GE Industrial Solutions EntelliGuard G Mechanical Operations Counter User Manual

Introduction Mechanical Operations Counter:
A simple and easy to install mechanical device that displays an accurate and cumulative record of the number of closing operation of the EntelliGuard® G Power Circuit Breaker in which it is installed. Note: this device does not have a reset function.

Catalog No. Description GMCNR Mechanical Operations Counter

DEH-41416 Installation Instructions
EntelliGuard ® G Circuit Breaker Accessories

Mechanical Operations Counter

Use the following procedure to install the Operations Counter accessory into the circuit breaker.
1. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background. If installing in a draw-out type breaker remove breaker from adaptor (cassette) before continuing.
2. Loosen the 6 screws on front cover (fascia) using a posidrive screw driver as shown in Fig 1.B Rotate the charging handle down and slide the front cover over the handle to remove the front cover as shown in Fig. 1.C.
Figure 1. (A) Front Cover (B) Screw Removal (C) Handle Rotation
WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
AVERTISSEMENT: Avant d’installer tout accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement
1
3. Position the mechanical operations counter (Fig
2.) over the two holes provided inside the mechanism bracket, ensuring the indicator face is aligned to show through the window in the cover.
C
B
A
Figure 4. Operations Counter Location A) Spring charging link B) Operating arm C) Operations Counter
6. To Reinstall the cover, rotate the charging
handle down and slide the front cover over the handle to assemble the front cover to housing as shown in Fig. 5.
Figure 2.
4. Mount in position using the screws provided and apply torque 2.5-3Nm (1.84-2.21 ft-lbs).
Figure 3.
5. Ensure the operating arm (B) on the counter rides over the spring charging link (A) of the circuit breaker mechanism (Fig.4).
Figure 5.
7. Ensure the fascia is aligned properly with the trip unit and the pad lock features of the breaker.
. Fasten the 6 mounting screws of fascia with
8 the housing using a pozidrive screwdriver. Apply torque of 6 Nm (4.42 ft-lbs).