GE Industrial Solutions EntelliGuard G Shunt Trip (Extended Range) User Manual

Introduction Shunt Trip (Extended Range):
A device designed to switch the Power Circuit Breaker OFF remotely. When energized a Shunt Release instantaneously activates the circuit breaker mechanism ensuring a rapid disconnection of the main contacts. Shunt trips are suitable for a continuous power supply and are designed to be used as a closure prevention device when energized. Two Shunt trips can be mounted in each Power Circuit Breaker. The device is available as factory mounted component or as a field mountable device. It is an easy-to-fit, clip-on unit, with simple plug-in connectors to the Secondary Disconnect Block.

Table 1.Catalog Numbers and Ratings

DC
Catalog No.
Voltage AC Voltage

GSTG024R 24V

GSTG048R 48V 48V
GSTG072R 70-72V
GSTG120R 110-125V 120-127V
GSTG208AR 208V
GSTG240R 220V 240V
GSTG250DR 250V
EntelliGuard ® G Circuit Breaker Accessories
Shunt Trip (Extended Range)
DEH-41411 Installation Instructions
WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
AVERTISSEMENT: Avant d’installer tout accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement
Inrush Power: 480VA Steady state : 50VA
Use the following procedure to install the Shunt Trip accessory into the circuit breaker.
1. Verify that the rating on the Shunt Trip Mechanism identification plate matches the voltage rating required for the application, as listed in Table 1.
2. Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background. If installing in a draw-out type breaker remove breaker from adaptor (cassette) before continuing.
3. Loosen the 6 screws on front cover (fascia) using a posidrive screw driver as shown in Fig 1.B Rotate the charging handle down and slide the front cover over the handle to remove the front cover as shown in Fig. 1.C
1
rear hooks engage in the slots on the mechanism top support plate as shown in the Fig. 4
Figure 1. (A) Front Cover (B) Screw Removal (C) Handle Rotation
4. This accessory is mounted on the mechanism top plate at 1st or 4th location as shown in Fig.
2.
Figure 2.
5. Tilt the coil forward and engage the front hooks into the mechanism top support plate as shown in the Fig. 3. Tilt the device backwards until the
Figure 3. Shunt Trip inserting.
Figure 4. Shunt Trip assembly
6. After installing the shunt release on the mechanism top plate, connect the input wire assembly plug to the A5/A6 if installed (1st Location) or A12/A13 (4th Location) Locations marked on the secondary disconnect as shown in Fig. 5.
2
Loading...
+ 2 hidden pages