GE Industrial Solutions EntelliGuard G Undervoltage Release User Manual

Introduction Undervoltage Release:
A device designed to open the breaker contacts and to prevent the breaker from closing when in a ‘No volt’ condition. On a de-energization the Undervoltage release activates the circuit breaker mechanism and ensures a rapid disconnection of the main contacts and the device prevents the Power Circuit Breaker from closing. The EntelliGuard G™ Undervoltage release is designed to react within a pre-defined Voltage band, only reacting when the voltage supply drops below the limits of this band. To prevent nuisance tripping due to short power interruptions or ‘Brown Outs’ the device has a built in delay of 50 Milliseconds when Voltage is at or below 50% of rated Voltage. Two under voltage Releases can be mounted in each Power Circuit Breaker.
Table 1.
Catalog No DC Voltage AC Voltage GUVT024DR 24V GUVT030DR 30V GUVT048R 48V 48V GUVT060DR 60-72V GUVT120R 110-130V 120-130V GUVT208AR 208V GUVT240R 220-240V 220-240V GUVT277R 250V 250-277V
DEH-41410 Installation Instructions
EntelliGuard ® G Circuit Breaker Accessories
Undervoltage Release
WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
AVERTISSEMENT: Avant d’installer tout accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement
For an External Time Delay Module (1-3 second delay) refer to Pub DEH-41406
Inrush Power: 350VA Steady state : 40VA
Use the following procedure to install the Undervoltage Device accessory into the circuit breaker.
1. Verify that the rating on the Undervoltage Device identification plate matches the voltage rating required for the application, as listed in Table 1.
2. Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background. If installing in a draw-out type breaker remove breaker from adaptor (cassette) before continuing.
3. Loosen the 6 screws on front cover (fascia) using a posidrive screw driver as shown in Fig 1.B Rotate the charging handle down and slide the front cover over the handle to remove the front cover as shown in Fig. 1.C.
1
hooks into the mechanism top support plate as shown in the Fig. 3.
Figure 1. (A) Front Cover (B) Screw Removal (C) Handle Rotation
4. This accessory is mounted on the mechanism.
nd
Top plate at 2
or 4th location as shown in Fig. 2.
Figure 3. Insert top plate
6. Tilt the device backwards until the rear hooks engage in the slots on the mechanism top support plate as shown in the Fig. 4
Figure 4. Snap on.
7. After installing the UV on the mechanism top plate, connect the input wire assembly plug to the
nd
A7/A8 if installed (2
location) or A12/A13 (4th location) marked on the secondary disconnect as shown in Fig. 5.
Figure 2.
5. Tilt the coil forward and engage the front
2
Loading...
+ 2 hidden pages