GE Industrial Solutions Compact Vacuum Circuit Breaker Coil Signaling Contacts User Manual

Page 1
1
Cat no
Cat no
Compact Vacuum
Circuit Breaker
WARNING: Before installing any accessories, turn
the
AVERTISSEMENT: Avant d’installer tout accessoire,
Introduction Coil Signaling Contacts:
DEH-41517 Installation Instructions
Accessories
Coil Signaling Contacts
breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement
CSC, Signal rated Contact:
Table 1. Catalog Number and Ratings:
CSC, Power rated Contact:
AC Ratings
125Vdc 6A
GCSP1R
250Vdc 6A
AC Ratings 125Vac 0.1A
GCSP2R
DC Ratings 30Vdc 0.1A
Use the following procedure to install Release Indication Contact accessory into the circuit breaker.
1. Verify that the rating on the Release Indication Contact identification plate matches the voltage rating required for the application, as listed in Table 1.
2. Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background. If installing in a draw-out type breaker remove breaker from adaptor (cassette) before continuing.
3. Loosen the 6 screws on front cover (fascia) using a posidrive screw driver as shown in Fig 1.B
Page 2
2
Rotate the charging handle down and slide the front cover over the handle to remove the front cover as shown in Fig. 1.C.
B
A
Figure 1. (A) Front Cover (B) Screw Removal (C) Handle Rotation
4. Remove the existing coil from the mechanism.
5. Remove the coil cover by pressing the three snaps as shown in Fig. 2.
C
Figure 3. Cover assembly
7. Guide the wires in the wire opening of the coil housing as shown in Fig. 4. Press the cover and ensure the 3 snaps are engaged with the openings in the coil housing.
Figure 4. Cover assembly
8. Tilt the coil forward and engage the front hooks into the mechanism top support plate as shown in the Fig. 5.
Figure 2. Removing the existing cover
6. Align the new cover with Release Indication Contacts on the coil as shown in Fig. 3.
Figure 5. Assembly of coil
Page 3
3
9. Tilt the device backwards until the rear hooks engage in the slots on the mechanism top support plate as shown in the Fig. 6.
11. To reinstall the cover, rotate the charging handle down and slide the front cover over the handle to assemble the front cover to housing as shown in Fig. 8.
Figure 6. Assembly of coil
10. Plug the connector from the Release Indication Contact cover with the connectors from the harness of the trip unit as shown in Fig.7. While connecting ensure the coils are connected with the correct connectors from the harness such as marked as ST1/UV1/CC/ST2&UV2 from the respective coils.
Figure 7. Assembly of connector
Figure 8
12. Ensure the fascia is aligned properly with the trip unit and the pad lock features of the breaker.
13. Fasten the 4 mounting screws of fascia with the housing using a pozi drive screwdriver. Apply torque of 3-4 Nm.
Page 4
4
These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in co
nnection
GE
DEH-41420 R2 (05/0
9)
Reference: Coil status connection scheme:
with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE.
41 Woodford Ave, Plainville, CT 06062 www.geelectrical.com
© 2009 General Electric Company