GE Industrial Solutions Power Break II Undervoltage Release 480 - 600 Vac User Manual

g
GEH–6520A
Power Break® II Circuit Breaker Accessories
Undervoltage Release 480 & 600 Vac
Introduction
The Undervoltage Release (UVR) accessory, shown in Figure 1, can be installed in 800–4000 ampere frame Power Break® II circuit breakers. This accessory trips the circuit breaker when the input control voltage drops to 35–60% of its rated value and prevents an open breaker from closing until the input control voltage is greater than 8 0% of the rated value.
In addition to providing a trip signal to the breaker, the UVR accessory can be set up to interact with other Power Break II accessories, when used with a MicroVersaTrip Plus™ or MicroVersaTrip PM™ Trip Unit. DIP switches on the rear of the breaker Trip Unit can configure the UVR accessory to activate a Bell Alarm–Alarm Only accessory or a Bell Alarm with Lockout accessory when a UVR trip occurs. The Accessory Configuration section below describes how this can be done. If the breaker is equipped with a Power+™ Trip Unit, it is configured so that only protection trips will activate a Bell Alarm–Alarm Only or Bell Alarm with Lockout.
The catalog numbers for the UVR for 480 and 600 Vac applications are listed in Table 1. Voltage and current ratings in Table 1 are given at the input of the transformer. The voltage and current ratings at the input of the UVR accessory are equal to that of the SPUV120AC accessory. Input voltage is 120 Vac, peak inrush current is 3 A, and the nominal RMS current is 80 mA.
Operation
Apply control voltage to the primary of the s upplied step-down transformer. The secondary of the transformer is connected to terminals 29 and 3 0 of the terminal strip on the right side of the breaker.
Figure 1. Undervoltage Release.
Catalog
Number
SPUV480AC 480 Vac 750 20
SPUV600AC 600 Vac 600 16
Rated for 50/60 Hz. Rating is 120 Vac without step-down transformer.
Peak inrush current is present for 2–6 ms after activation. This number is provided so that fuses and supplies can be chosen appropriately.
Table 1. Catalog numbers and voltages for the Undervoltage Release.
Voltage
Rating
Current, mA
Peak Inrush
Nominal RMS
Current, mA
Installation
WARNING: Before installing any accessories, turn the breaker
OFF, disconnect it from all voltage sources, and discharge the charging springs.
WARNING: 480 Vac and 600 Vac Undervoltage Release accessories must be used with the supplied step-down transformer.
AVERTISSEMENT: Les modules de déclenchement à manque de tension 480 Vac et 600 Vac doivent être utilisés avec le transformateur abaisseur de tension qui est fourni.
When the applied control voltage is above 80% of the UVR’s rated value, the breaker can be closed. When the voltage drops to 35–60% of the rated value, the UVR will trip the breaker.
AVERTISSEMENT: Avant d’installer toute accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation, et décharger les ressorts d’armement.
The Undervoltage Release is installed in the access ory compartment through the front of the circuit breaker in the position shown in Figure 2.
Use the following procedure to install the UVR accessory into the UVR slot in the accessory compartment of the circuit breaker:
1. Open the hinged door over the ac cessory compartment and Trip Unit.
2. To remove an existing accessory, loosen the accessory locking screw and pull the accessory out with the Rating Plug Removal Tool (catalog number TRTOOL).
Figure 2. Accessory compartment on front of circuit breaker, with
Undervoltage Release slot indicated.
3. Insert the UVR accessory into the proper slot, as illustrated in Figure 3. The UVR accessory is keyed for the correct slot in the accessory compartment. I f the accessory cannot be fully seated in the compartmen t, check that the compartment position is correct.
Catalog Number/
Control Voltage
9T58K0042 / 480 V H1, H4 X1, X2
9T58K0062 / 600 V H1, H4 X1, X3
A jumper must be placed from H2 to H3.
Primary
Connections
Secondary
Connections
Table 2. Primary and secondary connections for step-down
transformers.
8. Connect the secondary side of the transformer, marked as the X-numbered terminals, to terminals 29 and 30 of the terminal block on the right side of the breaker. Table 2 lists the correct transformer secondary taps.
WARNING: 480 Vac and 600 Vac Undervoltage Release accessories must be used with the supplied step-down transformer.
AVERTISSEMENT: Les modules de déclenchement à manque de tension 480 Vac et 600 Vac doivent être utilisés avec le transformateur abaisseur de tension qui est fourni.
9. Test the UVR to ensure proper operation, according to the procedures below.
10. Reconnect power to the circuit breaker and any other accessories.
11. Close and lock or seal the door over the accessory compartment and Trip Unit to prevent unauthorized changes to Trip Unit settings and to keep contaminants out of empty accessory slots.
Figure 3. Inserting the Undervoltage Release into the accessory
compartment.
4. Tighten the locking screw on the front of the accessory until it is snug (torque of 9 in-lb.)
CAUTION: Overtightening the locking screw may damage or distort the case of the accessory.
ATTENTION: Le serrage excessif de la vis de verrouillage peut déformer le boîtier d’accessoire.
5. If the breaker is equipped with a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit, the UV R accessory can be configured to activate installed Bell Alarm–Alarm Only or Bell Alarm with Lockout accessories when a UVR trip occurs, with the procedure described in the Accessory Configuration section.
6. Mount the supplied step-down transformer near the circuit breaker.
7. Connect the control wiring for the UVR to the primary side of the transformer, marked as the H-numbered terminals. Table 2 lists the correct transformer primary taps.
Accessory Configuration
This section only applies if Bell Alarm–Alarm Only or Bell Alarm with Lockout accessories are installed in the breaker, along with a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit. If the breaker is equipped with a Power+ Trip Unit, the factory default settings, listed in Table 3, can not be changed.
The UVR accessory can be configured to activate the Bell Alarm–Alarm Only or Bell Alarm with Lockout accessories if a UVR trip occurs. The configuration can be changed by removing the Trip Unit from the brea ker, setting the DIP switches on the rear of the Trip Unit, and reinstalling the Trip Unit. Figure 4 illustrates the Trip Unit read DIP switches and their functions. Table 3 lists the switch functions and the factory settings for each.
Figure 4. Accessory switch on the rear of the MicroVersaTrip Plus™ or
MicroVersaTrip PM™ Trip Unit, showing the factory settings (solid
part indicates that the switch is pushed in on that side).
Loading...
+ 2 hidden pages