Gaylord GRC-5000 User Manual

4.6 (5)
Gaylord GRC-5000 User Manual

MODEL“GRC-5000”

CONTROL CABINET FOR WATER WASH VENTILATORS,

WATER WASH VENTILATORS WITH UV,

POLLUTION CONTROL UNITS, and GAYLORD DUCT SUMPS

WITH BUILT-IN BACKFLOW PREVENTION

GENERAL SPECIFICATIONS

DESCRIPTION: Wash control Model GRC-5000-_____________ shall be furnishedtoreplaceelectricalcomponentsforoperationoftheventilator(s), pollution control unit(s) and/or duct sump(s), if specified. The electrical controlshallincludeaprogrammablelogiccontroller(PLC)forcontrollingall functionsoftheexhaustandsupplyfans,washcycle,damperoperationand internalfiresystem.Thecontrolshallbecapableofwashingupto5groupsof ventilators/pollutioncontrolunitsinsequencewithadelayperiodbetween each group. The control shall include a programmable digital interface module that includes“Start Fan”,“StartWash”, programming buttons and a digital display that shows current operating mode. Programming features shall include 1) Setting length of wash cycles, 2) Setting the length of the delaybetweeneachwashgroup,3)SettingautomaticoperationofStartFan and StartWash times for each day of operation, 4) Lockout of all operations for days not operating. The control shall be equipped with a battery backup to hold the clock and memory for programming functions. It shall also include volt-free contacts for interfacing exhaust and supply fans with a building management system (BMS) or other control circuits, and volt-free contacts for the fire cycle for interconnection to the building fire alarm or monitoring systems. The control shall include contacts to remotely Start and Stop the exhaust fans/supply fans and wash when interfacing with a BMS. It shall monitor “AutoStart” sensors mounted in the ventilator(s), if equipped, and automatically start the exhaust and supply fan(s) if cooking occurs when the fans are off and the temperature in the hood exceeds the thermostat set point. All components to be field wired by applicable trades. Control shall be UL508 listed.

GRC-5000

APPLICATION

Water wash ventilators, Water wash ventilators with Pollution Control

Units, Gaylord Duct Sumps

NUMBER REQUIRED

One control cabinet can be used for up to 5 wash groups. However, the amount of ventilator footage permitted on any one group has limitations.

Any number of exhaust fans and supply fans can be connected to the controlcabinetifsimultaneousoperationisdesired.Iftherearetwoormore groups of ventilators, each with their own exhaust fan, and independent operation of the fans is desired consult factory for options.

FEATURES

AutoStart capable to meet IMC 507.2.1.1

Remotely start/stop fans from Building Management System

Built-in time clock

OPTIONAL EQUIPMENT:

Low Detergent Monitor

Thecontrolshallincludeadetergentflowswitchtomonitordetergent flow and display a message on the command center to notify of low detergent.

Continuous Cold Water Mist

Continuous cold water mist ventilators are typically used over solid fuel burning equipment.

Control cabinet shall include provisions for operating continuous cold water mist ventilator(s) including shut-off valve, solenoid valve, pressure regulator and pressure gauge.

Terminal Input/Outputs

Voltage

120VAC POWER

 

+24VDC POWER

 

FIRE SYSTEM DRY CONTACTS

N/A

(OPEN IN FIRE MODE)

 

ALARM DRY CONTACTS

N/A

EXHAUST FAN DRY CONTACTS

N/A

SUPPLY FAN DRY CONTACTS

N/A

WASH MODE DRY CONTACTS

N/A

THERMOSTAT RETURN

120 Voltage

LOW DETERGENT FLOW SW

120 Voltage

EXT FIRE MODE

120 Voltage

120VAC PWR – 120V RTN

120 Voltage

120VAC PWR – 120V RTN

120 Voltage

SUPPLY FAN --

120 Voltage

LOCAL DETERGENT PUMP

 

Terminal Input/Outputs

Voltage

SPARE --

120 Voltage

REMOTE DETERGENT PUMP

 

LOCAL DET FLOW SW --

120 Voltage

FIRE SWITCH

 

DAMPER MOTOR -- MASTER

120 Voltage

SOLENOID/SOLENOID DRAIN

 

SOLENOID #1 -- SOLENOID #2

120 Voltage

SOLENOID #3 -- SOLENOID #4

120 Voltage

SOLENOID #5 – SPARE

120 Voltage

DISABLE WASH -

24 Voltage

WASH PERMISSION

 

REMOTE FAN START -

24 Voltage

REMOTE WASH START

 

REMOTE FAN/WASH START -

24 Voltage

REMOTE CANCEL

 

+24VDC - +24VDC

24 Voltage

The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials.