GE Industrial Solutions 664 Infinity C DC to DC Power System User Manual

Installation Guide
Infinity C™ DC to DC Power System
Models 663 / 664
dc to dc Power Shelf
Service and Assistance - +1 877 546 3243 or +1 972 244 9288 PE.TechSupport@ge.com © 2012 General Electric Company. All rights reserved. http://www.ge.com/powerelectronics CC848921016 r02 December 2012 1
663 / 664E Installation Guide

Table of Contents

Table of Contents ............................................................................................................................................................................ 2
Introduction ....................................................................................................................................................................................... 3
Reference Documents ..................................................................................................................................................................................................... 3
Customer Service Contacts .......................................................................................................................................................................................... 3
On-Line Power Systems Product Manuals and Software ........................................................................................................................ 3
Product Description ....................................................................................................................................................................... 4
Overview ................................................................................................................................................................................................................................... 4
Configurations ....................................................................................................................................................................................................................... 5
Converters................................................................................................................................................................................................................................ 5
Installation ......................................................................................................................................................................................... 6
Preparation .............................................................................................................................................................................................................................. 6
Safety ................................................................................................................................................................................................................................. 6
Installation ................................................................................................................................................................................................................................ 6
Safety................................................................................................................................................................................................. 11
Revision History ............................................................................................................................................................................ 14
CC848921016 r02 December 2012 Page 2
663 / 664E Installation Guide
Calling from
Phone Number
United States, Canada, Puerto Rico, and the US Virgin
+1 877 546 3243
All other countries
+1 972 244 9288
Or contact your local field support center or your sales representative to discuss your specific needs.

Introduction

This manual is intended as a guide in assisting equipment understanding, installation, testing, and troubleshooting.
For additional assistance contact Customer Service or access additional information on-line.

Reference Documents

Document Title
CC848921024 Quick Start Guide
CC848836981 Pulsar Edge Controller Family Product Manual
Infinity C™ Product Line Brochure – Specifications and Ordering Guide

Customer Service Contacts

Customer Service, Customer Training, Technical Support, Product Repair and Return, and Warranty Service
Services provided include initiating the spare parts procurement process, ordering documents, product warranty administration, and providing other product and service information.
GE Energy phones are staffed from 7:00 am to 5:00 pm USA Central Time Zone (GMT -6), Monday through Friday, on normal business days. At other times, this number is still available, but for emergencies only.
Islands
Or
USADCC
1
+ 877 546 3243

On-Line Power Systems Product Manuals and Software

Product manuals, product line brochures, and software are available on-line. Software includes Easy View and SNMP MIB.
http://www.ge.com/powerelectronics
1
the USA direct country code for the country where the call is originating
CC848921016 r02 December 2012 Page 3
663 / 664E Installation Guide
663
+24V
-48V
NE030DC48A4
30A
664
-48V
+24V
NE075DC24A5
75A

Product Description

Overview

Infinity C™ dc to dc power shelves convert and distribute available battery voltage to another dc voltage. This allows a single bank of batteries to provide battery reserve for equipment operating at a different dc voltage.
Features
Positive or Negative output
664 – Positive output 663 – Negative output
DC to DC Converters
48V 30A output
24V 75A output
Distribution
Plug in circuit breakers
Up to 6 5A to 100A
GMT fuses
Up to 10
0.18A to 15A
Controller - Galaxy Pulsar Edge
Ethernet and RS232 or USB
Windows GUI compatible via GE EasyView software
Mounting - 19” or 23” rack mount
NEBS Level 3
2
Models
Model Input3 Output3 Converter Output per Converter
2
Available at http://www.ge.com/powerelectronics
3
Nominal voltage
4
CC109112471 or SM48N30L
5
CC109142881
CC848921016 r02 December 2012 Page 4
663 / 664E Installation Guide
6 CB, 10 GMT, 3 Converters
4 CB, 10 GMT, 4 Converters
6 CB, 4 Converters
Converter retaining latch open
Converter Front View

Configurations

Converters

CC848921016 r02 December 2012 Page 5
663 / 664E Installation Guide

Installation

Preparation

Safety

Read and follow all safety statements, warnings, and precautions in the Safety section of this manual and manuals of all other equipment before installing, maintaining or repairing the equipment. Product manuals contain additional safety statements, warnings, and precautions specific to the products.
Installation Tools
Even though most initial installations are performed while the system is turned off, the use of properly insulated tools are recommended.
Wire Cutters and Strippers
SAE Socket Sets
Digital Meter, +/- 0.02% accuracy
Screw Drivers (flat-blade and Phillips)
Torque Wrench (0-240 in-lb / 28 Nm)
ESD Wrist or Heel Strap

Installation

Step 1 Mount Shelf
Shelf Mounting
The 663/664 shelf power system
mounts in a 19 inch relay rack. Additional brackets are required for 23 inch mounting
19 inch mounting
CC848921016 r02 December 2012 Page 6
663 / 664E Installation Guide
Chassis Ground
Loosen captive screws
Rear Cover
Supply and return connections
Step 2 Ground Chassis
Chassis Ground
Vertical or horizontal chassis ground cable
landings are threaded holes 1/4-20 on 5/8 inch centers Torque to 240 in-lb
Chassis ground connections are available if
customer standards require the power system to have an independent grounding connection. The manufacturer does not require this connection when the relay rack or cabinet housing power system is properly grounded to maintain product operation or product warranty
NOTE: Failure to properly ground the power system is
hazardous to site personnel and can damage the power system circuit cards and converter modules. It may void the power plant warranty.
Connections
Step 3 Run and Terminate dc Input Connections
Loosen captive hardware
Remove cover by sliding to the left and back.
Input supply and return lug landings are 1/4-20
on 5/8 inch centers Torque to 240 in-lb
Flex cable is recommended for sizes larger than
No. 2 AWG
Narrow tough lugs are required for lug sizes
larger than No.2 AWG
Supply and return tabs are staggered for ease of
cabling
Cabling exists to the left when facing the rear of
the system
CC848921016 r02 December 2012 Page 7
663 / 664E Installation Guide
Connectorized
Circuit breaker
GMT
Step 4 Run and Terminate Alarm Cabling
Run and terminate alarm cabling
Jumper settings are available for both
Close on Alarm and Open on Alarm extensions
Verify alarm extensions with the Alarm
Center
See Pulsar Edge Controller Family
Product Manual for additional information
Alarm Cable connection
Step 5 Run & Term. Supply and Return Cables
Output cabling
With GMT fuses and circuit breakers
removed, land all supply and return cabling at the rear of the system
Circuit breaker lug landings -
1/4” on 5/8 inch centers Torque to 240 in-lb
GMT wire landings –
Strip wire 3/8” Torque to 13 in-lb
landing positions
landing positions
CC848921016 r02 December 2012 Page 8
663 / 664E Installation Guide
Green during
Step 6 Energize Power Plant
Start up
Remove all converter modules from the power plant if
previously installed
Insert a single converter and turn on the input breaker
to this converter. This will apply input voltage to the controller and system load bus.
The controllers’ self-diagnostic will start within 30
seconds after power has been applied to the load bus
Normal operation is indicated by the Green illuminated
front display
Step 7 Install Converter Modules
Module Installation
Insert converter modules
Converters can be added or removed with the
power plant energized
Status LEDs:
Pulsar Edge Controller
Normal Operation
normal operation
Normal = Green
Input Fail = Amber
Fail = Red
CC848921016 r02 December 2012 Page 9
663 / 664E Installation Guide
Step 8
Using the Controller
Verify that the display screen is illuminated Green
Verify that no alarms are reported
Verify status of all converter modules are
communicating properly
Verify all extended alarms with the Alarm Center.
(see Pulsar Edge Controller Family Product Manual for alarm extension test)
Verify that the plant voltage displayed is within ±
0.05V of voltage measured between the charge bus and DC Return using a calibrated DVM
A Yellow display indicates the plant is in a Minor
Alarm condition
A Red Display indicates the plant is in a Major
Alarm condition
NOTE: Alarms will be extended to the Network Alarm
Center during alarm controller based alarm testing.
System Verification and Alarm Extension
Verification
Pulsar Edge Controller
Normal Operation
Pulsar Edge Controller Minor Alarm Condition
Pulsar Edge Controller Major Alarm Condition
Step 9 Verify Power Plant Set Points
Using the controller, verify all Power Plant
set points are per customer standards
See Pulsar Edge Controller Family Product
Manual for additional controller details
Pulsar Edge Controller
Normal Operation
CC848921016 r02 December 2012 Page 10
663 / 664E Installation Guide

Safety

Safety Statements
Read and follow these statements and those in equipment manuals.
Do not install this equipment over combustible surfaces.
Follow all national and local rules and regulations when making field connections.
Compression Connectors
For installations in the U. S. or Canada, use Listed/Certified compression connectors to terminate
Listed/Certified field-wire conductors where required.
For all installations, apply the appropriate connector to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer’s recommended or approved tooling for that connector.
If the proper connector for the country of installation is not provided, obtain appropriate connectors and follow
manufacturer’s requirements and all local requirements for proper connections.
Torque electrical connections to the values specified on labels or in the product documentation.
Dress cables to avoid damage to the conductors (caused by routing around sharp edges or routing in areas
where wires could get pinched) and undue stress on the connectors.
Size protectors (fuses or circuit breakers) as required by the National Electric Code (NEC) and/or local codes. Refer
to the equipment ratings to assure current does not exceed: Continuous Load (List 1) - 64% of protector rating Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations when making field
connections.
Size field-wired conductors based on listed recommendations, National Electric Code (NEC) and/or local codes
based on 70°C ampacity.
Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
Provide an accessible AC disconnect/protection device to remove AC power from the equipment in the event of an
emergency. This device must open all poles and be connected together.
Equipment and subassembly ports are suitable for connection to intra-building or unexposed wiring or
cabling. The equipment and subassembly ports can be connected to shielded intra-building cabling grounded at both ends.
Alarm contacts are not fused within the equipment. Current limiting protection for these contacts must
be provided by external circuits. Exceeding these maximum ratings could result in fire or damage to the unit. Alarm contacts are rated at 60V and 0.5A unless otherwise noted in the product Specifications section.
In enclosed equipment cabinets, the equipment chassis must be connected directly to the cabinet ac
service ground bus. For applications in huts, vaults, and central offices, the equipment chassis must be connected to the system bonding network.
Use only fuses and circuit breakers specified in the equipment documentation. Use of other parts may
result in injury to personnel or equipment damage.
Use only GMT fuses provided with safety caps.
This equipment operates equally well if installed as part of the Isolated Ground Plane (Isolated Bonding Network) or
the Integrated Ground Plane (Mesh-Bonding Network, aka, Common Bonding Network). Different grounding techniques are equally successful. Adhere to a commonly accepted and consistent grounding approach to ensure personnel safety, network protection, and proper equipment operation. Multiple low impedance paths to Earth ground are essential.
CC848921016 r02 December 2012 Page 11
663 / 664E Installation Guide
One of these two symbols (or equivalent) may be used to identify the presence of
precautions.”
Warning and Safety Symbols
The symbols may sometimes be accompanied by some type of statement, e.g. “Hazardous voltage/energy inside. Risk of injury. This unit must be accessed only by qualified personnel.” Signal words as described below may also be used to indicate the level of hazard
DANGER
WARNING
CAUTION
Indicates the presence of a hazard that will cause death or severe personal injury if the hazard is not avoided.
Indicates the presence of a hazard that can cause death or severe personal injury if the hazard is not avoided.
Indicates the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided.
This symbol identifies the need to refer to the equipment instructions for important information.
These symbols (or equivalent) are used to identify the presence of hazardous ac mains voltage.
This symbol is used to identify the presence of hazardous ac or dc voltages. It may also be used to warn of hazardous energy levels.
rectifier and battery voltages. The symbol may sometimes be accompanied by some type of statement, for example: “Battery voltage present. Risk of injury due to high current. Avoid contacting conductors with uninsulated metal objects. Follow safety
One of these two symbols may be used to identify the presence of a hot surface. It may also be accompanied by a statement explaining the hazard. A symbol like this with a lightning bolt through the hand also means that the part is or could be at hazardous voltage levels.
This symbol is used to identify the protective safety earth ground for the equipment.
This symbol is used to identify other bonding points within the equipment.
This symbol is used to identify the need for safety glasses and may sometimes be accompanied by some type of statement, for example: “Fuses can cause arcing and sparks. Risk of eye injury. Always wear safety glasses.”
CC848921016 r02 December 2012 Page 12
663 / 664E Installation Guide
Precautions
Read and follow these precautions and those in equipment manuals.
The equipment must be installed, serviced, and operated only by professional, skilled and qualified personnel
who have the necessary knowledge and practical experience with electrical equipment and who understand the hazards that can arise when working on this type of equipment.
The equipment may be powered by multiple AC inputs. Ensure that the appropriate circuit protection device for
each AC input being serviced is disconnected before servicing the equipment.
Do not disconnect permanent bonding provisions unless all ac inputs are disconnected.
Batteries may be connected in parallel with the output of the rectifiers. Turning off the rectifiers will not
necessarily remove power from the bus. Make sure the battery power is also disconnected and/or follow safety procedures while working on any equipment that contains hazardous energy/voltage.
High leakage currents may be possible on this type of equipment. Make sure the equipment is properly
safety earth grounded before connecting power.
Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy
and voltages are present in the unit and on the interface cables that can shock or cause serious injury. When equipped with ringer modules, hazardous voltages will be present on the ringer output connectors.
Use the following precautions in addition to proper job training and safety procedures:
Use only properly insulated tools.
Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).
Wear safety glasses. Fuses can produce sparks. High energy levels on buses and distribution components
can produce severe arcing.
Test circuits before touching.
Lock out and tag circuit breakers/fuses when possible to prevent accidental turn on.
Be aware of potential hazards before servicing equipment.
Identify exposed hazardous electrical potentials on connectors, wiring, etc. (note the condition of these
circuits, especially wiring).
Use care when removing or replacing covers; avoid contacting circuits.
Use a personal ESD strap when accessing or removing electronic components.
Electricity produces magnetic fields that can affect implanted medical electronic devices, such as pacemakers.
The strength of the magnetic field depends on the amount of current in the circuit, as well as other conditions (such as number of conductors, placement, and distance from the conductor). DC power and distribution systems, including batteries, which are typically used in telecommunications utility rooms, can operate at high current levels. Personnel with electronic medical devices need to be aware of their restrictions when working around electricity.
CC848921016 r02 December 2012 Page 13
663 / 664E Installation Guide

Revision History

Issue 2 Removed reference to rectifiers, rebrand, reformat
Issue 1 Initial Release
CC848921016 r02 December 2012 Page 14
Loading...