GE NX-591E, NetworX Series Installation And Startup Manual

Page 1
NetworX Series
NX-591E Cellemetry Module
Page 2
TABLE OF CONTENTS
I.
GENERAL DESCRIPTION............................................................................................3
II. ACTIVATION VIA WEBSITE ........................................................................................3
III. ENCLOSURE INFORMATION......................................................................................4
IV. MODULE ADDRESS.....................................................................................................4
V. ENROLLING THE MODULE.........................................................................................5
VI. WIRING THE MODULE.................................................................................................5
VII. TERMINAL DESCRIPTION...........................................................................................5
VIII. UNDERSTANDING THE LIGHTS.................................................................................6
IX. CONNECTION DIAGRAM ............................................................................................7
X. PROGRAMMING THE MODULE ..................................................................................8
A. USING THE LED KEYPAD...........................................................................................8
1. Entering the Program Mode................................................................................8
2. Selecting the Module to Program:.......................................................................8
3. Factory Defaulting the Module ............................................................................8
4. Programming a Location:....................................................................................8
5. Exiting the Program Mode:..................................................................................9
B. USING THE LCD KEYPAD.........................................................................................10
C. PROGRAMMING DATA..............................................................................................10
1. Numerical Data..................................................................................................10
2. Feature Selection Data......................................................................................10
XI. PROGRAMMING INSTRUCTIONS ............................................................................11
Location 0 Programming the Mode...................................................................... 11
Location 1 Feature Selection................................................................................11
Loc 2 –7 When Phone Fault Is Detected 12
Location 2 Events To Report To Central Station..................................................12
Location 3 Special Events To Report To Central Station.....................................12
Location 4 Events To Report To Email ................................................................13
Location 5 Special Events To Report To Email.................................................... 13
Location 6 Events To Report To Pager................................................................ 13
Location 7 Special Events To Report To Pager...................................................14
Loc 8 –13 When Phone Line Is Good.........................................................................15
Location 8 Events To Report To Central Station..................................................15
Location 9 Special Events To Report To Central Station.....................................15
Location 10 Events To Report To Email ................................................................15
Location 11 Special Events To Report To Email....................................................16
Location 12 Events To Report To Pager................................................................16
Location 13 Special Events To Report To Pager...................................................17
XII. PROGRAMMING WORKSHEETS..............................................................................18
XIII. SPECIFICATIONS.......................................................................................................24
2
NX-591E
Page 3

I. GENERAL DESCRIPTION

A
The NX-591E is a microprocessor-controlled Cellemetry interface used to connect the NetworX series of control panels to AMPS cellular network for event repor ting. The NX -591E can be used for pri mary, backup, or additional reporting when used in conjunction with the panel communicator or other optional reporting modules. Flexible event selection allows only specific messages to be reported, keeping airtime to a minimum. The NX-591E has 14 LEDs to provide extensive diagnostic and setup information.

II. ACTIVATION VIA WEBSITE

The cellemetry unit can be activated and managed via our web site address:
www.gesecurity.com/cellemetry
To set up a new dealer account
ctivation & management of units.
If your company already has an account set up, proceed to step 1 below. Otherwise, you must first set up a dealer account.
1. At the bottom of the web page, click on the activation link w hich takes you to th e member
login screen.
2. Type your Login Name and Password, then click
NX-591E
Login
3
Page 4
3. Several options are available on the left side of the next screen .
a. Activate Unit” -- This will activate the cellemetry unit. Enter the serial number of the
cellemetry module (located on the front of the unit).
10 digits.
Verify that the Service Plan Description indicates, “Security Plan”. Click
Note: The serial number must contain
“Activate”. Multiple units can be added from this screen.
b. Edit Unit Settings” -- Complete the information based on the way you want
to configure the reporting for the u nit. o
Select the unit you have just activated
o Add the Account Name to the Unit Name field o Select your Notification Method 1 o Change TX Retries to 8 (maximum allowed) o Go to the appropriate field for the Method 1 that was chosen (Alpha, Email or Central Station)
If Alpha Pager, the PIN number is required If Central Station, enter the Receiver Phone Number & Central Station A/C
number
o Select a 2 o Notification Enabled should read “Yes”.
o Click “Update” (bottom of page)
nd
Notification Type, if needed.

III. ENCLOSURE INFORMATION

Inside the can, several 2-hole d insertion points have been const ructed. This allows for either vertical or horizontal placement of the modules.
Notice that the insertion poi nts have two sizes of holes -- a larger hole and a smaller hole.
Diagram 1
the PC Board will be seated. The end with the half-moon protrusion fits into the larger hole. The smaller hole is for the screw.
Diagram 2
point, grooved edge downward. The half-moon protrusion will be in the large hole. It does not require force. Insert one of the provided screws into the smaller hole (from inside the can) to secure it in place. A screwdriver should reach through the notch that runs the length of the guide to tighten the screw. The second PCB guide should be positioned opposite of the first (grooved edge up) and placed in the lower insertion point, using the same procedures described above. Once mounted, screw it in securely.
Diagram 3
guides.
NOTE: Older style enclosures did not provide an exit hole for the 2dB “Rubber Duck” antenna included with the Cellemetry module. In such cases, you must either drill a new hole on top of th e can or use an optional external antenna such as the 5dB “Mag Mount”.
: The black plastic PCB guides are grooved on one edge where
: Place the first black plastic PCB guide in the top ins ertion
: The PC board should slide freely in the grooves of both

IV. MODULE ADDRESS

The cellemetry module has a fixed address of 76. When programming the module, enter the Program Mode and select the device address as 76. (See "PROGRAMMING THE MODULE", page 8.)
4
NX-591E
Page 5

V. ENROLLING THE MODULE

The NetworX control panels have the ability to automatically find and store in memory the presence of all keypads, zone expanders, wireless receivers, and any other device on the keypad buss. This allows these devices to be supervised by the control panel. To enroll the devices, enter the Program Mode of the NX control panel using the procedure outlined in the NX Installation Manual. When the Program Mode is exited, the NX control will automatically enroll all the devices. The enrolling pr ocess takes about 12 seconds, during which time the AService@ LED will illuminate. When using the LCD Keypad, the "Service Required" message will be displayed. User codes will not be accepted during the enrolling process. Once a module is enrolled, if the contro l panel does not detect it, the AService@ LED will illuminate.

VI. WIRING THE MODULE

MAXIMUM WIRE RUN
LENGTH
(IN FEET)
100 16
10 20 50 18
(Connected To NX Control Panel or NX320E Power Supply)
WIRE GAUGE

VII. TERMINAL DESCRIPTION

TERMINAL DESCRIPTION
POS
COM
DATA
TAMPER
Connect to the KP POS terminal of the panel. Refer t o “Specificati ons” in this manual for power consumption. Connect to the KP COM terminal of the panel. Connect to the KP DATA terminal of the panel. Normally closed
NX-591E
5
Page 6

VIII. UNDERSTANDING THE LIGHTS

The module has 14 green LEDs along the back of the board. These LEDs provide valuable information about the status of the module as shown in the following table.
Table VIII-1
LED DESCRIPTION
DS3 – DS6 LEDs flashing = Network failure DS3 – DS6 LEDs off = Normal idle condition (DS3 & DS4) (DS5 & DS6) Flashing alternately = Shut do wn
DS1 DS3 DS4
DS5
DS6
XMIT
POOR
FAIR
GOOD
BEST
SVC
SVC2
RXD TXD
Indicates proper circuitry operation ON steady = Reading MINs from cellemetr y ra di o ON steady = Looking for cellular service ON steady = Sending a network verification me ss ag e pa cket to tower Flashing = Waiting for acknowledgement ON = Sending data message to tower Flashing = Waiting for acknowledgement
Message packet being transmitted to tower
The LEDs will either be Off, On, Flashing slow, or Flashing Fast depending on the dB of the signal. Refer to Table VIII-2 for details.
Cellular service available Two or more control channels available Data being received from cellemetry radio Data being sent to cellemetry radio
Table VIII-2
LED Key
0 = OFF S = SLOW F = FAST 1 = ON
6
dB POOR FAIR GOOD BEST
-114 -107 0 0 0 0
-106 -104 S 0 0 0
-103 -101 F 0 0 0
-100 -98 1 0 0 0
-97 -95 1 S 0 0
-94 -92 1 F 0 0
-91 -89 1 1 0 0
-88 -86 1 1 S 0
-85 -83 1 1 F 0
-82 -80 1 1 1 0
-79 -77 1 1 1 S
-76 -74 1 1 1 F
-73 higher
1 1 1 1
NX-591E
Page 7

IX. CONNECTION DIAGRAM

NX-591E
7
Page 8

X. PROGRAMMING THE MODULE

A. USING THE LED KEYPAD

ACTION

1. Entering the Program Mode

    Go To Program Code

2. Selecting the Module to Program:

RESULT
Enters the Program Mode. Stay, Chime, Exit, Bypass & Cancel LEDS will
flash. If the "Go To Program Code" is valid, the
Factory Default is

"Service" LED will flash and the 5 function LEDs will illuminate steady. You are now in the Program Mode and ready to select the module to program .
The address of this cellemetry module is 76.
#
The Armed LED will illuminate while it is waiting for a programming location to be entered.

3. Factory Defaulting th e M o du le

    #

4. Programming a Location:

Once the number of the module to be programmed has been entered, the "Armed" LED will illuminate while it is waiting for a programming location to be entered.
If an attempt is made to program an invalid entry for a particular
segment, the keypad sounder will emit a triple error beep (beep, beep, beep), and remain in that segment awaiting a valid entry.
To Enter a Location:
[location] #
8
The keypad will beep 3 times indicating that the loading is in progress. Remember you will erase any values you may have enter ed previously.
The Armed LED will flash. If the location is valid, the "Armed" LED will extinguish, the "Ready" LED will illuminate, and the zone LED’s will show the data for the first segment of this location.
NX-591E
Page 9
To Change Location Data:
[changed data]  
NOTE: These steps are repeated until the last segment is reached.
To Exit a Location:
#
To Review The Data:
[location] #
 
The "Ready" LED will flash to indicate a data change in process and will continue until the data is saved.
The new data is saved. The keypad will advance to the next segment and
display its data.
Exits from this location. The “Ready” LED will extinguish. The "Armed" LED will illuminate waiting for a new programming location to be entered.
The Armed LED will flash. If the location number is valid, the "Armed" LED will extin guish , the "R eady" LED will illuminate, and the zone LEDs will show the binary data for the first segment of this location.
(Do not enter data.) The next segment is displayed. Each time
pressed, the data of the next segment will be displayed for review.
r is
Shortcuts:

5. Exiting the Program Mode:

EXIT
Previous location.
Same location.
Next sequential location.
Exits this programming level.
NX-591E
9
Page 10
B.

USING THE LCD KEYPAD

All steps required for programming are the same as the aforemen tioned LED keypad. The LCD
keypad display will prompt you for the data required. While in the programming mode, and not in
a location, the number in parenthesis is the location you were pre viously changing. For example,
if the display reads, "Enter location, then # (5)", it is reminding you that location 5 was the last
location you programmed. Refer also to "Programming Data" which follows.

C. PROGRAMMING DATA

Programming data is always one of three types. One type of data is numerical, which can take
on values from 0 -15, 0 - F, o r 0 - 255 de pen ding on t he s egm ent si ze. T he othe r t ype of d ata,
feature selection data, is used to turn features on/off. It can also be used as character data for
Internet names. Use the following procedures with these data types:

1. Numerical Data

Numerical data is programmed by entering a number from 0-255 on the numeric keys of the system keypad. To view the data in a location, a binary process is u sed. With this p rocess, the LED=s for zones 1 through 8 are utilized, and the numeric equivalents of their illuminated LED=s are added together to determine the data in a programming location. The numeric equivalents of these LED=s are as follows:
Zone 1 LED = 1 Zone 3 LED = 4 Zone 5 LED = 16 Zone 7 LED = 64 Zone 2 LED = 2 Zone 4 LED = 8 Zone 6 LED = 32 Zone 8 LED = 128
Example: If the numerical data to be programmed in a location is "66", press [6]-[6] on the keypad. The LED=s for Zone 2 and Zone 7 will become illuminated i ndicating 66 is in that location (2 + 64 = 66). Once the data is programmed, press [r] to enter the data and advance to the next segment of that location. After the last segment of a location is programmed, pressing [r] will exit that location, turn the "Ready" LED off, and the "Armed" LED on. As before, you are now ready to enter another programming location. If an attempt is made to program a number too large for a particular segment, the keypad sounder will emit a triple beep, indicating an error, and remain in that segment awaiting a valid entry.

2. Feature Selection Data

Feature selection data will display the current condition (on or off) of eight features associated with the programming location and segment selected . Pressing a button on the touchpad (1 thru 8) that corresponds to the "feature number" within a segment will toggle (on/off) that feature. Pressing any numeric key between [1] and [8] for selection of a feature will make the corresponding LED illuminate (feature ON). Press the number again, and the LED will extinguish (feature OFF). You will see that numerous features can be selected from within one segment. For instance, if all eight features of a segment are desired, pressing [1]-[2]-[3]- [4]-[5]-[6]-[7]-[8] will turn on LED's 1 thru 8 as you press the keys, indicating that those features are enabled. LCD Keypad Users Note
: The numbers of the enabled features will
be displayed. However, the features not en abled w ill display a hyphen (-). After the
desired setting of features is selected for this segment, press [r]. This will enter the data and automatically advance to the next segment of the location. When you are in the last segment of a location and press [r] to enter the data, you will exit that location. This will now turn the "Ready" LED off and the "Armed" LED on. You are now ready to ente r another programming location.
10
NX591E
Page 11

XI. PROGRAMMING INSTRUCTIONS

Location 0 Programming the Mode
5 segments Numeric Data
This location contains the System Identification Number (SID). Factory default is 0-0-0-0-0 for AutoSID.
Location 1 Feature Selection
4 segments Feature Selection Data Segment 1 contains the options to be programmed for the functioning of this module. Factory default
for all options is OFF.
Option Description ON
1 2 3 4 5 6 7 8
Notes:
Segment 2 programs for Host Acknowledgement requirements. Factory default f or all option s is OFF.
Option Description ON
1 2 3 4
5-8
Segments 3 and 4 are reserved for future use.
Format SIA Test Signal Daily System Preference Use “A” or “B” side only “B” Side Preference “B” Side (if Opt 3 is ON) Alternate MIN Disabled Disable Cellular Service LEDs Disabled Enable Tamper Switch Enabled Disable SIA DCS Area Modifier
Daily test will be performed 24 hours (+/- 10 minutes) from time this option is programmed.
Weekly test will be performed 168 hours (+/- 10 minutes) from time this option is programmed.
Some older SIA DCS compatible receivers may not support the use of area (partition) modifiers.
In such cases, the area modifier must be disabled (Option 8 ON).
Central Station messages Enabled Email messages Enabled Pager messages Enabled Periodic test signals Enabled Reserved
Disabled
OFF
Contact ID Weekly No Preference “A” Side Enabled Enabled Disabled Enabled
OFF
Disabled Disabled Disabled Disabled
NX-591E
11
Page 12
Loc 2 –7 When Phone Fault Is Detected Location 2 Events To Report To Central Station
(Phone fault detected) 16 segments of Feature Selection Data
Reporting must be enabled in the control panel for this location to function
properly.
This location selects the partition(s) to include when reporting to the Central Station. To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 –16. Factory default is all partitions ON for Segment 1; All partitio ns are defaulted OFF for Segments 2 -16.
Table XI-1
1 = Partition 1 3 = Partition 3 5 = Partition 5 7 = Partition 7 2 = Partition 2 4 = Partition 4 6 = Partition 6 8 = Partition 8
SEGMENT DESCRIPTION SEGMENT DESCRIPTION
1 2 3 4 5
6 7 8
Alarms
Open/Close Bypass Zone Trouble Power Trouble (AC Failure or Low Battery) Siren & Telephone Fault Test Reports Program, Download & Log Full
9 10 11 12 13
14 15 16
Location 3 Special Events To Report To Central Station
(Phone fault detected) 8 segments of Feature Selection Data This location selects the partition(s) to include when reporting Sp ecial Events to the Central Statio n.
To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 – 8. Factory default is all partitions ON for Segments 2 and 4; all partitions OFF for Segments 1 an d 3.
SEGMENT DESCRIPTION
1 2 3 4
5-8
Alarm Restores
Telephone Fault
Start Download
Fail to Communicate, Data Lost
Reserved
Tampers Short Circuit & Ground Fault Sensor Lost Sensor Low Battery Expander Trouble
Failure To Communicate Zone Activity Monitor Reserved
12
NX591E
Page 13
Location 4 Events To Report To Email
(Phone fault detected) 16 segments of Feature Selection Data
Reporting must be enabled in the control panel for this location to function
properly.
This location selects the partition(s) to include when reporting to email. To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 –16. Factory default is all partiti ons OFF
SEGMENT DESCRIPTION SEGMENT DESCRIPTION
1 2 3 4 5
6 7 8
Alarms Open/Close Bypass Zone Trouble Power Trouble (AC Failure or Low Battery) Siren & Telephone Fault Test Reports Program, Download & Log Full
9 10 11 12 13
14 15 16
Location 5 Special Events To Report To Email
(Phone fault detected) 8 segments of Feature Selection Data This location selects the partition(s) to include when reporting Special Events to email. To exclude any
partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 – 8. Factory default is all par titi o ns OFF.
SEGMENT DESCRIPTION
1 2 3 4
5-8
Alarm Restores Telephone Fault Start Download Fail to Communicate, Data Lost Reserved
Location 6 Events To Report To Pager
(Phone fault detected) 16 segments of Feature Selection Data
Tampers Short Circuit & Ground Fault Sensor Lost Sensor Low Battery Expander Trouble
Failure To Communicate Zone Activity Monitor Reserved
Reporting must be enabled in the control panel for this location to function
properly.
This location selects the partition (s) to include w hen reporting to a pager. To ex clude any par tition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the par tition(s) to include for each type of repo rt found in Segments 1 –16. Factory default is all partiti on s OF F.
NX-591E
13
Page 14
SEGMENT DESCRIPTION SEGMENT DESCRIPTION
1 2 3 4 5
6 7 8
Alarms Open/Close Bypass Zone Trouble Power Trouble (AC Failure or Low Battery) Siren & Telephone Fault Test Reports Program, Download & Log Full
9 10 11 12 13
14 15 16
Tampers Short Circuit & Ground Fault Sensor Lost Sensor Low Battery Expander Trouble
Failure To Communicate Zone Activity Monitor Reserved
Location 7 Special Events To Report To Pager
(Phone fault detected) 8 segments of Feature Selection Data This location selects the partition(s) to include when reporting Special Events to a pager. To exclude
any partition from reporting, simply turn o ff the LED co rresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 – 8. Factory default is all partitions OFF.
SEGMENT DESCRIPTION
1 2 3 4
5-8
Alarm Restores Telephone Fault Start Download Fail to Communicate, Data Lost Reserved
14
NX591E
Page 15
Loc 8 –13 When Phone Line Is Good
Location 8 Events To Report To Central Station
(Phone line is good) 16 segments of Feature Selection Data
Reporting must be enabled in the control panel for this location to function
properly.
This location selects the partition(s) to includ e when reporting to the Cen tral Station when the phone line is good. To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 –16. Factory default is all partitions OFF.
SEGMENT DESCRIPTION SEGMENT DESCRIPTION
1 2 3 4 5
6 7 8
Alarms Open/Close Bypass Zone Trouble Power Trouble (AC Failure or Low Battery) Siren & Telephone Fault Test Reports Program, Download & Log Full
9 10 11 12 13
14 15 16
Location 9 Special Events To Report To Central Station
(Phone line is good) 8 segments of Feature Selection Data This location selects the partition(s) to include when reporting Special Events to the Central Station
when the phone line is good. To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for ea ch type of report found in Segments 1 – 8 . Factory default is all partitions OFF.
SEGMENT DESCRIPTION
1 2 3 4
5-8
Alarm Restores Telephone Fault Start Download Fail to Communicate, Data Lost Reserved
Location 10 Events To Report To Email
(Phone line is good) 16 segments of Feature Selection Data
Tampers Short Circuit & Ground Fault Sensor Lost Sensor Low Battery Expander Trouble
Failure To Communicate Zone Activity Monitor Reserved
Reporting must be enabled in the control panel for this location to function
properly.
This location selects the partition(s) to include when reporting to email when the phone line is good. To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 –16. Factory default is all partitions OFF
NX-591E
15
Page 16
SEGMENT DESCRIPTION SEGMENT DESCRIPTION
1 2 3 4 5
6 7 8
Alarms Open/Close Bypass Zone Trouble Power Trouble (AC Failure or Low Battery) Siren & Telephone Fault Test Reports Program, Download & Log Full
9 10 11 12 13
14 15 16
Tampers Short Circuit & Ground Fault Sensor Lost Sensor Low Battery Expander Trouble
Failure To Communicate Zone Activity Monitor Reserved
Location 11 Special Events To Report To Email
(Phone line is good) 8 segments of Feature Selection Data This location selects the partition(s) to include when reporting Special Events to email when the phone
line is good. To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the correspond ing number of the partition(s) to include for each type of report found in Segments 1 – 8. Factory default is all partitions OFF.
SEGMENT DESCRIPTION
1 2 3 4
5-8
Alarm Restores Telephone Fault Start Download Fail to Communicate, Data Lost Reserved
Location 12 Events To Report To Pager
(Phone line is good) 16 segments of Feature Selection Data
Reporting must be enabled in the control panel for this location to function
properly.
This location selects the partition(s) to include when reporting to a pager when the phone line is good. To exclude any partition from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 –16. Factory default is all partitions OFF
SEGMENT DESCRIPTION SEGMENT DESCRIPTION
16
1 2 3 4 5
6 7 8
Alarms Open/Close Bypass Zone Trouble Power Trouble (AC Failure or Low Battery) Siren & Telephone Fault Test Reports Program, Download & Log Full
9 10 11 12 13
14 15 16
Tampers Short Circuit & Ground Fault Sensor Lost Sensor Low Battery Expander Trouble
Failure To Communicate Zone Activity Monitor Reserved
NX591E
Page 17
Location 13 Special Events To Report To Pager
(Phone line is good) 8 segments of Feature Selection Data This location selects the part ition(s) to i nclude when reporting Special Events to a pager when the
phone line is good. To exclude any partitio n from reporting, simply turn off the LED corresponding to that particular partition. Using Table XI-1 on page 12, enter the corresponding number of the partition(s) to include for each type of report found in Segments 1 – 8. Factory default is all partitions OFF.
SEGMENT DESCRIPTION
1 2 3 4
5-8
Alarm Restores Telephone Fault Start Download Fail to Communicate, Data Lost Reserved
SYSTEM NOTES
NX-591E
17
Page 18

XII. PROGRAMMING WORKSHEETS

DEFAULTS ARE SHOWN IN BOLD ITALICS
LOC PG SEG DESCRIPTION DEFAULT DATA
0 11 SYSTEM ID (all 0’s = AutoSID) 1 11 1 FEATURE SELECTION
1 = SIA Format (Off = Contact ID) 2 = Daily Test Signal (Off = Weekly) 3 = System Preference (Off = No preference) 4 = “B” Side Preference (Off = “A” side) 5 = Disable alternate MIN 6 = Disable cellular service LEDs 7 = Enable tamper switch 8 = Disable SIA DCS area modifier 2 HOST ACKNOWLEGEMENT REQUIRED 1 = Host Ack for Central Station messages 2 = Host Ack for email messages 3 = Host Ack for pager messages 4 = Host Ack for periodic test signals 5-8=Reserved 3-4 Reserved
LOC PG SEG DESCRIPTION PARTITION
2 12 REPORTING EVENTS TO CENTRAL STATION (Phone line fault detected)
2 Open / Close 3 Bypass 4 Zone Trouble 5 Power Trouble (AC Fail or Low Battery) 6 Siren & Telephone Fault 7 Test Reports 8 Program, Download & Log Full 9 Tampers 10 Short Circuit & Ground Fault 11 Sensor Lost 12 Sensor Low Battery 13 Expander Trouble 14 Fail to Communicate 15 Zone Activity Monitor 16 Reserved
18
1 Alarms
0-0-0-0-0
OFF OFF OFF OFF OFF OFF OFF OFF
OFF OFF OFF OFF
1 2 3 4 5 6 7 8
_ _ _ _ _
NX591E
Page 19
LOC PG SEG DESCRIPTION PARTITION
3 12 REPORTING SPECIAL EVENTS TO CENTRAL STATION (Phone line fault
detected)
1 2 3 4 5 6 7 8
1 Alarm Restores
2 Telephone Fault
3 Start Download
4 Fail to Communicate, Data Lost
5-8 Reserved
4 13 REPORTING EVENTS TO EMAIL (Phone line fault detected)
1 2 3 4 5 6 7 8
1 Alarms 2 Open / Close 3 Bypass 4 Zone Trouble 5 Power Trouble (AC Fail or Low Battery) 6 Siren & Telephone Fault 7 Test Reports 8 Program, Download & Log Full 9 Tampers 10 Short Circuit & Ground Fault 11 Sensor Lost 12 Sensor Low Battery 13 Expander Trouble 14 Fail to Communicate 15 Zone Activity Monitor 16 Reserved
5 13 REPORTING SPECIAL EVENTS TO EMAIL (Phone line fault detected)
1 2 3 4 5 6 7 8
1 Alarm Restores 2 Telephone Fault 3 Start Download 4 Fail to Communicate, Data Lost 5-8 Reserved
NX-591E
19
Page 20
LOC PG SEG DESCRIPTION PARTITION
6 13 REPORTING EVENTS TO PAGER (Pho ne line fault detected)
1 2 3 4 5 6 7 8
1 Alarms 2 Open / Close 3 Bypass 4 Zone Trouble 5 Power Trouble (AC Fail or Low Battery) 6 Siren & Telephone Fault 7 Test Reports 8 Program, Download & Log Full 9 Tampers 10 Short Circuit & Ground Fault 11 Sensor Lost 12 Sensor Low Battery 13 Expander Trouble 14 Fail to Communicate 15 Zone Activity Monitor 16 Reserved
7 14 REPORTING SPECIAL EVENTS TO PAGER (Phone line fault detected)
1 2 3 4 5 6 7 8
1 Alarm Restores
2 Telephone Fault 3 Start Download 4 Fail to Communicate, Data Lost 5-8 Reserved
8 15 REPORTING EVENTS TO CENTRAL STATION (Phone line is good)
1 2 3 4 5 6 7 8
1 Alarms 2 Open / Close 3 Bypass 4 Zone Trouble 5 Power Trouble (AC Fail or Low Battery) 6 Siren & Telephone Fault 7 Test Reports 8 Program, Download & Log Full 9 Tampers 10 Short Circuit & Ground Fault 11 Sensor Lost 12 Sensor Low Battery 13 Expander Trouble 14 Fail to Communicate 15 Zone Activity Monitor 16 Reserved
20
NX591E
Page 21
LOC PG SEG DESCRIPTION PARTITION
9 15 REPORTING SPECIAL EVENTS TO CENTRAL STATION (Phone line is good)
1 2 3 4 5 6 7 8
1 Alarm Restores 2 Telephone Fault 3 Start Download 4 Fail to Communicate, Data Lost 5-8 Reserved
10 15 REPORTING EVENTS TO EMAIL (Phone line is good)
1 2 3 4 5 6 7 8
1 Alarms 2 Open / Close 3 Bypass 4 Zone Trouble 5 Power Trouble (AC Fail or Low Battery) 6 Siren & Telephone Fault 7 Test Reports 8 Program, Download & Log Full 9 Tampers 10 Short Circuit & Ground Fault 11 Sensor Lost 12 Sensor Low Battery 13 Expander Trouble 14 Fail to Communicate 15 Zone Activity Monitor 16 Reserved
11 16 REPORTING SPECIAL EVENTS TO EMAIL (Phone line is good)
1 2 3 4 5 6 7 8
1 Alarm Restores 2 Telephone Fault 3 Start Download 4 Fail to Communicate, Data Lost 5-8 Reserved
NX-591E
21
Page 22
LOC PG SEG DESCRIPTION PARTITION
12 16 REPORTING EVENTS TO PAGER (Phone line is good)
1 2 3 4 5 6 7 8
1 Alarms 2 Open / Close 3 Bypass 4 Zone Trouble 5 Power Trouble (AC Fail or Low Battery) 6 Siren & Telephone Fault 7 Test Reports 8 Program, Download & Log Full 9 Tampers 10 Short Circuit & Ground Fault 11 Sensor Lost 12 Sensor Low Battery 13 Expander Trouble 14 Fail to Communicate 15 Zone Activity Monitor 16 Reserved
13 17 REPORTING SPECIAL EVENTS TO PAGER (Phone line is good)
1 2 3 4 5 6 7 8
1 Alarm Restores
2 Telephone Fault 3 Start Download 4 Fail to Communicate, Data Lost 5-8 Reserved
22
NX591E
Page 23
ORDERING INFORMATION
PART #
NX-591E Cellemetry Module NX-108E 8 Zone LED Horizontal Keypad NX-591E­MAG MOUNT P-0005 2dB “Rubber Ducky”
NX-8E-KIT
NX-8E-KIT-8
NX-8E NX-8E Control Only NX-8-KIT
NX-8 NX-8 Control Onl y
DESCRIPTION
Magnetic Mount Antenna NX-116E 16 Zone LED Horizontal
Antenna NX-8E Control, NX-108E Keypad, 40VA Transformer
NX-8E Control, NX-1448E Keypad, 40VA Transformer
NX-8 Control, NX-108E Keypad, 40VA Transformer
PART #
NX-124E 24 Zone LED Horizontal NX-148E Alphanumeric LCD Keypad
NX-1308E 8 Zone LED Door Design
NX-1316E 16 Zone LED Door Design
NX-1324E
NX-1448E
Keypad Keypad
Keypad
Keypad
24 Zone LED Door Design Keypad
48 Zone Fixed Language Icon Keypad
DESCRIPTION
NOTES
Page 24

XIII. SPECIFICATIONS

OPERATING POWER
12VDC Supplied from NX Control Panel or NX-320E Power Supply
POWER CONSUMPTION
Standby w/ Service LEDs disabled 70mA Max
Standby w/ Service LEDs enabled 90mA Max
Transmission Burst (<1 second) 1300mA Max
OPERATING TEMPERATURE 32 to 120 degrees F DIMENSIONS 2.40" Wide
SHIPPING WEIGHT 1 lb.
4.40" High
1.20" Deep
Main Phone 800-727-2339 Technical Support 888-437-3287 Outside the US 903-845-6941 Sales & Literature 800-547-2556 Main Fax 903-845-6811 Web: www.gesecurity.com
NX591E INSTALLATION MANUAL
NX591EIE05 REV. E (May 2005)
Loading...