GE Industrial Solutions DNK400 User Manual

DEH44151 Installation Instructions
g
Neutral mounting kit
Catalog number – TNK400
Introduction
This bulletin provides instructions for installing Neutral lug kit – TNK400 on all GE Double throw safety switch rated 400A.
WARNING: Hazard of electrical shock or burn. Turn off power before working inside this equipment.
Description
This neutral kit consists of the following parts:
1. One (1) Neutral assembly
2. Two (2) 1/4-20 X 9/16” mounting screws
Mounting Instruction
1. Tighten item 2 (Mounting screws) in to
mounting hole in the enclosure. Ref. Fig 1
2. For bonding, bare wire 1/0 CU/AL is to
be used to connect small lug in neutral assembly to ground kit (Order separately).
Wire range: 2 – 600MCM CU/AL
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE
g
Company.
General Electric Company 41 Woodford Ave., Plainville, CT. 06062 DEH44151 R01 08/07 © 2007 General Electric
Visit us on the web at www.GEindustrial.com