GE Industrial Solutions EntelliGuard TU Conversion kits User Manual

DEH–3456
g
For I-T-E Low Voltage Power Circuit breaker types:
For Allis Chalmers Low Voltage Power Circuit breaker types:
Entelliguard TU Conversion kits
AK, AKT, AKS, AKU, AKJ, AKR, AKRU, AKRT, AKJT, AKW
K, KA, KB, KC, KD, KE
LA Gold, LA Blue
For Westinghouse Low Voltage Power Circuit breaker types:
DB, DS
Supplementary Instructions Only
This publication must be read in conjunction with the installation instructions for
MicroVersaTrip
1
Plus and PM Conversion kits for GE Low Voltage Power Circuit Breaker of
respective type.
Introduction
GE conversion kits are designed to upgrade existing GE Low Voltage Power Circuit Breakers, rather then replacing the entire breaker. The conversion kits contain enhanced solid state Entelliguard TU, representing the latest technological advancements in GE trip systems.
This supplementary publication covers specific instructions for the installation of Entelliguard TU with advanced optional features like RELT (Reduced energy let through mode), Ground Fault Alarm etc. in GE Low Voltage Power Circuit Breakers. This supplementary publication does not detail all aspects of the conversion kit installation process.
The EntelliGuard TU trip unit provides an optional second, user-adjustable, RELT Instantaneous trip. This trip provides an alternate Instantaneous setting that allows a user to temporarily set a circuit breaker to a more sensitive pickup to provide better protection, only when better protection is needed and some selectivity may be sacrificed.
RELT Instantaneous pickup can be enabled via application of 24Vdc or Vac at the RELT input terminals or serial communications via the Modbus communication port. The RELT input command may be wired to a manual switch, automatic sensor or, via external logic, to one or more signal sources. When the EntelliGuard TU trip unit has the RELT Instantaneous pickup enabled, the trip unit provides a feedback signal via an optically isolated dry contact and serial communication. This provides positive feedback that the trip unit has received and reacted to the RELT Enable command. RELT harness consists of four wires for this input and output signal
The EntelliGuard TU trip unit’s RELT capability provides the ultimate in user flexibility for wiring and controlling an alternate Instantaneous setting for temporary use to reduce personnel hazard.
The RELT switch may be connected to a manually operated two-position switch, a remote sensor, or both simultaneously. The EntelliGuard TU trip unit provides a feedback capability directly from the trip so the user is able to verify that the signal was received by the trip unit and the settings have changed. Optionally, an indicating light may also be connected to the source of control power so the user knows if control power is available to change the setting. The trip unit does not require its own control power to accept a RELT input and change the Instantaneous trip pickup according to the user settings. However, if control power is available to the trip unit, the feedback signal will function immediately, rather than when the trip unit becomes self-powered through its load current (Fig. 1).
2
Figure 1
Section 2 in this instruction manual explains the process of upgrading the LV power Circuit Breaker from MVT (Microversatrip Plus and PM) to Entelliguard TU with RELT. Sections 3 to 7 have the process of routing the “RELT wire harness” in different types of GE circuit breaker as supplemental to base instruction manual.
3
TABLE OF CONTENTS
Page
SECTION 1 Prior To Installation…………………………………………………..……………………………….4
SECTION 2 Installation instructions for “RELT wire harness kit” GTURHA.……………….5
SECTION 3 Supplement to GEH – 5965…………….…………………………………………………………..8
SECTION 4 Supplement to GEH – 5966…………….…………………………………………………………..10
SECTION 5 Supplement to GEH – 5967…………….…………………………………………………………..12
SECTION 6 Supplement to GEH – 5964…………….…………………………………………………………..14
SECTION 7 Supplement to GEH – 6466…………….…………………………………………………………..16
SECTION 8 Supplement to DEH-40008 & DEH-40009..………………………………………………..19
SECTION 9 Supplement to GEH-6293, GEH-6294, GEH-6295, GEH-6433, DEH-40019 &
DEH-133..…………………………………………………………………………………………………....21
SECTION 10 Supplement to GEH-6318, GEH-6319, GEH-6320 & DEH-023.………………....23
4
SECTION 1 Prior To Installation
1. Before starting any work, turn off and lock out all power sources leading to the breaker, both primary and secondary. Remove the breaker to a clean, well-lighted work area.
WARNING: Low-voltage power circuit breakers use high-speed, stored-energy spring operating mechanisms. The breakers and their enclosures contain interlocks and safety features intended to provide safe, proper operating sequences. For maximum personnel protection during installation, operation, and maintenance of these breakers, the following procedures must be followed. Failure to follow these procedures may result in personal injury or property damage.
2. Only qualified persons, as defined in the National Electrical Code, who are familiar with the installation and maintenance of low-voltage power circuit breakers and switchgear assem­blies, should perform any work on these breakers.
3. Completely read and understand all instructions before attempting any breaker installation, operation, maintenance, or modification.
4. Turn off and lock out the power source feeding the breaker before attempting any installation, maintenance, or modification. Follow all lock-out and tag-out rules of the National Electrical Code and all other applicable codes.
5. Do not work on a closed breaker or a breaker with the closing springs charged. Trip the breaker OPEN and be sure the stored-energy springs are discharged, thus eliminating the possibility that the breaker may trip open or the closing springs discharge and cause injury.
6. Trip the breaker OPEN, then remove the breaker to a well-lighted work area before beginning work.
7. Do not perform any maintenance that includes breaker charging, closing, tripping, or any other function that could cause significant movement of a draw-out breaker while it is on the draw-out extension rails.
8. Do not leave the breaker in an intermediate position in the switchgear compartment. Always leave it in the CONNECTED, TEST, or DISCONNECTED position. Failure to do so could lead to improper positioning of the breaker and flashback.
5
SECTION 2 Installation instructions for “RELT wire harness kit” (Catalogue Number – GTURHA)
For GE type AK, AKT, AKS, AKU, AKJ, AKR, AKRU, AKRT, AKJT, AKW Low Voltage Power Circuit Breakers.
Installing the RELT wire harness
1. Remove the existing MVT trip unit from breaker by pressing the lever on side of trip unit mounting plate and gently pull the trip unit toward yourself as facing the breaker,.
Figure 2
2. Loosen the three screws with screwdriver as shown in figure 3. Save the screws, washer and nut for mounting back the plate later.
Figure 3
3. Rotate the mounting plate from frame, being careful not to pull on existing wires.
Figure 4
6
Wire
Slot in 36
connect
Functio
35 24 V DC
+
White
36
2
4 V DC
-
4. Take the “RELT wire harness” (4 wire harness) provided with kit and insert the pins at the end of wire to respective terminal on 36-pin connector.
Individual wires in harness are color coded and numbered. The pins should be inserted at correct places on backside of 36-pin connector. Refer figure 7 and table 1.
Table 1
Figure 5
Wire Colour
Red 4 Input +
Yellow 2 Input -
Black 30 Output +
White 27 Output -
Slot in 36 pin
connector
Function
5. The control power supply voltage to trip unit shall be given through wires 1 and 2 of communication harness already installed in breaker or supplied.
In case when communication wire harness is not installed on the breaker, use the power supply harness (2 wire harness) supplied with the kit.
Individual wires in power supply harness are color coded
and numbered. The pins should be inserted at correct places on backside of 36-pin connector. Refer table 2.
Table 2
Black
Figure 6
Figure 7
Figure 8
7
6. Tie these extra four wires (or 6 wires) with other wires at back of 36-pin connector properly. Inspect the 36-pin connector from front side of plate for extra four connectors installed.
7 Take the earlier removed sets of screws, washers and
nuts.
Figure 9
Install the mounting plate again on frame by tightening the screws at three locations.
Figure 10
9. Route the RELT & power supply wire harnesses as instructed in following section 2 to section 6 depends on breaker type.
8
Loading...
+ 16 hidden pages