUHZRQ
0RQLWRUFDVH
0RGEXV+RVW
DQ(WKHUQHW*DWHZD\56SRUWRU
DQRWKHU0RGEXV0RQLWRU
56
56'HYLFH
6KLHOG
56'HYLFH
0RGEXV0RQLWRU
LQ
6KLHOG
RXW
6KLHOGWR
GRZQVWUHDP
GHYLFHV
FRQQHFWHGDW
0RGEXV0RQLWRU
56SRUW
RKPZDWWWHUPLQDWLQJUHVLVWRU
7ZRZLUHWZLVWHGVKLHOGHGSDLUFDEOH
6KLHOGIURPKRVW
QRWFRQQHFWHG
6KLHOGIURPKRVWRUSUHYLRXVGHYLFHQRWFRQQHFWHG
The RS-485 shield is attached to ground at the host. The
shield is not connected to the RS-485 IN port of the next
device, but is connected to the RS-485 OUT port and to
a grounding screw if the shield terminal of the RS-485
port is not directly grounded. This procedure provides an
isolated ground for each device.
IMPORTANT: The Modbus Monitor’s shield terminal is
not directly grounded. If you wish to connect the RS-485
shield to ground at the Monitor, you must also make a
connection from the shield terminal to the grounding
screw on the Monitor’s case. Use AWG #12-14 wire for
this connection.
Software Installation
Modbus Monitor Configuration Tool
Configuration of the Monitor requires a Windows-based
software program, the Modbus Monitor Configuration
Tool. This program is included with the Modbus
Monitor, on several 3.5” high density floppy disks. This
section describes installation of this software onto a PC.
A laptop PC’s portability lends itself well to this use if
configurations are to be downloaded to Monitors already
installed in the likely facility-floor setting. However, it is
acceptable to create configuration files on a desktop PC
and then copy the files to a laptop for transportation to
the Monitor’s location.
The Configuration Tool requires a 486 or better PC
running Windows 3.1x, at least 8 megabytes of RAM,
and a floppy drive for installing the Configuration Tool
from the floppy disk. A minimum of 15 megabytes of
hard disk space is required to install the Configuration
Tool. A mouse is recommended for ease of use, but not
required.
To install the Monitor Configuration Tool on the
selected PC:
56'HYLFH
6KLHOG
RKPZDWWWHUPLQDWLQJUHVLVWRU
6KLHOGIURPKRVWRUSUHYLRXVGHYLFHQRWFRQQHFWHG
Figure 12. RS-485 network wiring.
1. Power up the PC and launch Windows. Start the
Windows Program Manager.
2. Insert the Monitor Configuration Tool disk
labeled “DISK 1”.
3. Select Run from the Program Manager’s File
Menu.
4. Enter A:\setup.exe and press return.
12
POWER LEADER Modbus Monitor
Chapter 2 – Installation
A new program group with the name Modbus Monitor
Configuration Tool will be created. In it will be a
README file and the Configuration Tool application.
Double-click on the application’s icon to launch the
Configuration Tool.
Modbus Monitor Proxy
For the Modbus Monitor to function in slave mode in a
PMCS system, the Modbus Monitor Proxy client
program must be installed on the host PC where the
PMCS DDE Server is running. Complete the PMCS
installation, then perform the Proxy installation as
described below. The Modbus Monitor Proxy program is
included with the Modbus Monitor on 3.5” high density
floppy disk(s).
NOTE: PMCS requires the Windows NT 4.0 operating
system, therefore the Modbus Monitor Proxy also
requires NT 4.0.
To install the Modbus Monitor Proxy:
Maintenance
The Modbus Monitor requires very little operational
maintenance due to its heavy-duty industrial
construction. However, it is recommended that the
cooling fan filter be cleaned periodically to prevent
unnecessary heat buildup inside the Monitor case.
To clean the fan filter, remove the plastic gasket from
the rear of the Monitor case, then remove the fan filter
itself, as shown in Figure 13. Gently vacuum or shake
the filter to remove any accumulated dust or debris, or
blow the debris off using a can of compressed air.
Replace the filter and gasket when cleaning is complete.
1. Log in to Windows NT on the host PC.
2. Insert the Modbus Monitor Proxy disk labeled
Disk 1.
3. Select Run from the Windows NT Start menu.
4. Enter A:\SETUP and hit return.
Follow the on-screen instructions. The installer will
prompt you to select a directory to install the Proxy in.
The default is C:\Monitor.
You will be prompted to locate the PMCS DDE Server’s
.ini file. This file is usually located in the WINNT\
directory and will have the name GE32MODB.ini or
GE32ENET.ini.
If you’re using the PMCS Event Logger client program,
you’ll also be asked to locate the directory where the
Event Logger database file is located. The file name is
EventLog.mdb and is usually located in the directory
GE_PMCS\EventLog\ .
To use the Proxy, launch the application from the Start
menu. You’ll find an icon for the program named GE
Modbus Monitor Proxy. Launching the Proxy
application automatically starts the PMCS DDE Server.
Figure 13. Removing the cooling fan filter.
13
POWER LEADER Modbus Monitor
Chapter 2 – Installation
(This page left blank intentionally.)
14
POWER LEADER Modbus Monitor
Chapter 3
Configuration
Chapter 3 – Configuration
After installing the Modbus Monitor, some initial
configuration is required to set up the Monitor for
communications. Communications settings such as baud
rate, parity, and Modbus address must be set to
correspond with the network’s settings.
Once the Monitor has been successfully configured for
network communications, it must also be configured for
its task: monitoring the other devices on the network. To
successfully monitor other devices on the Modbus
segment(s), a Monitor must know the Modbus addresses
and device types of all the devices on the segment(s).
These configuration tasks require the use of the Modbus
Monitor Configuration Tool, a Windows-based software
program included with the Modbus Monitor.
The Modbus Monitor Configuration Tool is used to
create a “profile” of the Monitor, consisting of all the
different configurable attributes, such as
communications settings, information on devices
connected to the Modbus segment(s), the register maps
for these devices, etc.
Once the desired profile has been established, it can be
downloaded to the Monitor via the RS-232 port on the
Monitor’s front panel. When a new profile has been
downloaded to the Monitor, the old profile will be
replaced and the new profile will take effect.
This chapter will cover using the Configuration Tool to
create a profile for the Monitor and how to download the
profile to the Monitor. Later in the chapter, we’ll discuss
what other configuration options are available from the
Monitor’s display/keypad, not requiring the
Configuration Tool.
Modbus Monitor Configuration Tool
First, launch the Monitor Configuration Tool from the
Windows Program Manager. The Modbus Monitor
Configuration Tool main window will appear (Figure
14).
There are three pulldown menus available from the main
screen of the Configuration Tool. The first, File, offers
standard options to create a new database of Monitor
configurations, open an existing database, or create a
new database by Saving the current database As… under
a new file name. Within one database, you may have
many Monitor configurations. This allows you to group
configurations by project or customer; for instance, you
might have a file called Customer_A and within that file,
there might be configurations named Plant 1 Monitor 1,
Plant 1 Monitor 2, Paint Shop Monitor, etc.
The Configuration pulldown menu offers access to the
Print dialog box (discussed later in this chapter) and the
View dialog box, which permits you to create, modify or
delete configurations within a database. The View dialog
box is shown in Figure 15.
The third pulldown menu, Help, offers the standard
Contents item, which accesses the Configuration Tool’s
HELP table of contents, and the About dialog, which
gives information about the version of the Configuration
Tool you are using.
15
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.