For I-T-E
K-1600 Low-Voltage Power Circuit
Breakers
INTRODUCTION
GE Conversion Kits are designed for upgrading existing
I-T-E low-voltage power circuit breakers, rather than
replacing the entire breaker. The Conversion Kits include
ProTrip™ Trip Units, the latest technological advance in
GE trip systems.
ProTrip Conversion Kits are designed and tested to
conform to ANSI Standard C37.59, allowing the retrofitter
to properly install the kit and acceptance test the breaker.
This publication covers installation of ProTrip Conversion
Kits on I-T-E® Types K-225, K-600, K-800, and K-1600
low-voltage power circuit breakers. Each Conversion Kit
contains all the components needed to convert from the
existing I-T-E electromechanical trip system.
®
Types K-225, K-600, K-800,
TABLE OF CONTENTS
SECTION 1. GENERAL INFORMATION............................................................................................................4
SECTION 2. BEFORE INSTALLATION..............................................................................................................4
Nuisance Tripping on Ground Fault-Equipped Breakers.........................................................21
2
LIST OF FIGURES
1. Removing the insulated housing on a K-225, K-600, or K-800 breaker. .........................................................5
2. Trip unit housing removed, 225–800 A breaker s............................................................................................. 5
3. Drilling out the screws holding the trip units to the housing, 225–800 A breakers..........................................6
4. Bolts to be removed from the load stabs, 225–800 A breakers.......................................................................6
5. Removing the draw-out contact block on a K-1600 breaker............................................................................6
6. Removing the trip unit housings on a K-1600 breaker.....................................................................................7
7. Contact arm connections, 1600 A breaker.......................................................................................................7
8. Electromechanical trip unit disassembly, 1600 A breaker...............................................................................7
9. Trip unit housing, 1600 A breaker....................................................................................................................8
10. Installing shims on red frame 225–800 A breakers. ........................................................................................9
11. Copper load terminal installed, 225–800 A breakers....................................................................................... 9
12. Installing a CT assembly., 225–800 A breakers. .............................................................................................9
13. Converted trip unit housing, 225–800 A breakers............................................................................................9
14. Installed CT assemblies, 225–800 A breakers. ............................................................................................. 10
15. Tightening the CT assembly bolts, 225–800 A breakers...............................................................................10
16. Terminal assembly for K-1600 red frame breaker. ........................................................................................ 11
17. CT assembly for K-1600 red frame breaker...................................................................................................11
18. C-shaped barrier modification, 1600 A breakers. .......................................................................................... 12
19. Reassembled 1600 A breaker........................................................................................................................12
20. Terminal assembly, 1600 A black frame breakers......................................................................................... 13
21. CT assembly, 1600 A black frame breakers..................................................................................................13
22. Flux shifter installation, 225–800 A breakers.................................................................................................14
23. Flux shifter installation, 1600 A breakers. ......................................................................................................14
26. Removing the top cover screws.....................................................................................................................16
27. Trip unit bracket and insulating barrier assembly.......................................................................................... 16
28. Trip unit bracket attached to the breaker. ......................................................................................................16
29. Attaching the trip unit to the mounting plate...................................................................................................17
30. Harness connector attached to the trip unit. ..................................................................................................17
31. Trip unit mounted on the breaker...................................................................................................................17
32. Optional trip unit mounting position................................................................................................................17
33. Trip unit wiring harness installation................................................................................................................ 18
34. Neutral sensor outline for K-225 and K-600 breakers...................................................................................19
35. Neutral sensor outline for K-800 and K-1600 breakers.................................................................................20
36. Cabling diagram for ProTrip™ trip units with ground fault on four-wire loads...............................................23
3
SECTION 1. GENERAL INFORMATION
SECTION 2. BEFORE INSTALLATION
GE Conversion Kit installation is straightforward, but
does require careful workmanship and attention to these
instructions. Familiarity with the breaker is highly
desirable. The general approach is to first remove the
existing trip devices from the breaker, then install the
ProTrip components. Following this procedure, the
converted breaker is performance tested before it is
returned to service.
The majority of trip unit kit installations do not require any
customized assembly work. However, some conversions
may involve unusual mounting conditions or accessory
combinations that require minor modifications and/or
relocation of components. In most instances, this
supplementary work can be done on site.
In preparation for the conversion, the installer should
verify that the appropriate current sensors and trip unit
have been furnished. Note that all ProTrip trip units
supplied with conversion kits are equipped with longtime, short-time, instantaneous, and defeatable ground
fault (LSIGX) trip functions. The installer should be aware
of how these functions will affect his application before
installing the conversion kit.
Whenever a ProTrip kit is installed on a breaker with a
four-wire system, an associated neutral sensor (CT) is
required for separate mounting in the equipment. Ensure
that retrofitted breakers are applied within their shortcircuit ratings.
As a service-related consideration, the installation of a
ProTrip kit provides an excellent opportunity to perform
normal maintenance on the breaker, particularly when
the front and back frames are separated. Such
procedures are described in the installation and
maintenance manuals supplied with the breaker and
equipment.
Before starting any work, turn off and lock out all power
sources leading to the breaker, both primary and
secondary. Remove the breaker to a clean, well-lighted
work area.
WARNING: Low-voltage power circuit breakers use
high-speed, stored-energy spring operating
mechanisms. The breakers and their enclosures
contain interlocks and safety features intended to
provide safe, proper operating sequences. For
maximum personnel protection during installation,
operation, and maintenance of these breakers, the
following procedures must be followed. Failure to follow
these procedures may result in personal injury or
property damage.
• Only qualified persons, as defined in the National
Electrical Code, who are familiar with the installation
and maintenance of low-voltage power circuit
breakers and switchgear assemblies, should
perform any work on these breakers.
• Completely read and understand all instructions
before attempting any breaker installation,
operation, maintenance, or modification.
• Turn off and lock out the power source feeding the
breaker before attempting any installation,
maintenance, or modification. Follow all lock-out
and tag-out rules of the National Electrical Code and
all other applicable codes.
• Do not work on a closed breaker or a breaker with
the closing springs charged. Trip an OPEN breaker
and be sure the stored-energy springs are
discharged, thus removing the possibility that the
breaker may trip OPEN or the closing springs
discharge and cause injury.
• Trip the breaker OPEN, then remove the breaker to
a well-lighted work area before beginning work.
• Do not perform any maintenance that includes
breaker charging, closing, tripping, or any other
function that could cause significant movement of a
draw-out breaker while it is on the draw-out
extension rails.
• Do not leave the breaker in an intermediate position
in the switchgear compartment. Always leave it in
the CONNECTED, TEST, or DISCONNECTED
position. Failure to do so could lead to improper
positioning of the breaker and flashback.
4
SECTION 3. DISASSEMBLING THE
BREAKER
I-T-E K series breaker frames need not be separated
front and back for installation of the Conversion Kit. The
general procedure is to remove and disassemble the trip
unit housing, then install the kit.
First, remove the breaker to a clean, well-lighted work
bench and place it in the upright position, so that both the
front and back are easily accessible.
I-T-E 225–800 Ampere Breakers
The electromechanical trip units are contained in a
common, insulated housing, as shown in Figure 1. Use
the following procedure to remove the trip units.
1. Remove the five Philips-head screws holding the trip
unit housing in place at the rear of the breaker. Save
the hardware for later reinstallation.
NOTE: On some I-T-E breakers, the load-side draw-out
fingers must also be removed.
2. Remove and discard the two Philips-head screws
mounting the trip unit to the contact arm on each
phase, as shown in Figure 1.
3. Remove the trip unit housing assembly from the rear
of the breaker, as shown in Figure 2.
Figure 2. Trip unit housing removed, 225–800 A
breakers.
Figure 1. Removing the insulated housing on a K-225, K-
600, or K-800 breaker.
5
4. Carefully drill out the four #10-32 screws on each
phase that hold the trip units to the housing, as
shown in Figure 3.
3
-16 x 2" bolt, nut, and lock
5. Remove and save the
/8
washer holding the trip unit to the bus on each
phase, as shown in Figure 4. The trip units can be
removed and discarded. The breaker is now ready
for conversion.
I-T-E 1600 Ampere Breakers
On I-T-E 1600 ampere breakers, each electromechanical
trip unit is contained in its own housing.
1. On draw-out breakers with electrical operators,
remove the four screws holding the draw-out contact
block assembly to the back frame, as shown in
Figure 5. Lift off the contact block assembly. Save
the hardware for later reinstallation.
2. Remove the two top and two bottom Philips-head
screws at the breaker rear holding each insulated trip
unit housing to the breaker frame, as shown in Figure
6. Save the hardware for later reinstallation.
NOTE: On some I-T-E breakers, the load-side draw-out
fingers must also be removed.
Figure 4. Bolts to be removed from the load stabs, 225–
800 A breakers.
Figure 3. Drilling out the screws holding the trip units to
the housing, 225–800 A breakers.
Figure 5. Removing the draw-out contact block on a K-
1600 breaker.
6
Figure 6. Removing the trip unit housings on a K-1600
breaker.
3. Remove and discard the four Philips-head screws
above the load terminals that connect each trip unit
to the contact arm, as shown in Figure 7. The trip unit
assemblies can be removed by pulling them out of
the rear of the breaker frame.
4. Carefully drill out the four #10-32 screws holding
each trip unit in its housing, as shown in Figure 8.
5. Remove and save the two Philips-head screws that
hold the copper terminal extensions beneath the load
terminals of each trip unit housing, as shown in
Figure 8.
6. Remove and discard the hardware holding each
copper load terminal to the metal mounting brackets.
Separate each trip unit from its housing. Discard the
trip units and save the insulated housing and
mounting brackets, shown in Figure 9.
Figure 7. Contact arm connections, 1600 A breaker.
Figure 8. Electromechanical trip unit disassembly, 1600
A breaker.
7
Figure 9. Trip unit housing, 1600 A breaker.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.