Installer Instructions
DEH41543 Homeowner & Installer Information
Combination Arc-Fault Circuit Breaker
Arc-Fault Circuit Breaker Connection Diagram
WARNING: Failure to follow these instructions could
result in death, personal injury, or property damage.
• This circuit breaker is intended for use on single-phase
grounded 120 Vac 2-wire branch circuits.
• Can be used with a shared neutral circuit. Refer to
DET-719, “Applying 1-pole Combination AFCIs to
Shared Neutral Circuits”.
• This equipment must be installed and serviced only by
a qualified electrician.
WARNING: Turn off power to main breaker before
beginning installation. Failure to do so will risk electrical
shock and possible death, personal injury, or property
damage.
Install the Arc-Fault Circuit Breaker using the following
procedure:
1. Open the Arc-Fault Circuit Breaker by moving its handle
firmly to the OFF position.
2. Install the Arc-Fault Circuit Breaker into the load center
(see connection diagram).
A. Connect the coiled white “pigtail” wire from the Arc-
Fault Circuit Breaker to the panel or enclosure neutral
bus terminal and secure it tightly. Uncoil pigtail as
necessary.
B. Connect the white (neutral) load wire to the terminal
side of the circuit breaker, identified by a silver-colored
terminal screw, labeled LOAD NEUTRAL.
C. Connect black (hot) wire to circuit breaker terminals
labeled LOAD, identified by a gold-colored terminal
screw.
3. Plug in or bolt on the circuit breaker into the desired pole
position.
4. Test the Arc-Fault Circuit Breaker using the test rocker
switch on the front of the breaker. Follow Test Procedures
as indicated in next section.
5. See Troubleshooting Guide for the troubleshooting method
to be used for a tripped Arc-Fault Circuit Breaker.
Warning: Do not reverse-feed or back-wire. Do not subject to megger, high-voltage, or high-pot tests. Remove the circuit
breaker before high-potting occurs on the circuit or the system.
Test Procedures (AFCI circuit breakers should be tested regularly, at least once per month.)
Note: refer to DEH41133 for AFCI Circuit Breakers (AFCI breakers will have an “AF” in the suffix of the catalog number)
The test feature allows the homeowner to test the arc detection capability by depressing a rocker switch in two directions. The
breaker has passed the test if the TRIP flag appears in the window.
Parallel Arc Test: Rotate the test switch in the direction labeled “PAR ARC TEST” to check the ability of the Arc-Fault Circuit
Breaker to detect high current arcing line-to-neutral or line-to-ground.
Series Arc Test: Rotate the test switch in the direction labeled “SER ARC TEST” to check the ability of the Arc-Fault Circuit
Breaker to detect low current arcing in series with the load.
CAUTION: The Arc-Fault Circuit Breaker must be supplied with power from the load center in order for the tests to
function properly. If the power is on and either of these tests fails to trip, the Arc-Fault Circuit Breaker may be unable to
detect arcs. The circuit breaker is defective and should be replaced.
Troubleshooting Guidelines
Push-to-test
switch will not
trip circuit
breaker.
1. Circuit breaker is OFF.
2. Circuit breaker is tripped.
3. Load center is not energized.
4. Load center neutral (pigtail) is not
connected to the neutral bus bar.
5. Circuit breaker is damaged.
1. Turn circuit breaker ON.
2. Reset the breaker by switching it OFF and then
ON.
3. Check to be sure load center is energized.
4. Check neutral (pigtail) connection.
5. Replace circuit breaker.
Circuit
breaker trips
(handle in
center
position and
trip flag
appears).
1. Circuit breaker is not installed correctly.
2. An overload condition exists on the
branch circuit (total current drawn
exceeds rating of breaker).
3. An arc-fault condition exists on the
branch circuit, or circuit breaker is
damaged.
4. A load or combination of loads on the
branch circuit emits a current signature
that looks like a valid arc-fault.
1. See installation instructions on reverse side.
2. Assess the current on the circuit drawn by all the
loads by summing all branch amperages (divide
the rated wattage of each load by 120). If this
total is greater than the circuit breaker rating, the
circuit is overloaded and some of the load should
be removed.
3. Test for arc-fault by completing instructions
below.
4. Contact GE (see contact information below) for
troubleshooting information.
To test for arc-fault:
Unplug all items from the receptacles in branch circuit. Reset circuit breaker by pushing its handle to the OFF position
and then to the ON position:
1. If breaker trips with all loads OFF: Check permanent electrical circuit wiring, arcing, poor insulation, shorted wires,
wet connections, wet conduit, a neutral lead pinched to a grounded metal box, receptacle leakage, loose
connections, or other faults that could cause safety features in the breaker to open the circuit.
2. Switch ON one of the original loads. Reset the breaker. If breaker does not trip with this load ON, switch on an
additional load. Repeat until breaker trips. Examine last additional load for possible faults.
Loads and/or wiring suspected of having faults should not be restored to service.
g
GE Consumer and Industrial
General Electric Company
41 Woodford Ave., Plainville, CT 06062
DEH41543 R02 0312 © 2011 General Electric Company
INSTALLING ELECTRICIAN’S INFORMATION
Installing electrician should add the following information:
Installer’s Name
Installer’s Address
Installer’s Phone #
NOTICE: These instructions do not cover all details or
variations in equipment nor do they provide for every
possible contingency that may be met in connection with
installation, operation, or maintenance. Should further
information be desired or should particular problems
arise that are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to
the GE Company. See contact information below.
For troubleshooting or service related questions, contact GE at 800-782-8061 or at
gebreaker@ge.com