GE Industrial Solutions E9000 User Manual

imagination at work
GE Energy
Industrial Solutions
Evolution Series E9000 Motor Control Centers
Installation & Maintenance Guide DEH-40472 Rev. 05
Evolution Series E9000 Installation & Maintenance Guide
Contents
Warnings, Cautions & Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General Description – Vertical Section Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General Description – Motor Control Center Buses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Description – Motor Control Center Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Receiving, Handling & Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation of Bottom Entry Conduits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Preparation of Flooring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Positioning and Joining Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Bus Splicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Bus Splice Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
NEC Work Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation of Top Entry Conduits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Equipment Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Main Incoming Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Individual Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wiring NEMA Type A Motor Control Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring NEMA Type B Motor Control Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring NEMA Type C Motor Control Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring Between Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation of Motor Control Center Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Removal of Draw-out Motor Control Center Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Operating Handles, Door Interlocks and Padlocking Provisions . . . . . . . . . . . . . . . . . . . . . . . 14
Operating Handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Pilot Bracket and Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
NEMA 3R Outdoor Enclosure Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Preparing for Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Initial Operation of the Motor Control Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Door Closing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5. Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Equipment Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Control Power Fusing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Suggested Maintenance Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Replacing or Adding Breaker Accessories to Plug-in E or F Frame Circuit Breaker . . . . . 21
Replacing a Control Power Transformer Mounted Under Disconnect . . . . . . . . . . . . . . . . . 21
Replace a Compact Starter (1/2 X) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Suggested Lifts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Publications Available from GE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Renewal Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Ordering Additional or Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Other Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6. Overload Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Heaters for Ther-Mag Circuit Breaker Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Heaters for Mag-Break Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Heaters for Fused Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heaters for Size 6 and 7 Fused Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Electronic Overload for Circuit Breaker and Fused Controllers . . . . . . . . . . . . . . . . . . . . . . . . 33
DEH–40472
Warnings, Cautions & Notes As Used In This Publication
WARNINGS
Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other condi­tions that could cause personal injury are present in this equipment or may be associated with its use.
Warning notices are also used for situations in which inattention or lack of equipment knowledge could cause either personal injury or damage to equipment.
CAUTIONS
Caution notices are used for situations in which equipment might be damaged if care is not taken.
NOTES
Notes call attention to information that is especially significant to understanding and operating the equipment.
This document is based on information available at the time of its publication. While efforts have been made to ensure accuracy, the information contained herein does not cover all details or variations in hardware and software, nor does it provide for every possible contingency in connection with installation, operation, and maintenance. Features may be described herein that are not present in all hardware and software systems. GE Energy assumes no obligation of notice to holders of this document with respect to changes subsequently made.
GE Energy makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warrantees of merchantability or fitness for purpose shall apply.
© Copyright 2010 General Electric Company All Rights Reserved
Evolution Series E9000 Installation & Maintenance Guide
Chapter 1 – Introduction
This publication provides guidelines for installation and maintenance of Evolution Motor Control Centers, as shown in Figure 1. The information provided does not cover all details or variations in this product offering, nor does it address all possible contingencies to be met in connection with installation, operation, or main­tenance. Should further information be desired, contact GE Field Service Administration:
Call GE–RESOLve 1-888-437-3765
Refer to the GE requisition number found on the front of the equipment when calling for assistance.
Disconnect equipment from all electrical services before performing any installation or maintenance work.
For additional information, including safety considera­tions for personnel working on this product, see NEMA Standard Publication No. ICS 2.3, Instructions on the
Handling, Installation, Operation, and Maintenance of Motor Control Centers.
General Description – Vertical Section Enclosures
Each Evolution MCC vertical section is assembled with two full-side sheets having openings near the top and bottom for lateral busing and wiring between sections. Multiple sections are joined together at the factory in three-section (maximum) shipping splits. Each shipping split is provided with continuous floor sills and a lifting angle. Floor sills and lifting angles are field removable. Each shipping split includes a continuous non-removable main horizontal bus. Main bus splice bars are provided within each shipping split for field connecting main busses. Refer to motor control center outline drawings furnished by the General Electric Company for location of shipping splits within each motor control center lineup.
Vertical sections are normally provided with a top (12" high) horizontal wireway and a bottom (6" high) horizontal wireway. Each vertical section is also provided with a vertical (4" wide) wireway. Hinged doors are provided over horizontal and vertical wireways. (These doors can be removed by extracting the hinge pins inside the doors.)
To open the external doors, rotate the latches 90° counter-clockwise until the screwdriver slots are vertical.
Secure Open
Because of the great variety of motor controller assemblies and components provided within industrial motor control centers and to satisfy floor-space limitations at installation sites, a large variety of vertical section dimensions are provided, as follows:
• Section Height: 90”, 78”, 66” etc.
• Section Width: 20”, 24”, 30” etc.
• Section Depth: 13”, 20”, 22” or deeper for large assemblies.
Refer to motor control center drawings furnished by GE before performing any field-installation work.
Figure 1. Evolution Series three-section lineup.
Evolution Series E9000 Installation & Maintenance Guide
General Description – Motor Control Center Buses
The main horizontal power bus is located at the top of the vertical section. The bus bolted joints are accessible from the front by loosening the barrier mounting screws and sliding the Lexan the main bus. Figure 2 shows a horizontal power bus with its Lexan barrier. Figure 3 shows the bus barrier mounting slots and screw.
The vertical bus, either 300A or 600/850 A, is connected with two bolts per phase to the main bus. The phase relationship is A–B–C from top to bottom and left to right, as viewed from the front.
A continuous horizontal ground bus, sized in accordance with the National Electrical Code, is provided near the bottom of all motor control centers.
A optional vertical ground bus can be provided in each section providing additional grounding. A neutral bus is provided, when specified, in the bottom of the incoming section or in the bottom of all enclosure(s) as specified.
®
bus barrier up and forward from
General Description – Control Center Units
Consult Publication DET-291 for detailed listings of Evolution MCC units.
Plug-in units are supplied with stabs rated at either 250 A or 600 A. Units above 600 A may be fixed (bolt­ed) in place and are either bus or cable connected.
Installation and operation of units are described else­where in this guide.
Figure 2. Horizontal bus with Lexan barrier
Loosen screw, lift and pull barrier forward
Figure 3. Horizontal bus barrier mounting slot and screw
Evolution Series E9000 Installation & Maintenance Guide
Chapter 2 – Receiving, Handling & Storage
Receiving
Before leaving the factory, the motor control center is given a final mechanical and electrical inspection and is packed in accordance with the best practices for electrical equipment.
On receipt of any apparatus, make an immediate inspection for any damage or loss of equipment in transit. Should damage or missing material be noted, file a claim immediately with the carrier and notify the nearest office of the General Electric Company. Information such as a description of the damage, the shipping crate numbers, the requisition numbers and the panel catalog number should accompany the claim.
Handling
Control center sections are always shipped in an upright position, in single or group sections. Sections must be maintained in an upright position during all handling.
Never attempt to jack, lift, or move the equipment at points other than the lifting angle or floor sills. Use two or more chains or cables to distribute the weight evenly. Pinch bars, pipe rollers or slings are useful implements for handling equipment; but be careful to maintain distributed loading and to always apply leverage at the floor sills and/or lifting angle. Figures 4 and 5 illustrate typical handling techniques.
Figure 5. Positioning the MCC with rollers
Storage
If it is necessary to store the equipment for any length of time, be sure to observe the following precautions:
• Uncrate the equipment.
• Store the equipment in a clean, dry, humidity-controlled
area at moderate temperature. Cover with a suitable canvas or heavy-duty plastic cover to prevent entrance of foreign material.
• If equipment must be stored in cool or high humidity
areas, in addition to completely covering the equipment, provide a heat source to prevent condensation of moisture in the equipment . Energize space heaters (if furnished in the equipment) or place a standard 120­volt lamp rated at 75 watts inside the bottom of each vertical section.
Figure 4. Using standard lifting angles to hoist the MCC
Evolution Series E9000 Installation & Maintenance Guide
Chapter 3 – Installation
Before any installation work is begun, consult all drawings furnished by the General Electric Company as well as all applicable contract drawings for the particular installation. Pay particular attention to the location of units in the motor control center and their relations to existing or planned conduits and busways.
Installation of Bottom Entry Conduits
Conduits can be stubbed in after the location of the motor control center lineup has been established. Conduit should be stubbed approximately 2 inches (51mm) above the finished floor line. Figure 6 and Figure 7 show the conduit entrance space available at the bottom of standard sections. Exceptions to this available space rule are indicated on drawings furnished by GE for specific installations. Center the conduit beneath the section vertical wireway to facilitate direct cable entry. Note: Bottom rear entrance should only be used with full rear accessibility.
Figure 6C. Bottom conduit entrance for standard 20-inch deep section, low bus position, 6-inch bottom cover.
Figure 6A. Bottom conduit entrance details for standard 13-inch deep section, low bus position.
Figure 6B. Bottom conduit entrance details for standard 13-inch deep section, bus upper position.
Figure 6D. Bottom conduit entrance details for standard 20-inch deep section, bus upper position.
Figure 7A. Low bus position of ground and neutral bus (minimum available space for conduit entry) in 13-inch deep section, 6-inch cover.
Figure 7B. Standard position of ground and neutral bus with 12-inch cover compartment at the bottom of MCC.
Evolution Series E9000 Installation & Maintenance Guide
The overall height of the equipment should be considered with respect to headroom, top conduit entry space and alignment with other equipment.
Surface under motor control center base must be of non-combustible material unless bottom covers are installed in each vertical section.
Figure 7C. Low bus position of ground and neutral bus (minimum available space for conduit entry) in 13-inch deep section, 6-inch cover.
Figure 7D. Upper position of ground and neutral bus (maximum space available for conduit entry), 6-inch bottom cover.
Preparation of Flooring
For most installations, the MCC floor sills can rest on the finished floor. The foundation for the equipment should be level and even. Although not normally required, the purchaser may elect to install, level and grout the steel members or MCC floor sills in the floor, as illustrated in Figure 8 and Figure 9. If the floor sills are removed, lifting and moving the shipping sections must be done carefully.
If anchor bolts are to be imbedded in the foundation, they must be located according to the drawings furnished by GE for the specific equipment. For 13-inch (330.2 mm) deep vertical sections, anchor bolts or some form of external bracing is required. Anchor bolts should be 1/2-inch diameter of Grade 2 steel (minimum).
If there are vertical sections of varying depths (such as 13, 20, or 22 inches) in a single lineup, the fronts of the sections must be lined up for proper alignment of the main bus bars. Figure 9 illustrates this point.
Figure 8. Control center floor sills grouted to the floor before installation to provide a level foundation
Note: Cannot be rolled (as in Figure 5) without floor sills
Figure 9. Installing steel floor members
Note the front alignment of the 13-inch-deep section
Positioning and Joining Sections
If groups of sections are to be joined together in a final lineup, remove the end cover plates and the plug buttons, from the sides of the sections to be joined. Figure 10 shows the side views, with the end cover plates removed, for 20-inch-deep sections with 2-inch (50.8 mm) and 4-inch (101.6 mm) bus bars.
Carefully check and remove dirt, dust or bits of packing material from the interior of all sections. Use a brush, soft cloth or vacuum cleaner.
Evolution Series E9000 Installation & Maintenance Guide
Do not use compressed air to clean the equipment if it contains moisture. Remove all hardware pack­ages, drawings and other items shipped with the equipment. Check all nuts, bolts, and electrical joints for tightness.
All cables entering the bottoms of sections should be pulled through conduits to a point where they will be accessible after the equipment is in place. Sections can be moved to their final position and properly leveled.
Figure 11. Horizontal bus with Lexan barrier
Figure 10. Side view of a 20-inch-deep section showing the cover
plates, plug bottoms and joining points
Bus Splicing
Main, neutral and ground bus splice bars (with all asso­ciated hardware) are furnished, as necessary, to join sections together. They are located in the first section to the right of the joint. See Figures 13, 14 and 15 for approxi­mate dimensions for main, neutral, and ground bus.
Remove the top Lexan barrier, as shown in Figure 11 and Figure 12, to access the main bus. Refer to instruction drawings in splice kit. See Table 2.
Loosen screw, lift and pull barrier forward
Figure 12. Horizontal bus barrier mounting slot and screw
Table 1. Torque values for various bolt sizes and joint types.
Bolt Size
5/16-18 5–9 7–12 6.5–9 9–12 3/8-16 12–16 16–22 10–15 14–20 1/2-13 30–39 41–53 25–35 34–47 5/8-11 65–80 88–108 35–45 47–61 3/4-10 125–150 169–203 50–75 68–102
Note: When assembling or connecting to aluminum bus, apply a suitable joint compound between the contacting surfaces.
Copper Joints Aluminum Joints
lb-ft N-m lb-ft N-m
Evolution Series E9000 Installation & Maintenance Guide
Bus Splice Kits
Table 2. Bus Splice Kits
Splicing From / To E9000/E9000
Main Bus Splice
Amps
Assembly Kit
Standard Splicing
600 110C1735G1SM 1 1/4 x 2 65K 110C1258TG1 800 110C1735G4SM 1 3/8 x 2 65K 110C1256TG1 1200 110C1735G7SM 1 1/2 x 2 100K 110C1253TG1
1600/
110C1735G12SM 2 1/2 x 2 100K 110C1263TG1
2000 2500 110C1735G13SM 2 1/2 x 2 100K 110C1785TG1
N3R and Spacer Shells
600 110C1735G14SM 1 1/4 x 2 65K 110C1258TG1 800 110C1735G15SM 1 3/8 x 2 65K 110C1256TG1 1200 110C1735G16SM 1 1/2 x 2 100K 110C1253TG1 1600/
110C1735G17SM 2 1/2 x 2 100K 110C1263TG1
2000 2500 110C1735G13SM 2 1/2 x 2 100K 110C1263TG1
*Included in kits. Note: Standard plating is tin. Refer to factory for alternate plating.
Bars/ Phase Copper
Size (in.) (thick x width)
SC Rating 600V Max. (sym. amps)
Splice Instruction Drawing*
as illustrated. Note that for Condition 3, where there is an enclosure on opposite sides of the working space, the clearance for only one working space is required.
Figure 14. General Working Clearance Requirements
Installation of Top Entry Conduits
NEC Work Space
NEC Work Space is defined in Table 110.26(a) Working Spaces. Included in these clearance requirements is the
step-back distance from the face of the equipment. Table 110.26(a) provides requirements for clearances away from the equipment, based on the circuit voltage to ground, and whether there are grounded or unground­ed objects in the step-back space, or if there are exposed live parts across from each other. The voltages to ground consist of two groups: 0 to 150 and 151 to 600, inclusive. Remember, where an ungrounded system is utilized, the voltage to ground will be the greatest voltage between the given conductor and any other conductor of the circuit. For example, the voltage to ground for a 480­volt ungrounded delta system is 480 volts.
See Figure 14 for general working clearance requirements. Distances are measured from the live parts if the live parts are exposed, or from the enclosure front if live parts are enclosed. If any assemblies, such as switch­boards or motor control centers, are accessible from the back and expose live parts, the working clearance dimensions would be required at the rear of the equipment,
After the motor control center is in place and leveled, and the sections are joined together, conduits can be brought into the tops of sections as required. Figure 15 and Figure 16 show the conduit entry space available at the tops of standard sections. Refer to drawings furnished by GE for deviations on specific installations. Note: Top rear entrance should only be used with full rear accessibility.
Always remove top cover plates when drilling holes. This prevents small metal chips from falling into the panel and cause serious damage.
Figure 15. Top conduit entry space for 13-inch sections
Evolution Series E9000 Installation & Maintenance Guide
Figure 17. Typical top entry of main cables to the incoming-line lug
Figure 16. Top conduit entry space for 20-inch and 22-inch sections
Table 3. Dimensions for Figures 15 and 16
Width Dimension A Dimension B
20" 20" 17.56" 24" 24" 21.56" 30" 30" 27.56"
compartment (600A shown)
Equipment Wiring
When pulling, bending, and terminating field wiring, avoid scraping, cutting or otherwise damaging cable insulation or strands.
Main Incoming Power Cables
Refer to the motor control center drawings provided by GE for the location of the main disconnect or incoming line terminals and the direction (top or bottom) of cable entry. Cable-bending room provided within the vertical section will meet or exceed National Electrical Code requirements.
Incoming line sections are provided with cable supports. Incoming cables must be firmly secured to withstand the significant forces that may be generated during a short circuit .
Cables secured at each support, as illustrated in Figure 17 and Figure 18 (600A example), will adequately brace cables for faults of 100K RMS symmetrical amperes, based on horizontal bus bracing. However, cables should always be secured at the first support inside the enclosure and at the support nearest to the incoming terminals. Insulated bushings are also rec­ommended at conduit terminations.
Figure 18. Typical bottom entry or main cables to the incoming­line lug compartment (600A shown)
Align the conduit linearly directly over or as close as possible to the supports. Run the cable in a convenient orientation, making sure the cable is located against the supports before it connects to the cable terminals. Lash the cable using the following procedure:
Wrap the line cables together and, if provided, tie cables together with nominal 3/8-inch (9.5 mm) nylon rope or rope having a minimum tensile strength of 2000 pounds (8896 N), at 6 inches (152 mm) and 12 inches (305 mm) from the line terminals. Use five wraps and complete every additional 6 inches with five wraps or every 1 inch (25 mm) with one wrap. Use supplied cable supports as desired. Refer to UL 891.
Individual Unit Wiring
Open the vertical wireway door(s) and the top and/or bottom horizontal wireway hinged covers. All doors can be removed, if desired, by extracting hinge pins or removing the hinge.
10
Evolution Series E9000 Installation & Maintenance Guide
When installing cables, be sure to not damage the cable insulation on any sharp edges, such as steel work or screws.
Where access to the rear of the section is available, cables can be brought into the space behind the vertical bus and brought forward into the front wire trough area through any of the modular openings in the right­hand steel support plate.
Wiring NEMA Type A Motor Control Centers
Use the following procedure to wire NEMA Type A MCCs:
1. Remove black plastic barrier closest to unit connection points and remove knockouts as required.
2. Pull load cables near the unit to be wired. Measure (allowing for cable bends), cut and strip the cables, and feed them carefully through barrier knockout into the unit. Terminate the cables on the feeder or starter lugs provided in the unit. If aluminum wire is used, coat the wire strands with an oxide-inhibiting grease specifically designated for use with aluminum cable. Install plastic side barrier.
3. Pull the control wiring, then measure, cut, strip, and terminate it on individual device terminals in the unit.
4. When specified, an optional ground lug is provided in each draw-out combination starter unit for termi­nating a motor-frame grounding wire. (For larger starters, the lug is mounted on the horizontal ground bus.)
5. Use cord or plastic ties to secure all wiring. Route the wiring to avoid interference with moving parts and to keep it away from heat-producing components, such as resistors and fuses.
6. Verify that the connections on all devices and terminal blocks are tightened to their proper torque values, as listed on the label on the vertical wireway door.
Wiring NEMA Type B Motor Control Centers
Use the following procedure to wire NEMA Type B MCCs:
1. Remove black plastic barrier closest to unit connection points and remove knockouts as required.
2. Pull load cables near the unit to be wired. Measure (allowing for cable bends), cut and strip the cables, and feed them carefully through barrier knockout into the unit. Terminate feeder cables directly on the
lugs on the disconnect. Connect the motor leads at the starter terminals if either of these conditions is met:
a. The motor control center is furnished as
“NEMA B-D wiring” (where D=Device) or
b. The starter is NEMA size 6 or smaller. Connect the motor leads to the starter at the T1, T2, and T3 terminals if these conditions are met:
a. The equipment is furnished as “NEMA B-T” wiring
and
b. The starter is NEMA size 2 or smaller.
Install plastic side barrier after power and control wiring in Step 4 is complete. Aluminum wire is not recommended for this product.
3. Pull the control wiring, then measure, cut, strip and terminate it at the terminal blocks provided within the unit. Optionally, control terminal blocks may be pulled apart and the plastic knock-outs removed to allow wiring outside the bucket. The terminal blocks can then be placed back through the plastic knock­out openings and reinstalled. This method allows wiring to terminal blocks outside the confines of the starter unit.
4. When specified, an optional ground lug is provided in each draw-out combination starter unit for terminating a motor frame grounding wire. (For larger starters, the lug is mounted on the horizontal ground bus.)
5. Use cord or plastic ties to secure all wiring. Route the wiring to avoid interference with moving parts and to keep it away from heat-producing components, such as resistors and fuses.
6. Verify that the connections on all devices and terminal blocks are tightened to their proper torque values, as listed on the label on the vertical wireway door.
Wiring NEMA Type C Motor Control Centers
Master terminal boards in NEMA Type C motor control centers are provided in the larger top or bottom hori­zontal wireway of each vertical section. (Refer to the drawings provided by GE for the locations of master terminal boards.) Figure 19 and Figure 20 show typical Type C terminal board arrangements.
These terminal boards are connected at the factory to control terminal blocks of plug-in units in each vertical section. Wiring diagrams provided by GE show these terminal points. These terminal blocks are also factory wired to the T1, T2 and T3 motor-lead terminals for each NEMA size 1–2 starter unit in each vertical section.
11
Evolution Series E9000 Installation & Maintenance Guide
Field connections to these control and load terminals should be made at the master terminal boards.
Make field connections to all feeders and motor loads for starters larger than NEMA size 2 as described for NEMA Type B motor control centers.
Optional grounding lug can be provided in each Plug-in unite if vertical ground bus is specified.
Figure 21. Side cutout dimensions on 13", 20", 22" and 25".
If rear access is used, a rear main bus barrier is a required option.
Figure 19. Typical Type C terminal board at the top of a section
Figure 20. Typical Type C terminal boards in multiple sections
Wiring Between Sections
Figure 21 shows the dimensions of side cutouts in each vertical section for wiring between sections. Cross-wiring can be accomplished at both the top and bottom of sections. 20”or 22”deep vertical sections accessible from the rear can be cross-wired in the open rear area, with the wiring brought forward through oval openings in the rear of the vertical wireway.
Terminal Blocks
The new style terminal blocks are mounted on a metal rail located at the bottom of the unit, as shown in Figure 22. The terminal block easily slides into position from either side of the mounting rail.
Figure 22. Mounting the terminal block
Installation of Motor Control Center Units
Any unit ordered separately is shipped complete with the door and associated hardware. If the space available in the vertical section is greater than the new unit
12
Evolution Series E9000 Installation & Maintenance Guide
height, order a blank filler door with hinge hardware and a snap shelf. See the renewal parts bulletin for ordering blank doors and gasket materials. The gasket material lines the inner perimeter of the section. Figure 23 shows the gasket material mounted to the outside of the door.
Gasket
Figure 23. NEMA 12 Gasket material installed in a MCC section.
9. Slide the unit into the vertical section, then push at
the top and bottom until the stabs are fully engaged with the vertical bus.
10. Rotate the latches at the top and bottom of the unit
clockwise to engage the latches with the horizontal shelves above and below the unit. See Figures 25 and 26.
11. Verify the operation of the disconnect handle and
safety interlocks, as described later in this manual.
Use the following procedure to install a motor control center unit:
1. Attach the door hinges to the left side of the section, line up the door with the hinges, then insert the hinge pins to secure the door. Install a hold-down bracket with the lower door hinge, but do not tighten the mounting screw at this time.
2. Place the two tabs on the left side of the shelf into the appropriate openings in the section structure.
3. Lower the right side of the shelf and snap the two detents in the right-side flange into the two holes in the side of the vertical wiring trough barrier, as shown in Figure 24. Swivel the shelf hold-down bracket and grounding spring into place and tighten the lower case hinge.
4. Examine the new unit carefully, front and rear, to ensure that all screw terminals are tight, all foreign material and packing are removed, and the insulat­ing barriers are secure.
5. The unit disconnect must be in the OFF position before the unit can be inserted into the vertical section.
6. If necessary, rotate the latches at the top and bottom of the unit so that they are horizontal.
7. Remove the snap-in cover over the vertical bus stab-in openings at the appropriate installation location for the unit to be installed.
8. Lift the unit and place its base on the front horizontal surface of the snap-in shelf.
13
Figure 24. Front view of the snap-in shelf as installed.
Latches
Figure 25. Unit disconnect in the OFF position. Two quarter-turn
door latches are located at the top.
Evolution Series E9000 Installation & Maintenance Guide
5. Turn the latches at the top and bottom of the unit a quarter turn counterclockwise to release the unit. These latches are shown in Figure 25 and Figure 26.
6. Pull unit out to remove it, being extremely careful to support its weight as it is fully withdrawn.
7. The door over the withdrawn unit can be latched closed.
8. If desired, a blank door can be ordered to cover the unused opening. (For large unit spaces, two blank doors and a horizontal unit shelf may be required.)
Latch
Figure 26. Quarter-turn latch located at the bottom of the unit.
Removal of Draw-Out Motor Control Center Units
Some units may still have control power applied from an external source after the unit disconnect has been switched to the OFF position. Be extremely careful when removing units from any motor control center. Failure to observe this precaution can result in serious injury or death.
The procedure for removing a motor control center unit is generally the reverse of the procedure for installing a unit:
1. Ensure that the unit disconnect is in the OFF position, as shown in Figure 25.
2. Turn the door latches a quarter turn, open the unit door and the vertical wiring trough door.
3. Disconnect all field-connected wiring by separating the pull-apart terminal blocks in the unit. Pass the terminal blocks and wires into the vertical wiring trough. Note that the plastic knock-outs in the verti­cal wireway barrier can be removed and left within the vertical wireway, with the field wiring, rather than threading the wiring and terminals back through the knock-out.
4. Disconnect any other field-installed wires that are terminated in the unit. Remove these wires from the unit, tag them (if desired), and leave them in the vertical wireway adjacent to the unit.
Operating Handles, Door Interlocks and Padlocking Provisions
All Evolution motor control center units are furnished with disconnect operating handles that are integral to the unit structure. The position of the disconnect (ON–OFF for switches or ON–OFF–TRIP for circuit breakers) is indicated by the position of the operating handle. The operating handle is interlocked with a catch on the inside of the unit door to prevent inadvertent opening of the door when the disconnect is in the ON position, as shown in Figure 27. Switching the handle to OFF allows access to the interior of the unit.
Each disconnect operating handle is equipped with an interlock that prevents opening the door when the dis­connect is ON.
A concealed screw can be turned counterclockwise with a 5/32” Allen wrench to defeat the door interlock and access the breaker disconnect when ON, as shown in Figure 28. Only qualified personnel should be allowed to defeat the interlock.
Be careful with any field wiring removed from a unit that may become energized. Such wiring must be adequately insulated to avoid inadvertent contact. Failure to observe this precaution can result in serious injury or death.
Figure 27. Door-interlock feature that prevents access to the disconnect when the power is ON.
14
Evolution Series E9000 Installation & Maintenance Guide
Table 3. Weight and heights of CB basic with CPT
Plug-in units no door
NEMA Size 1 FVNR 35 12 NEMA Size 2 FVNR 37 12 NEMA Size 3 FVNR 53 18 NEMA Size 4 FVNR 62 24 NEMA Size 5 FVNR 125 36
Estimated weight (lbs)
Minimum height (inches)
Figure 28. Concealed screw used to defeat the door interlock.
Figure 29. The door cannot be opened when the disconnect is ON.
The disconnect is also equipped with a padlocking pro­vision, so that the operating handle can be locked in the OFF position with as many as three padlocks, as shown in Figure 30. The handle can also be drilled to accommo­date one padlock to secure it in the ON position. In either case, the unit cannot be withdrawn because of interference between the padlock(s) and door.
CAUTION should be used when removing or installing units consider the weight in table above. Two persons may be required or the assistance of a lifting devices. See page 21 for suggested lifts.
Operating Handle
The operating handle must be moved out of the way to access to the breakerdisconnect. Make sure that the disconnect operating handle is in the OFF position, as shown in Figure 30. Open the door, then remove the mounting screw securing the base of the handle to the side of the unit, as shown in Figure 31. The handle can then be rotated up and out of the way, as shown in Figure 32, allowing access to the breaker.
Final commissioning: Verify that all doors are properly latched and interlocked prior to energizing.
Figure 30. Operating handle, also showing the safety lockout hasp.
15
Figure 31. Removing the operating handle mounting screw.
Evolution Series E9000 Installation & Maintenance Guide
NEMA 3R Outdoor Enclosure Installation
Figure 32. Rotating the operating handle to access the breaker.
Pilot Bracket and Door
The pilot device door can be removed by lifting straight off per Figure 33. Also, the metal bracket can be removed by loosening mounting screws and removing bracket.
Figure 33. Grasp the center of the door.
NEMA 3R Installation Instructions
1. Remove left rear cover on right shipping module (Figure 1.) Save the screws for later reassembly of the cover. Note that the left module right rear cover has a flange that will be underneath the removed covered with it is replaced. This provides an over­lapping connection in the rear of the two spliced modules (Detail C).
2. Slide adjoining shipping modules as close together as possible while carefully aligning the modules front-to-back.
3. Join shipping modules together using (4 sets) 1/2 hardware (front only). Hardware kits shipping with modules.
4. Assemble bus splices per splice instructions (included in splice kit).
5. Install wireway transition channel barrier by sliding it though the 5 x 5 wireway cutout and attaching it using (1) 1/4-28 x 3/8 thread rolling (Figure 3).
6. Re-attach right, rear cover by re-attaching 1/4-20 x 5/8 sealing screw (Detail C).
7. Attached center cap using (8) 1/4-20 x 5/8 thread rolling screws (Figure 1).
Notes:
1. 3-inch floor members can be installed similarly to standard MCC flor members.
2. Module doors can be removed by removing 1/4-20 x 3/8 thread rolling screws from door hinge bracket (Detail D).
Figure 34. Pilot Device Bracket locking bracket in door
The pilot device bracket in is locked in place using the door mounted locking bracket shown in Figure 34.
16
Evolution Series E9000 Installation & Maintenance Guide
17
Evolution Series E9000 Installation & Maintenance Guide
Chapter 4 – Operation
Preparing for Initial Operation
In addition to the normal circuit checking after wiring is completed, the following specific actions should be taken before energizing the equipment:
1. Check and tighten any electrical connections, such as lugs and bus splices that may have loosened during shipment, handling and installation. Torque values are provided on or adjacent to components or lugs. See torque labels in MCC vertical wireway door.
2. Operate each magnetic device by hand to verify that all moving parts operate freely. Check all elec­trical contacts for proper operation.
3. Current transformers are shipped with a shunt across the secondary if the circuit is not complete. Remove the shunt after completing the connections to the transformer secondary.
4. Verify that the horsepower and voltage rating of the motor agree with the rating stamped on the starter unit to which it is connected.
5. Check each overload heater or electronic overload relay setting against the motor full-load current.
Check current transformer-operated overload relays to be certain that overload heaters are in place. Do not operate starters without overload protection.
6. Check all circuit breaker trip settings and fuse ratings against the drawings supplied with the equipment. a. If trip settings must be changed, use the GE rating
plug extractor tool (catalog number TRTOOL) to remove rating plugs from Spectra circuit breakers.
b. See the startup procedure following information
regarding instantaneous trip settings on magnetic­only circuit breakers.
The operating handle should move upward to the OFF position after the breaker has been reset. After the reset, turn the circuit breaker ON and then OFF to confirm proper operation.
10. Visually check all units and enclosures to ensure that electrical spacings have not been reduced because of shipping and handling actions.
11. Verify that the motor control center enclosure and units are grounded.
12. Replace all protection barriers and panels that have been removed during installation.
13. Carefully clean the equipment interior with a clean cloth, soft brush or vacuum cleaner to remove all metal chips, dust, wire and other debris.
14. After taking precautions to prevent accidental contact with the motor control center buswork, conduct the following insulation-resistance test with a 1000 Vdc (Megger) tester. With all disconnects in the OFF position,
• Apply voltage between all phase pairs.
• Apply voltage between each phase and ground. All readings should be 1 megohm minimum; typical values will be 50–100 megohm but may vary based on humidity. Similarly, test individual feeder and motor circuit wiring (field wiring) as each set of conductors is pulled into the motor control center, before termi­nating the conductors at either end.
15. With all disconnects OFF, close and latch all doors and secure all external covers.
Initial Operation of the Motor Control Center
Because of problems that may occur during the initial energizing of the motor control equipment, only qualified personnel should carry out this startup procedure.
Do not exceed the long-time and/or instanta­neous trip settings stipulated in the National Electrical Code and as identified in the overload heater selection tables in this manual.
7. Check all pneumatic or motor-driven timers for proper time-interval settings.
8. Manually operate all branch-circuit disconnects and verify proper operation of disconnects and door interlocks.
9. Where applicable, manually trip all circuit breakers to verify that operating handles move freely to the TRIP indicating position. With the door closed and latched, reset each tripped circuit breaker by pushing the operating handle down beyond the OFF position.
Use the following procedure for initial startup of the motor control equipment. Be sure that the steps in the previous section, Preparing for Initial Operation, have been completed.
1. Ensure that all doors are closed and latched and all external covers on the motor control center are secured.
2. Verify that all main and branch disconnects within the motor control center are OFF.
3. Verify (with an insulation-resistance tester) that all main incoming feeders to the motor control center are adequately insulated.
4. Close the upstream feeder to energize the motor control center.
18
Evolution Series E9000 Installation & Maintenance Guide
5. Close the main disconnects, if any, at the motor control center.
6. Close each branch-circuit disconnect or feeder at the motor control center.
7. Operate each motor starter individually to verify satis­factory operation, including the following parameters:
• Motor rotation
• Pilot light indication
• Electrical interlocking
• Acceleration and sequence timing
Power-factor correction capacitors on individual motor circuits should be temporarily disconnected during startup.
8. Adjust instantaneous settings on magnetic-only circuit breakers and/or fuse sizes and overload heater selections to achieve proper motor and branch circuit protection. (See NEC Article 430.52.) Since the adjustable trip setting on magnetic-only circuit breakers is factory set at the minimum trip position, nuisance tripping may occur on initial motor starting. Increase the trip setting in increments until tripping no longer occurs during motor starting. Do not exceed the maximum trip settings given in overload relay tables in this publication. All adjustable overloads are also factory set at minimum. Check motor name-plate data and set overloads accordingly.
PD Bracket
Figure 36. Partially close the pilot device bracket and extension bubble as shown
Figure 37. Partially close the door as shown
Locking Bracket
Door Closing Procedure of Pilot Device Bracket, Extension Bubble Door for Some GP/FP Drives E9000 MCC units
Variable Frequency Drive
Extension Bubble
Figure 35. Door, pilot device bracket and extension bubble in open position
19
Extension Bubble
GasketDoor Door Cut Out
Figure 38. Adjust the pilot device bracket and extension bubble lip so it enters in between the keeper bracket and inside of the door
1/4 Turn Latch
Figure 39. Close the door completely and turn the 1/4-turn latches
Evolution Series E9000 Installation & Maintenance Guide
Chapter 5 – Maintenance
Equipment Maintenance
De-energize all equipment before performing any maintenance operation. There may be voltage present within the equipment from remote sources, even though all main- and branch-circuit disconnects have been opened at the equipment. Failure to observe this precaution can result in serious injury or death.
The customer should prepare a maintenance program consisting of a schedule and checklist matrix listing items to be periodically examined on the installed equipment. The frequency and extent of the maintenance activities will vary depending on such factors as equipment usage and environmental conditions. In any maintenance program the following actions should be included:
1. Remove accumulated dust and dirt with a soft cloth, brush or vacuum cleaner.
2. Wipe clean all main bus insulators and vertical bus barriers.
3. Inspect main and vertical bus joints and main bus supports and tighten, if necessary. Refer to Table 1 for torque specifications.
4. Inspect all wiring from units for deterioration of insulation.
5. Remove draw-out units and check stabs and all unit wiring. Remove accumulated dust from horizontal shelves and the areas around stabs.
6. Check all starter contacts. They need only be replaced when nearly all the silver tip is gone and the contact tip support is exposed. Do not file the contacts. Filing or otherwise dressing the contacts only results in lost tip material and reduces starter life. See GE publication GET-6915A for questionable contact appearance.
7. Check all unit wiring for deterioration of insulation and tighten all connections.
8. Visually check meters and instruments. Check critical instrument calibrations.
9. Check all unit door interlocks for proper operation.
10. Check all indicating lights and replace, as required.
11. If fuse replacement is necessary, always install the same type and rating as the fuses furnished with the motor control center. Fuse designs may be mechani­cally equivalent but not electrically equivalent. They may not have the same short-circuit withstand and current-limiting ability.
Control Power Fusing
Control fuses are front accessible except in the 6-inch compact starter. Remove 6-inch FVNR starter for maintenance. Fuses are located on the side, as shown in Figure 40.
Figure 40. Fuse location.
Suggested Maintenance Tools
The following tools are recommended for performing maintenance operations:
• GE Spectra circuit breaker rating plug removal tool, catalog number TRTOOL (see Figure 41).
• GE pilot light and push button removal tool, catalog number GEN-1684A (see Figure 42).
• EntelliGuard TU Digital Test Kit, catalog number GTUK20 (see Figure 43). The Test Kit may also be used to temporarily defeat the ground-fault function during primary injection (high-current test set).
• Allen wrench in size 5/32 inch or #4 metric for defeating the door interlock.
Figure 41. Rating plug removal tool, catalog number TRTOOL.
20
Evolution Series E9000 Installation & Maintenance Guide
7. Slide the breaker down and out.
8. Install the new breaker by following this procedure in the reverse order. Torque all electrical connections.
Replacing a Control Power Transformer Mounted Under Disconnect
Figure 42. Pilot light and pushbutton removal tool,
catalog number GEN-1684A.
Figure 43. EntelliGuard Trip Unit Digital Test Kit, catalog number GTUK20.
Rearrangement of units must follow the following loading rules: 80% of the feeder trip or fuse clip rating, plus 100% of the starters full load current, plus 25% of the largest motor full load current. Do not exceed the vertical bus rating label on each section.
Replacing or Adding Breaker Accessories to Plug-in E or F frame Circuit Breaker
Use the following procedure to replace a control power transformer mounted under a disconnect.
1. Turn the power off.
2. Remove the saddle unit from the motor control center.
3. Remove the top plate from the saddle unit.
4. Remove the handle assembly, as described on page 15.
5. Remove line and load cables.
6. Loosen the screws securing the disconnect assembly to the back plate and slide the assembly out.
7. Disconnect the transformer power and control leads.
8. Remove the transformer mounting screws and lift out the transformer.
9. Install the new transformer by following this procedure in the reverse order. Torque all electrical connections.
Replacing a Compact Starter (1/2X)
Use the following procedure to replace the starter.
1. Turn the power off.
2. Remove the saddle unit for the motor control center.
3. Remove the pilot device bracket (it is not required to remove control wiring)
4. Remove overload relay.
5. Use DIN rail release to gain access to line side wiring of contactor, remove line wires.
6. Reverse to install new starter.
Use the following procedure to replace a circuit breaker in a motor control center.
1. Turn the power off.
2. Remove the unit from the motor control center.
3. Remove line and load cables (not required for accessories only)
4. Remove the toggle holding plate (toggle needs to be in the ON position, UP)
5. Remove the top four screws in top plate holding the breaker assembly (not required for accessories only).
6. Remove three front breaker screws from assembly.
21
Suggested Lifts
Example: GE Model No. 55B534913P1
• All welded construction
• Positive lock winch system
• 500 lb. capacity
• Raised height 58”
• Lowered height 3-1/8”
• 20”X20” deck size
• 10” load center
• 2” X 6” molded-on-rubber casters
Evolution Series E9000 Installation & Maintenance Guide
Publications Available from GE
Order any of the following publications from your nearest GE Energy representative, authorized distributor, or from the following address:
GE Energy Distribution Services PO Box 2913 Bloomington IL 61702-2913 Phone: 309-664-1513 Fax: 309-662-6990
The following instructions are available.
300 Line Starter
GEH-5190 – NEMA Size 1 FVNR GEH-4774 – NEMA Size 2 FVNR GEH-4806 – NEMA Size 3 FVNR GEH-4807 – NEMA Size 4 FVNR GEH-4839 – NEMA Size 5 FVNR GEH-5198 – NEMA Size 6 FVNR GEH-5190 – NEMA Size 1 FVR & 2 Speed GEH-4775 – NEMA Size 2 FVR & 2 Speed GEH-4806 – NEMA Size 3 FVR & 2 Speed GEH-4807 – NEMA Size 4 FVR & 2 Speed GEH-4839 – NEMA Size 5 FVR & 2 Speed GET-6915A - Tech Info.- Contact Appearance
C-2000 Contactors
GEH-6263 – CL02, CL025 GEH-6264 – CL045 GEH-6265 – CL08 GEH-6266 – CL10 GEH-6350 – CK08 GEH-6227 – CK095 GEH-6228 – CK10B, CK11B, CK12B
Solid State Starters
DEH40396 – ASTAT-IBP Plus DEH-40397 – ASTAT-CD Plus
Relays
GEH-4115 – CR120B GEH-6435 – ECM
AF600 Drives
DET-609 – AF-600FP Operating/Installation DET-620 – AF-600FP Programming Guide DET-623 – AF-600 FP/AF-650 GP DET-624 – AF-600FP / AF-650 GP Profibus DP DET-633 – AF-600 FP Analog I/O Instructions DET-635 – AF-600 FP / AF-650 GP External DC Supply DET-607 – AF-650 GP Operating/Installation DET-618 – AF-650 GP Programming Guide
Smart Relays LM 10
GEK-106642
MM300
GEK-113022 – Instruction Manual GEK-113336 – Quick Start Guide GEK-113392 – Communication Guide
MM200
GEK-113400 – Instruction Manual GEK-113401 – Quick Start Guide GEK-113402 – Communication Guide
Spectra Circuit Breakers
DET-244 – Special Lugs GET-7002 – Application and Selection DES-210 thru DES-214 – SG Frame Trip Curves DES-215 thru DES-219 – SK Frame Trip Curves GEZ-7754 – Spectra Time-Current Curves
Power Break II Insulated-Case Circuit Breakers
DEH-4568 – GTU Test Kit GEH-6270 – PBII Instruction Manual DEH-4567 – EntelliGuard Instruction Manual DES-096 thru DES-100 – EntelliGuard TU Trip Curves
Renewal Parts
Because of the variety of components furnished in the E9000 motor control center, the suggested spare parts will vary. You should consider maintaining an adequate supply of the following components as spares:
• Overload heaters
• Power and control circuit fuses
• Replacement starter contact kits
• Starter coils
• Pilot lights
• Push buttons
• Circuit breakers and fusible switches
• Extra draw-out terminal blocks
• Complete starters and/or spare units as warranted by installation needs.
Your GE account manager will be glad to assist you in preparing a recommended parts list for your installation.
22
Evolution Series E9000 Installation & Maintenance Guide
Ordering Additional or Replacement Parts
The following information is needed for supplying the proper equipment:
1. All data on the motor control center master nameplate
2. If the unit is to be a duplicate of an existing unit, all data on that unit’s nameplate, located on the right side of the unit
3. NEMA control center class: I or II
4. NEMA wiring type: A, B or C
5. NEMA enclosure type: 1, 1 Gasketed, 2, 3R or 12
6. Power supply characteristics:
• Voltage
• Number of phases
• Frequency in Hz
7. Control power voltage and frequency in Hz
8. Nameplate designation and title
9. Motor characteristics:
• Horsepower rating
• Speed in RPM
• Temperature rise in °C
• Full-load current in amperes
• Accelerating time in seconds
• Service factor
10. Disconnect characteristics:
• Fusible switch rating (A), fuse type, and clips
• Circuit breaker frame size and current rating (A)
11. NEMA starter size: 1, 2, 3, 4, 5, 6 or 7
12. Starter type: FVNR, FVR, RVNR, 2-speed winding and accessories:
• Push buttons: start-stop, forward, reverse, up, down
• Transfer switch: H-O-A
• Pilot lights: quantity, color and type
• Interlocks: quantity of NO and NC
• Control power transformer
13. Unit X height or space available
14. Are horizontal shelves or other parts required?
15 Circuitry
16. All other modifications
Other Information
For other information, refer to the nearest GE sales office and give full details, including equipment name­plate data. Nameplates are prominently displayed on the motor control center lineup and contain such details as service, voltage, frequency, factory order number. Similar nameplates are mounted on each motor control center unit .
www.geelectrical.com
23
Evolution Series E9000 Installation & Maintenance Guide
Chapter 6 – Overload Heaters
Heaters for Ther-Mag Circuit Breaker Controllers
For continuous-rated motors with a service factor of
1.15 to 1.25, select the appropriate heaters for the motor full-load current. For continuous-rated motors with a service factor of 1.0, multiply the motor full-load current by 0.9 and use this value to select heaters.
Overload relay tripping current in 40°C ambient is the minimum value of full-load current multiplied by 1.25.
Provide short-circuit protection in accordance with the National Electrical Code.
Overload relays with automatic reset may auto­matically start a motor connected to a two-wire control circuit. When automatic restarting is not desired, use a three-wire control circuit.
Circuit breaker tripping may be an indication that a fault current has been interrupted. To provide continued protection against fire or shock hazard, examine all current-carrying parts and other components of the motor controller and replace any damaged components. If heater burnout occurs, the complete overload relay must be replaced.
Size 0 and 1 (Standard and Ambient Comp.)
Motor Full- Heater Motor Full- Heater Load Amps Number Load Amps Number
3-Ph, 3 Heater CR 123 3-Ph, 3 Heater CR 123
.41-.45 C054A 4.96-549 C592A .46-.49 C060A 5.50-5.91 C630A .50-.53 C066A 5.92-6.47 C695A .54-.59 C071A 6.48-7.20 C778A .60-.65 C078A 7.21-8.22 C867A .66-.76 C087A 8.23-8.72 C955A .77-.84 C097A 8.73-9.67 C104B .85-.93 C109A 9.68-10.4 C113B
.94-1.04 C118A 10.5-11.0 C125B
1.05-1.15 C131A 11.1-12.4 C137B
1.16-1.27 C148A 12.5-13.2 C151B
1.28-1.39 C163A 13.3-15.4 C163B
1.40-1.55 C184A 15.5-17.1 C180B
1.56-1.73 C196A 17.2-18.0 C198B
1.74-1.89 C220A
1.90-2.05 C239A
2.06-2.28 C268A 17.2-18.1 C198B
2.29-2.47 C301A 18.2-20.0 C214B
2.48-2.79 C326A 20.1-21.5 C228B
2.80-3.31 C356A 21.6-22.5 C250B
3.32-3.70 C379A 22.6-23.9 C273B
3.71-4.06 C419A 24.0-26.3 C303B
4.07-4.47 C466A 26.4-27.0 C330B
4.48-4.95 C526A
Size 1
Size 2 (Standard and Ambient Comp.)
Motor Full- Heater Motor Full- Heater Load Amps Number Load Amps Number
3-Ph, 3 Heater CR 123 3-Ph, 3 Heater CR 123
5.48-5.85 C630A 16.8-17.9 C180B
5.85-6.47 C695A 18.0-18.7 C198B
6.48-7.35 C778A 18.8-20.4 C214B
7.36-8.06 C867A 20.5-22.7 C228B
8.07-9.03 C955A 22.8-24.7 C250B
9.04-9.61 C104B 24.8-26.3 C273B
9.62-10.5 C113B 26.4-29.5 C303B
10.6-11.6 C125B 29.6-32.5 C330B
11.7-12.5 C137B 32.6-36.7 C366B
12.6-13.6 C151B 36.8-41.9 C400B
13.7-16.7 C163B 42.0-43.2 C440B
43.3-45.0 C460B
Size 3 (Standard and Ambient Comp.)
Motor Full- Heater Motor Full- Heater Load Amps Number Load Amps Number
3-Ph, 3 Heater CR 123 3-Ph, 3 Heater CR 123
19.0-19.3 F233B 17.8-18.4 F233B
19.4-22.1 F243B 18.5-21.1 F243B
22.2-23.4 F270B 21.2-22.1 F270B
23.5-27.0 F300B 22.2-26.1 F300B
27.1-29.1 F327B 26.2-28.0 F327B
29.2-31.8 F357B 28.1-31.3 F357B
31.9-33.9 F395B 31.4-33.3 F395B
34.0-37.6 F430B 33.4-34.3 F430B
37.7-41.9 F487B 34.4-40.9 F487B
42.0-47.7 F567B 41.0-44.7 F567B
47.8-52.1 F614B 44.8-51.0 F614B
52.2-55.8 F658B 51.1-52.0 F658B
55.9-59.7 F719B 52.1-55.4 F719B
59.8-68.1 F772B 55.5-63.3 F772B
68.2-71.5 F848B 63.4-66.1 F848B
71.6-78.2 F914B 66.2-73.5 F914B
78.3-87.5 F104C 73.6-82.2 F104C
87.6-90.0 F114C 82.3-90.0 F114C
Size 4 (Standard and Ambient Comp.)
Motor Full- Heater Motor Full- Heater Load Amps Number Load Amps Number
3-Ph, 3 Heater CR 123 3-Ph, 3 Heater CR 123
27.1-32.2 F357B 28.8-32.0 F357B
32.3-34.0 F395B 32.1-34.2 F395B
34.1-36.8 F430B 34.3-36.7 F430B
36.9-44.6 F487B 36.8-43.9 F487B
44.7-48.4 F567B 44.0-46.6 F567B
48.5-53.9 F614B 46.7-52.6 F614B
54.0-57.4 F658B 52.7-55.6 F658B
57.5-60.0 F719B 55.7-58.7 F719B
60.1-69.5 F772B 58.8-67.1 F772B
69.6-71.7 F848B 67.2-70.6 F848B
71.8-79.9 F914B 70.7-76.3 F914B
80.0-92.3 F104C 76.4-88.7 F104C
92.4-97.0 F114C 88.8-93.4 F114C
97.1-108 F118C 93.5-105 F118C 109-118 F133C 106-114 F133C 119-131 F149C 115-128 F149C 132-135 F161C 129-131 F161C
132-135 F174C
24
Evolution Series E9000 Installation & Maintenance Guide
Size 5 (Standard and Ambient Comp.)
Motor Full- Heater Motor Full- Heater
Load Amps Number Load Amps Number
3-Ph, 3 Heater CR 123 3-Ph, 3 Heater CR 123
109-118 C592A 185-200 C104B 119-128 C630A 201-221 C113B 129-138 C695A 222-237 C125B 139-155 C778A 238-262 C137B 156-168 C867A 263-270 C151B 169-184 C955A
Heaters for Mag-Break®Controllers
The Mag-Break protector is factory adjusted to the minimum trip setting.
To maintain overload, short-circuit, and ground­fault protection, use the following instructions to select heaters and to adjust the Mag-Break trip setting.
For continuous-rated motors with a service factor of
1.15 to 1.25, select the appropriate heaters for the motor full-load current. For continuous-rated motors with a service factor of 1.0, multiply the motor full-load current by 0.9 and use this value to select heaters.
Use the heater table to verify that the Mag-Break and current limiter rating is correct for the motor full-load current. Then set the Mag-Break trip setting to the recommended value.
If the Mag-Break trips during motor startup, increase the trip setting by one step at a time until the motor can be consistently started. Do not exceed the maximum trip setting shown in the heater table.
Overload relay tripping current in 40° C ambient is the minimum value of heater full-load current multiplied by 1.25.
Circuit breaker tripping may be an indication that a fault current has been interrupted. To provide continued protection against fire or shock hazard, examine all current-carrying parts and other components of the motor controller and replace any damaged components. If heater burnout occurs, the complete overload relay must be replaced.
Size 0 and 1 (Standard )
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
.65-.74 C087A 3 LO LO .75-.84 C097A 3 LO LO .85-.92 C109A 3 LO 1
.93-1.02 C118A 3 LO 1
1.03-1.10 C131A 3 LO 2
1.11-1.23 C148A 3 LO 2
1.24-1.38 C163A 3 LO 3
1.39-1.49 C184A 3 LO 4
1.50-1.67 C196A 314
1.68-1.79 C220A 315
1.80-1.98 C239A 316
1.99-2.24 C268A 327
2.25-2.43 C301A 338
2.25-2.43 C301A 7 LO 1
2.44-2.75 C326A 7 LO 2
2.76-3.25 C356A 7 LO 3
3.26-3.43 C379A 7 LO 4
3.44-4.03 C419A 714
4.04-4.43 C466A 715
4.44-4.94 C526A 726
4.95-5.36 C592A 727
5.37-5.77 C630A 736
5.37-5.77 C630A 15 LO 2
5.78-6.35 C695A 15 LO 2
6.36-6.92 C778A 15 LO 3
6.93-7.99 C867A 15 LO 3
8.00-8.47 C955A 15 14
8.48-9.19 C104B 15 15
9.20-10.0 C113B 15 16
10.1-10.7 C125B 15 26
10.8-12.0 C137B 15 27
10.8-12.0 C137B 30 LO 2
12.1-12.9 C151B 15 38
12.1-12.9 C151B 30 LO 2
13.0-15.1 C163B 30 LO 3
15.2-16.3 C180B 30 LO 4
16.4-17.9 C198B 30 14
Size 1
18.0-19.7 C214B 30 15
19.8-21.2 C228B 30 16
21.3-22.3 C250B 30 27
22.4-23.5 C273B 30 28
23.6-25.5 C303B 30 38
23.6-25.5 C303B 50 LO 3
25.6-27.0 C330B 50 LO 3
25
Evolution Series E9000 Installation & Maintenance Guide
Size 0 and 1 (Ambient Comp.)
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
.66-.76 C087A 3 LO LO .77-.84 C097A 3 LO LO .85-.93 C109A 3 LO 1
.94-1.04 C118A 3 LO 1
1.05-1.15 C131A 3 LO 2
1.16-1.27 C148A 3 LO 2
1.28-1.39 C163A 3 LO 3
1.40-1.55 C184A 3 LO 4
1.56-1.73 C196A 314
1.74-1.89 C220A 315
1.90-2.05 C239A 326
2.06-2.28 C268A 327
2.29-2.47 C301A 338
2.29-2.47 C301A 7 LO 1
2.48-2.79 C326A 7 LO 2
2.80-3.31 C356A 7 LO 3
3.32-3.70 C379A 7 LO 4
3.71-4.06 C419A 715
4.07-4.47 C466A 715
4.48-4.95 C526A 726
4.96-5.49 C592A 727
4.96-5.49 C592A 15 LO 1
5.50-5.91 C630A 738
5.50-5.91 C630A 15 LO 2
5.92-6.47 C695A 15 LO 2
6.48-7.20 C778A 15 LO 3
7.21-8.22 C867A 15 LO 3
8.23-8.72 C955A 15 14
8.73-9.67 C104B 15 15
9.68-10.4 C113B 15 16
10.5-11.0 C125B 15 27
11.1-12.4 C137B 15 27
11.1-12.4 C137B 30 LO 2
12.5-13.2 C151B 30 LO 2
13.3-15.4 C163B 30 LO 3
15.5-17.1 C180B 30 LO 4
Size 1
17.2-18.1 C198B 30 15
18.2-20.0 C214B 30 15
20.1-21.5 C228B 30 26
21.6-22.5 C250B 30 27
22.6-23.9 C273B 30 28
22.6-23.9 C273B 50 LO 2
24.0-26.0 C303B 30 38
24.0-26.0 C303B 50 LO 3
26.1-27.0 C330B 50 LO 4
Size 2 (Standard)
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
8.81-9.27 C104B 15 25
9.28-9.99 C113B 15 26
10.0-11.1 C125B 15 36
11.2-12.1 C137B 15 37
11.2-12.1 C137B 30 LO 2
12.2-13.0 C151B 15 48
12.2-13.0 C151B 30 LO 2
13.1-15.5 C163B 30 13
15.6-16.8 C180B 30 14
16.9-18.0 C198B 30 25
18.1-19.7 C214B 30 25
19.8-21.6 C228B 30 26
21.7-23.9 C250B 30 37
21.7-23.9 C250B 50 LO 2
24.0-25.5 C273B 30 38
24.0-25.5 C273B 50 LO 3
25.6-26.0 C303B 30 39
25.6-28.2 C303B 50 LO 3
28.3-31.6 C330B 50 14
31.7-34.7 C366B 50 25
34.8-37.8 C400B 50 26
37.9-40.6 C440B 50 37
40.7-43.4 C460B 50 38
Size 2 (Ambient Comp.)
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
9.04-9.61 C104B 15 25
9.62-10.5 C113B 15 26
10.6-11.6 C125B 15 37
11.7-12.5 C137B 15 38
11.7-12.5 C137B 30 LO 2
12.6-13.0 C151B 15 49
12.6-13.6 C151B 30 LO 3
13.7-16.7 C163B 30 13
16.8-17.9 C180B 30 15
18.0-18.7 C198B 30 25
18.8-20.4 C214B 30 26
20.5-22.7 C228B 30 27
22.8-24.7 C250B 30 38
22.8-24.7 C250B 50 LO 2
24.8-26.0 C273B 30 49
24.8-26.3 C273B 50 LO 4
26.4-29.5 C303B 50 LO 4
29.6-32.5 C330B 50 14
32.6-36.7 C366B 50 26
36.8-41.9 C400B 50 27
42.0-43.2 C440B 50 39
43.3-43.4 C460B 50 39
Size 3 (Standard and Ambient Comp.)
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
17.8-18.4 F233B 30 15
18.5-21.1 F243B 30 16
21.2-22.1 F270B 30 27
22.2-26.0 F300B 30 37
26.1-28.0 F327B 50 LO 4
28.1-31.3 F357B 50 LO 4
31.4-33.3 F395B 50 15
33.4-34.3 F430B 50 16
34.4-40.9 F487B 50 16
41.0-43.4 F567B 50 28
43.5-44.7 F567B 100 LO 3
44.8-51.0 F614B 100 LO 3
51.1-52.0 F658B 100 14
52.1-55.4 F719B 100 14
26
Evolution Series E9000 Installation & Maintenance Guide
Size 3 (Standard and Ambient Comp.) cont.
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
55.5-63.3 F772B 100 15
63.4-66.1 F848B 100 26
66.2-73.5 F914B 100 26
73.6-82.2 F104C 100 27
82.3-86.9 F114C 100 39
Size 4 (Standard)
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
28.8-32.0 F357B 50 14
32.1-34.2 F395B 50 25
34.3-36.7 F430B 50 26
36.8-43.4 F487B 50 37
43.5-43.9 F487B 100 13
44.0-46.6 F567B 100 13
46.7-52.6 F614B 100 13
52.7-55.6 F658B 100 14
55.7-58.7 F719B 100 25
58.8-67.1 F772B 100 25
67.2-70.6 F848B 100 36
70.7-76.3 F914B 100 37
70.7-76.3 F914B 150 LO 1
76.4-86.9 F104C 100 48
76.4-88.7 F104C 150 LO 2
88.8-93.4 F114C 150 13
93.5-102 F118C 150 13 103-110 F133C 150 14 111-122 F149C 150 14 123-131 F161C 150 25
Size 4 (Ambient Comp.)
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
28.8-32.0 F357B 50 24
32.1-34.2 F395B 50 25
34.3-36.7 F430B 50 26
36.8-43.4 F487B 50 37
36.8-43.8 F487B 100 LO 2
43.9-46.6 F567B 100 23
46.7-52.6 F614B 100 13
52.7-55.6 F658B 100 14
55.7-58.7 F719B 100 25
58.8-67.1 F772B 100 25
67.2-70.6 F848B 100 36
70.7-76.3 F914B 100 37
76.4-86.9 F104C 100 48
76.4-88.7 F104C 150 LO 2
88.8-93.4 F114C 150 13
93.5-105 F118C 150 13 106-114 F133C 150 14 115-128 F149C 150 25 129-130 F161C 150 26
Size 0 and 1 (Standard)
Motor Full- Heater SE Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
.65-.74 C087A 3 LO LO .75-.84 C097A 3 LO LO .85-.92 C109A 3 LO LO
.93-1.02 C118A 3 LO 2
1.03-1.10 C131A 3 LO 2
1.11-1.23 C148A 3 LO 2
1.24-1.38 C163A 3 LO 3
1.39-1.49 C184A 3 LO 4
1.50-1.67 C196A 3 LO 4
1.68-1.79 C220A 3 LO 5
1.80-1.98 C239A 325
1.99-2.24 C268A 335
2.25-2.43 C301A 336
2.44-2.75 C326A 7 LO 3
2.76-3.25 C356A 7 LO 4
3.26-3.43 C379A 7 LO 4
3.44-4.03 C419A 724
4.04-4.43 C466A 725
4.44-4.94 C526A 735
4.95-5.36 C592A 736
5.37-5.77 C630A 746
5.37-5.77 C630A 15 LO 3
5.78-6.35 C695A 15 LO 3
6.36-6.92 C778A 15 LO 4
6.93-7.99 C867A 15 24
8.00-8.47 C955A 15 25
8.48-9.19 C104B 15 35
9.20-10.0 C113B 20 24
10.1-10.7 C125B 20 25
10.8-12.0 C137B 20 25
12.1-12.9 C151B 20 35
13.0-15.1 C163B 20 46
15.2-16.3 C180B 25 35
16.4-17.9 C198B 25 36
Size 1 (Standard)
Motor Full- Heater SE Mag-Break
Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
18.0-19.7 C214B 30 35
19.8-21.2 C228B 30 35
21.3-22.3 C250B 30 36
22.4-23.5 C273B 40 25
23.6-25.5 C303B 40 35
25.6-27.0 C330B 40 35
Size 5 (Standard and Ambient Comp.)
Motor Full- Heater TEC & Mag-Break Load Amps Number TECL Trip Setting
3-Ph, 3 Heater CR 123 Rating Rec. Max.
106-115 C592A 550-1670 26 116-125 C630A 550-1670 37 126-135 C695A 550-1670 37 126-135 C695A 1000-3300 LO 3 136-151 C778A 1000-3300 LO 3 152-164 C867A 1000-3300 LO 4 165-179 C955A 1000-3300 15 180-195 C104B 1000-3300 25 196-215 C113B 1000-3300 26 216-231 C125B 1000-3300 36 232-255 C137B 1000-3300 47 256-270 C151B 1000-3300 4 HI
27
Evolution Series E9000 Installation & Maintenance Guide
Size 0 and 1 (Ambient Comp.)
Motor Full- Heater SE Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
.66-.76 C087A 3 LO LO .77-.84 C097A 3 LO LO .85-.93 C109A 3 LO LO
.94-1.04 C118A 3 LO 2
1.05-1.15 C131A 3 LO 2
1.16-1.27 C148A 3 LO 3
1.28-1.39 C163A 3 LO 3
1.40-1.55 C184A 3 LO 4
1.56-1.73 C196A 324
1.74-1.89 C220A 325
1.90-2.05 C239A 325
2.06-2.28 C268A 335
2.29-2.47 C301A 336
2.48-2.79 C326A 7 LO 3
2.80-3.31 C356A 7 LO 4
3.32-3.70 C379A 724
3.71-4.06 C419A 724
4.07-4.47 C466A 725
4.48-4.95 C526A 735
4.96-5.49 C592A 736
5.50-5.91 C630A 746
5.50-5.91 C630A 15 LO 3
5.92-6.47 C695A 15 LO 3
6.48-7.20 C778A 15 24
7.21-8.22 C867A 15 24
8.23-8.72 C955A 15 25
8.73-9.67 C104B 15 35
9.68-10.4 C113B 20 24
10.5-11.0 C125B 20 24
11.1-12.4 C137B 20 25
12.5-13.2 C151B 20 35
13.3-15.4 C163B 20 46
15.5-17.1 C180B 25 35
Size 1 (Ambient Comp.)
Motor Full- Heater SE Mag-Break
Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
17.2-18.1 C198B 25 36
18.2-20.0 C214B 30 35
20.1-21.5 C228B 30 35
21.6-22.5 C250B 30 36
22.6-23.9 C273B 40 25
24.0-26.0 C303B 40 35
26.1-27.0 C330B 40 35
Size 2 (Standard)
Motor Full- Heater SE Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
8.81-9.27 C104B 15 35
9.28-9.99 C113B 20 24
10.0-11.1 C125B 20 25
11.2-12.1 C137B 20 35
12.2-13.0 C151B 20 35
13.1-15.5 C163B 20 46
15.6-16.8 C180B 25 35
16.9-18.0 C198B 25 36
18.1-19.7 C214B 30 35
19.8-21.6 C228B 30 35
21.7-23.9 C250B 40 25
24.0-25.5 C273B 40 25
25.6-28.2 C303B 50 25
28.3-31.6 C330B 50 35
31.7-34.7 C366B 50 36
34.8-37.8 C400B 50 36
37.9-40.6 C440B 60 35
40.7-43.4 C460B 60 36
Size 2 (Ambient Comp.)
Motor Full- Heater SE Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
28.8-32.0 F357B 50 35
32.1-34.2 F395B 50 35
34.3-36.7 F430B 70 25
36.8-43.8 F487B 70 35
43.9-46.6 F567B 70 35
46.7-52.6 F614B 100 24
52.7-55.6 F658B 100 25
55.7-58.7 F719B 100 25
58.8-67.1 F772B 100 35
67.2-70.6 F848B 100 36
70.7-76.3 F914B 150 24
76.4-88.7 F104C 150 25
88.8-93.4 F114C 150 35
93.5-105.0 F118C 150 35
106.0-114.0 F133C 150 35
115.0-128.0 F149C 150 46
129.0-130.0 F161C 150 46
Size 3 (Standard and Ambient Comp.)
Motor Full- Heater SE Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
17.8-18.4 F233B 30 25
18.5-21.1 F243B 30 35
21.2-22.1 F207B 30 35
22.2-26.0 F300B 40 35
26.1-28.0 F327B 40 35
28.1-31.3 F357B 50 35
31.4-33.3 F395B 50 35
33.4-34.3 F430B 50 35
34.4-40.9 F487B 70 25
41.0-44.7 F567B 70 35
44.8-51.0 F614B 100 LO 4
51.1-52.0 F658B 100 LO 4
52.1-55.4 F719B 100 25
55.5-63.3 F772B 100 35
63.4-66.1 F848B 100 35
66.2-73.5 F914B 100 36
73.6-82.2 F104C 150 24
82.3-86.9 F114C 150 25
28
Evolution Series E9000 Installation & Maintenance Guide
Size 4 (Standard)
Motor Full- Heater SE Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
28.8-32.0 F357B 50 35
32.1-34.2 F395B 50 35
34.3-36.7 F430B 70 25
36.8-43.9 F487B 70 35
44.0-46.6 F567B 70 35
46.7-52.6 F614B 100 24
52.7-55.6 F658B 100 25
55.7-58.7 F719B 100 25
58.8-67.1 F772B 100 35
67.2-70.6 F848B 100 36
70.7-76.3 F914B 150 24
76.4-88.7 F104C 150 25
88.8-93.4 F114C 150 35
93.5-102.0 F118C 150 35
103.0-110.0 F133C 150 35
111.0-122.0 F149C 150 46
123.0-131.0 F161C 150 46
Size 4 (Ambient Comp.)
Motor Full- Heater SE Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
28.8-32.0 F357B 50 35
32.1-34.2 F395B 50 35
34.3-36.7 F430B 70 25
36.8-43.8 F487B 70 35
43.9-46.6 F567B 70 35
46.7-52.6 F614B 100 24
52.7-55.6 F658B 100 25
55.7-58.7 F719B 100 25
58.8-67.1 F772B 100 35
67.2-70.6 F848B 100 36
70.7-76.3 F914B 150 24
76.4-88.7 F104C 150 25
88.8-93.4 F114C 150 35
93.5-105.0 F118C 150 35
106.0-114.0 F133C 150 35
115.0-128.0 F149C 150 46
129.0-130.0 F161C 150 46
Size 4 (Standard)
Motor Full- Heater SF Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
28.8-32.0 F357B 70 24
32.1-34.2 F395B 70 24
34.3-36.7 F430B 70 25
36.8-43.9 F487B 70 25
44.0-46.6 F567B 70 35
46.7-52.6 F614B 100 24
52.7-55.6 F658B 100 24
55.7-58.7 F719B 100 25
58.8-67.1 F772B 150 LO 4
67.2-70.6 F848B 150 LO 4
70.7-76.3 F914B 150 24
76.4-88.7 F104C 200 LO 4
88.8-93.4 F114C 200 LO 4
93.5-102.0 F118C 200 LO 5
103.0-110.0 F133C 200 26
111.0-122.0 F149C 200 26
123.0-131.0 F161C 200 26
Size 4 (Ambient Comp.)
Motor Full- Heater SF Mag-Break Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
28.8-32.0 F357B 70 24
32.1-34.2 F395B 70 34
34.3-36.7 F430B 70 35
36.8-43.8 F487B 70 35
43.9-46.6 F567B 70 35
46.7-52.6 F614B 100 24
52.7-55.6 F658B 100 24
55.7-58.7 F719B 100 25
58.8-67.1 F772B 150 LO 4
67.2-70.6 F848B 150 LO 4
70.7-76.3 F914B 150 24
76.4-88.7 F104C 200 LO 4
88.8-93.4 F114C 200 LO 4
93.5-105.0 F118C 200 LO 5
106.0-114.0 F133C 200 26
115.0-128.0 F149C 200 26
129.0-130.0 F161C 200 26
29
Evolution Series E9000 Installation & Maintenance Guide
Size 5 – 300:15 CT (Standard and Ambient Comp.)
Motor Full- Heater SG Instantaneous Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
106-115 C592A 250 LO 3 116-125 C630A 250 LO 4 126-135 C695A 250 24 136-151 C778A 250 25 152-164 C867A 300 24 165-179 C955A 300 25 180-195 C104B 350 24 196-215 C113B 350 25 216-231 C125B 400 24 232-255 C137B 400 25 256-270 C151B 400 35
Size 6 – 600:5 CT (Standard and Ambient Comp.)
Motor Full- Heater SG Instantaneous Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
181-197 C220A 400 MIN. 4 198-214 C239A 400 25 215-238 C268A 500 MIN 4 239-258 C301A 500 MIN 4 259-290 C326A 500 25 291-346 C356A 600 MIN 5 347-387 C379A 600 25 388-424 C419A 600 3 MAX
Size 6 – 600:5 CT (Standard and Ambient Comp.)
Motor Full- Heater SK Instantaneous Load Amps Number Rating Trip Setting
3-Ph, 3 Heater CR123 Plug Rec. Max.
181-197 C220A 400 LO 4 198-214 C239A 400 24 215-238 C268A 400 35 239-258 C301A 500 LO 4 259-290 C326A 500 25 291-346 C356A 800 LO 4 347-387 C379A 800 LO 5 388-423 C419A 800 25 424-467 C466A 1000 LO 4 468-516 C526A 1000 24 517-540 C592A 1000 25
Overload Heaters for Fused Controllers
For continuous-rated motors with a service factor of
1.15 to 1.25, select the appropriate heaters for the motor full-load current. For continuous-rated motors with a service factor of 1.0, multiply the motor full-load current by 0.9 and use this value to select heaters.
Overload relay tripping current in 40° C ambient is the minimum value of full-load current multiplied by 1.25.
Overload relays with automatic reset may auto­matically start a motor connected to a two-wire control circuit. When automatic restarting is not desired, use a three-wire control circuit.
Provide short-circuit protection in accordance with the National Electrical Code, except that fuses are not to exceed the value shown in the table.
Suitable for use in a circuit capable of delivering not more than the maximum RMS symmetrical amperes indicated in the Maximum Fuse and Short-Circuit Rating table below, 600 V maximum, when protected by an appropriate fuse having an interrupting rating not less than the available short-circuit current.
Opening of the fuse(s) may be an indication that a fault current has been interrupted. To provide continued protection against fire or shock hazard, examine all current-carrying parts and other components of the motor controller and replace any damaged components. If heater burnout occurs, the complete overload relay must be replaced.
Maximum Fuse and Short-Circuit Rating
NEMA
Size
Class RK Fuse Class J Fuse Class K-1, K-5 Fuse
Max. Max. RMS Max. Max. RMS Max. Max. RMS
Clip Sym. Amps Clip Sym. Amps Clip Sym. Amps
1 30A 100,000 60A 100,000 Fuse 5,000 2 60 100,000 100 100,000 per 5,000 3 100 100,000 200 100,000 Overload 5,000 4 200 100,000 400 100,000 Heater 10,000 5 400 100,000 600 100,000 Table 10,000
30
Evolution Series E9000 Installation & Maintenance Guide
Size 0 and 1 (Standard and Ambient Comp.)
Motor Full- Heater Maximum Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
.41-.45 C054A 3 .46-.49 C060A 3 .50-.53 C066A 3 .54-.59 C071A 3 .60-.65 C078A 3 .66-.76 C087A 3 .77-.84 C097A 3 .85-.93 C109A 3
.94-1.04 C118A 3
1.05-1.15 C131A 3
1.16-1.27 C148A 3
1.28-1.39 C163A 3
1.40-1.55 C184A 6
1.56-1.73 C196A 6
1.74-1.89 C220A 6
1.90-2.05 C239A 6
2.06-2.28 C268A 6
2.29-2.47 C301A 6
2.48-2.79 C326A 10
2.80-3.31 C356A 10
3.32-3.70 C379A 12
3.71-4.06 C419A 15
4.07-4.47 C466A 15
4.48-4.95 C526A 15
4.96-5.49 C592A 20
5.50-5.91 C630A 20
5.92-6.47 C695A 25
6.48-7.20 C778A 25
7.21-8.22 C867A 30
8.23-8.72 C955A 30
8.73-9.67 C104B 35
9.68-10.4 C113B 35
10.5-11.0 C125B 40
11.1-12.4 C137B 45
12.5-13.2 C151B 50
13.3-15.4 C163B 60
15.5-17.1 C180B 60
17.2-18.0 C198B 60
➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀
Size 1 (Standard and Ambient Comp.)
Motor Full- Heater Maximum
Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
17.2-18.1 C198B 60
18.2-20.0 C214B 60
20.1-21.5 C228B 60
21.6-22.5 C250B 60
22.6-23.9 C273B 60
24.0-26.3 C303B 60
26.4-27.0 C330B 60
Size 2 (Standard and Ambient Comp.)
Motor Full- Heater Maximum Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
5.48-5.85 C630A 20
5.86-6.47 C695A 20
6.48-7.35 C778A 25
7.36-8.06 C867A 30
8.07-9.03 C955A 30
9.04-9.61 C104B 35
9.62-10.5 C113B 35
10.6-11.6 C125B 40
11.7-12.5 C137B 45
12.6-13.6 C151B 50
13.7-16.7 C163B 60
16.8-17.9 C180B 60
18.0-18.7 C198B 70
18.8-20.4 C214B 80
20.5-22.7 C228B 80
22.8-24.7 C250B 90
24.8-26.3 C273B 90
26.4-29.5 C303B 100
29.6-32.5 C330B 100
32.6-36.7 C366B 100
36.8-41.9 C400B 100
42.0-43.2 C440B 100
43.3-45.0 C460B 100
Size 3 (Standard)
Motor Full- Heater Maximum Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
19.0-19.3 F233B 70
19.4-22.1 F243B 80
22.2-23.4 F270B 80
23.5-27.0 F300B 90
27.1-29.1 F327B 100
29.2-31.8 F357B 110
31.9-33.9 F395B 125
34.0-37.6 F430B 125
37.7-41.9 F487B 150
42.0-47.7 F567B 175
47.8-52.1 F614B 175
52.2-55.8 F658B 200
55.9-59.7 F719B 200
59.8-68.1 F772B 200
68.2-71.5 F848B 200
71.6-78.2 F914B 200
78.3-87.5 F104C 200
87.6-90.0 F114C 200
➀ ➀ ➀ ➀ ➀
➀ ➀ ➀ ➀ ➀ ➀
➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀
See maximum fuse and short-circuit rating table on page 29.
31
Evolution Series E9000 Installation & Maintenance Guide
Size 3 (Ambient Comp.)
Motor Full- Heater Maximum
Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
17.8-18.4 F233B 70
18.5-21.1 F243B 80
21.2-22.1 F270B 80
22.2-26.1 F300B 90
26.2-28.0 F327B 100
28.1-31.3 F357B 110
31.4-33.3 F395B 125
33.4-34.3 F430B 125
34.4-40.9 F487B 150
41.0-44.7 F567B 150
44.8-51.0 F614B 175
51.1-52.0 F658B 200
52.1-55.4 F719B 200
55.5-63.3 F772B 200
63.4-66.1 F848B 200
66.2-73.5 F914B 200
73.6-82.2 F104C 200
82.3-90.0 F114C 200
Size 4 (Standard)
Motor Full- Heater Maximum
Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
27.1-32.2 F357B 110
32.3-34.0 F395B 125
34.1-36.8 F430B 125
36.9-44.6 F487B 150
44.7-48.4 F567B 175
48.5-53.9 F614B 175
54.0-57.4 F658B 200
57.5-60.0 F719B 225
60.1-69.5 F772B 225
69.6-71.7 F848B 250
71.8-79.9 F914B 275
80.0-92.3 F104C 300
92.4-97.0 F114C 350
97.1-108 F118C 400 109-118 F133C 400 119-131 F149C 400 132-135 F161C 400
Size 4 (Ambient Comp.)
Motor Full- Heater Maximum
Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
28.8-32.0 F357B 110
32.1-34.2 F395B 125
34.3-36.7 F430B 125
36.8-43.9 F487B 150
44.0-46.6 F567B 175
46.7-52.6 F614B 175
52.7-55.6 F658B 200
55.7-58.7 F719B 225
58.8-67.1 F772B 225
67.2-70.6 F848B 250
70.7-76.3 F914B 275
76.4-88.7 F104C 300
88.8-93.4 F114C 350
93.5-105 F118C 350 106-114 F133C 400 115-128 F149C 400 129-131 F161C 400 132-135 F174C 400
Size 5 – 300:15CT (Standard and Ambient Comp.)
Motor Full- Heater Maximum
Load Amps Number Fuse
3-Ph., 3-Heater CR123 Rating
109-118 C592A 600 119-128 C630A 600 129-138 C695A 600 139-155 C778A 600 156-168 C867A 600
➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀
169-184 C955A 600 185-200 C104B 600 201-221 C113B 600 222-237 C125B 600 238-262 C137B 600 263-270 C151B 600
Electronic Overload Table for Fusible Controllers
Tripping current is 120% of Dial setting. Motors with 1.15-1.25 serv­ice factor, set dial to motor FLA Motors with 1.0 service factor, set dial to 0.9 motor FLA.
NEMA Size FLA Range in Amps Catalog Number Max. Fuse in Amps
1 0.8 to 1.59 CR324CXD Class R 30 Class J 60 1 1.6 to 3.19 CR324CXE 1 3.2 to 6.49 CR324CXF 1 6.5 to 12.8 CR324CXG 1 13 to 27 CR324CXH 2 13 to 25.6 CR324DXG 60 100 2 26 to 49.9 CR324DXH 2 50 to 100 CR324DXJ 3 17 to 34.9 CR324FXK 100 200
➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀
3 35 to 64.9 CR324FXL 3 65 to 90 CR324FXM 4 17 to 34.9 CR324FXK 200 400 4 35 to 64.9 CR324FXL
4 65 to 135 CR324FXM 5 32 to 64.0 CR324GXN 400 600 5 65 to 129.9 CR324GXP 5 130 to 270 CR324GXQ 6 130 to 259.9 CR324HXS 600 Class L 1200 6 260 to 540 CR324HXT
300:15 CT’s800:5 CT’s
Additional motor overload protection required for MM200 abd MM300 relay applications with FLA less than 6A.
➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀ ➀
See maximum fuse and short-circuit rating table on page 29.
32
Evolution Series E9000 Installation & Maintenance Guide
Heaters for NEMA Size 6 and 7 Fused Controllers
For continuous-rated motors with a service factor of
1.15 to 1.25, select the appropriate heaters for the motor full-load current. For continuous-rated motors with a service factor of 1.0, multiply the motor full-load current by 0.9 and use this value to select heaters.
Overload relay tripping current in 40° C ambient is the minimum value of full-load current multiplied by 1.25. Provide short-circuit protection in accordance with the National Electrical Code.
Opening of the circuit breaker or power fuse may be an indication that a fault current has been interrupted. To provide continued protection against fire or shock hazard, examine all current­carrying parts and other components of the motor controller and replace any damaged components. If heater burnout occurs, the complete overload relay must be replaced.
Overload heaters for controllers with NEMA Size 6 starters for standard and ambient-compensated ratings, CT ratio 600:5.
Maximum Motor
Full-Load Current
181-197 1.51-1.64 C220A 198-214 1.65-1.78 C239A 215-238 1.79-1.98 C268A 239-258 1.99-2.15 C301A 259-290 2.16-2.42 C326A 291-346 2.43-2.88 C356A 347-387 2.89-3.22 C379A 388-423 3.23-3.53 C419A 424-467 3.54-3.89 C466A 468-516 3.90-4.30 C526A 517-540 4.31-4.50 C592A
Overload heaters for controllers with NEMA Size 7 starters for standard and ambient-compensated ratings, CT ratio 800:5.
Maximum Motor
Full-Load Current
346-387 2.16-2.42 C326A 388-461 2.43-2.88 C356A 462-515 2.89-3.22 C379A 516-565 3.23-3.53 C419A 566-622 3.54-3.89 C466A 623-688 3.90-4.30 C526A 689-763 4.31-4.77 C592A 764-810 4.78-5.06 C630A
Current Transformer
Secondary Amps
Current Transformer
Secondary Amps
Heater Number
CR 123
Heater Number
CR 123
Electronic Overload for Circuit Breaker and Fused Controllers
The tripping current is 120% of the dial setting. For continuous-rated motors with a service factor of 1.15 to 1.25, set the dial to the motor full-load current. For continuous-rated motors with a service factor of 1.0, set the dial to 0.9 of the motor full-load current. Refer to GEH-6430 or 6431 before energizing.
Opening of the branch-circuit protective device may be an indication that a fault current has been interrupted. To provide continued protection against fire or shock hazard, examine all current­carrying parts and other components of the motor controller and replace any damaged components. If heater burnout occurs, the complete overload relay must be replaced.
Provide short-circuit protection in accordance with NEC Article 430 or CE Code Part 1.
Tripping current is 120% of Dial setting. Motors with 1.15-1.25 service factor, set dial to motor FLA Motors with 1.0 service factor, set dial to 0.9 motor FLA.
Catalog numbers of electronic overloads for various sizes of NEMA starters and current ranges.
NEMA
FLA Range
Size
in Amps
1 0.8 to 1.59 CR324CXD E Mag. & Thermal Mag. 1 1.6 to 3.19 CR324CXE E Mag. & Thermal Mag. 1 3.2 to 6.49 CR324CXF E Mag. & Thermal Mag. 1 6.5 to 12.8 CR324CXG E Mag. & Thermal Mag. 1 13 to 27 CR324CXH E Mag. & Thermal Mag. 2 13 to 25.6 CR324DXG E Mag. & Thermal Mag. 2 26 to 49.9 CR324DXH E Mag. & Thermal Mag. 2 50 to 100 CR324DXJ E Mag. & Thermal Mag. 3 17 to 34.9 CR324FXK E Mag. & Thermal Mag. 3 35 to 64.9 CR324FXL E Mag. & Thermal Mag. 3 65 to 90 CR324FXM E Mag. & Thermal Mag. 4 17 to 34.9 CR324FXK E,F&G Mag. & Thermal Mag. 4 35 to 64.9 CR324FXL E,F&G Mag. & Thermal Mag. 4 65 to 135 CR324FXM E,F&G Mag. & Thermal Mag. 5
32 to 64.0 CR324GXN G Mag. & Thermal Mag.
5
65 to 129.9 CR324GXP G Mag. & Thermal Mag.
5
130 to 270 CR324GXQ G Mag. & Thermal Mag.
6
130 to 259.9 CR324HXS G,K Mag. & Thermal Mag.
6
260 to 540 CR324HXT K Mag. & Thermal Mag
300:15 CT’s800:5 CT’s
Catalog Number
Breaker Frame & Type
33
Catalog numbers of electronic overloads for various sizes of NEMA starters and current ranges.
NEMA Size
FLA Range in Amps
Catalog Number
Max. Fuse in Amps
1 0.8 to 1.59 CR324CXD 1 1.6 to 3.19 CR324CXE 1 3.2 to 6.49 CR324CXF 1 6.5 to 12.8 CR324CXG
Time-Delay Class R&J 30
Time-Delay Class J 60
1 13 to 27 CR324CXH 2 13 to 25.6 CR324DXG 2 26 to 49.9 CR324DXH
60
100 2 50 to 100 CR324DXJ 3 17 to 34.9 CR324FXK 3 35 to 64.9 CR324FXL
100
200 3 65 to 90 CR324FXM 4 17 to 34.9 CR324FXK 4 35 to 64.9 CR324FXL
200
400 4 65 to 135 CR324FXM 5 5 5
6
300:15 CT’s800:5 CT’s
32 to 64.0 CR324GXN 65 to 129.9 CR324GXP
400
130 to 270 CR324GXQ
130 to 259.9 CR324HXS 600
600
Class L 1200
IEC Style Overload Relays C2000 Contactor CLNCJ Type RT Overload Relay for 1/2X Starter
Current Range
Max
Cat. No. Class Cat. No. Class
CB
Lug/ wire size
Torque (in-lbs)
0.4-.65 15 RTN1D 10 RT12D 20 #14-8 14-20
0.65-1.1 15 RTN1F 10 RT12F 20 #14-8 14-20 1-1.5 15 RTN1G 10 RT12G 20 #14-8 14-20
1.3-1.9 15 RTN1H 10 RT12H 20 #14-8 14-20
1.8-2.7 15 RTN1J 10 RT12J 20 #14-8 14-20
2.5-4.1 15 RTNIK 10 RT12K 20 #14-8 14-20
4.0-6.3 15 RTNIL 10 RT12L 20 #14-8 14-20
5.5-8.5 15 RTNIM 10 RT12M 20 #14-8 14-20
8.0-12 30 RTNIN 10 RT12N 20 #14-8 14-20
10.0-16 35 RTNIP 10 RT12P 20 #14-8 14-20
14.5-18 40 RTNIS 10 RT12S 20 #14-8 14-20
17.5-22 50 RTNIT 10 RT12T 20 #14-8 14-20
AF-600 FP / AF-650 GP Drives E9000
Panel mount use with RTXP base adapter
Contactor
Cat. No. Class 10 Class 20
FLA range
Lug/ wire size
Torque (in-lbs)
LAR02AJ RTN1B NA 0.16-0.26 #14-8 AWG 14-20 LAR25AJ RTN1C NA 0.27-0.41 #14-8 AWG 14-20
RTN1D RT12D 0.42-0.65 #14-8 AWG 14-20 RTN1F RT12F 0.66-1.10 #14-8 AWG 14-20 RTN1G RT12G 1.11-1.50 #14-8 AWG 14-20 RTN1H RT12H 1.51-1.90 #14-8 AWG 14-20 RTN1J RT12J 1.91-2.5 #14-8 AWG 14-20 RTN1K RT12K 2.51-4.10 #14-8 AWG 14-20 RTN1L RT12L 4.11-6.3 #14-8 AWG 14-20
LAR45AJ
RTN1M RT12M 6.31-8.5 #14-8 AWG 14-20 RTN1N RT12N 8.51-12.0 #14-8 AWG 14-20 RTN1P RT12P 12.1-16 #14-8 AWG 14-20 RTN1S RT12S 16.1-18 #14-8 AWG 14-20 RTN1T RT12T 18.1-22 #14-8 AWG 14-20 RTN1U RT12U 22.1-26 #14-8 AWG 14-20 RTN1V RT12V 26.1-32 #14-8 AWG 14-20 RTN1W RT12W 32.1-40 #14-8 AWG 14-20
LAR08AJ RTN2A NA 11.5-15 #10-3 AWG 50
Mount direct to contactor
Contactor
Cat. No. Class 10 Class 20
FLA range Lug/ wire size
Torque (in-lbs)
LAR08AJ RTN2B NA 15.1-19 #10-3 AWG 50
RTN2C NA 19.1-25 #10-3 AWG 50 RTN2D RT22D 25.1-32 #10-3 AWG 50 RTN2E RT22E 32.1-43 #10-3 AWG 50
LAR10AJ
RTN2G RT22G 43.1-55 #10-3 AWG 50 RTN2H RT22H 55.1-65 #10-3 AWG 50 RTN2J RT22H 65.1-82 #10-3 AWG 50 RTN2L RT22L 82.1-97 #10-1 AWG 50 RTN2M RT22M 97.1-110 #10-1 AWG 50 RTN3B NA 55-80 #6-250 MCM 275 RTN3C RT32C 80.1-90 #6-250 MCM 275
KAR08CJ
RTN3D RT32D 90.1-120 #6-250 MCM 275 RTN3E RT32E 120.1-140 #6-250 MCM 275 RTN3F RT32F 140.1-190 #6-250 MCM 275 RTN4N NA * 120-190 #6-350MCM 200
KAR95BYWZ
RTN4P NA * 190.1-280 #6-350MCM 200 RTN4R NA * 280.1-310 #6-350MCM 200 RTN4N NA * 120-190 #6-350 MCM 200
KAR95BJWZ
RTN4P NA * 190.1-280 #6-350 MCM 200
RTN4R NA * 280.1-310 #6-350 MCM 200 KAR10BYWZ RTN5A NA * 120-190 #6-350MCM 375 KAR11BYWZ RTN5B NA * 190.1-280 #6-350MCM 375 KAR11BJWZ RTN5B NA * 190.1-280 #6-350 MCM 375 KAR12BJWZ RTN5C NA * 280.1-400 #6-350 MCM 375
RTN5C NA * 280.1-400 #8-500 MCM 375 KAR12BYWZ
RTN5D NA * 400.1-500 #8-500 MCM 375
RTN5E NA * 500.1-650 #8-500 MCM 375
*Class 30 is available WZ – Special for Mebane
34
imagination at work
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.
GE Energy
41 Woodford Avenue, Plainville, CT 06062 www.geelectrical.com
© 2010 General Electric Company
DEH-40472 R05 07/10
Loading...