Gaylord C-7000 Installation Manual

4.6 (8)

Rev 03

Issue Date: 4-25-2012

Certified Service Agency Manual

For

OPERATION, MAINTENANCE & INSTALLATION of

MODEL C-7000 COMMAND CENTER and

GPC-7000 SERIES WASH CONTROL CABINET

GAYLORD INDUSTRIES

10900 SW Avery Street – Tualatin, Oregon 97062 USA

Email: info@gaylordusa.com Toll Free 800-547-9696 – Fax 5023-692-6048 www.gaylordusa.com

All rights reserved. No part of this book may be reproduced, stored in a retrieval system, or transmitted in any form by an electronic, mechanical, photocopying, recording means or otherwise without prior written permission of Gaylord Industries.

©Copyright 2012, Gaylord Industries

The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials

Additional Copies $25.00 Each

Gaylord C-7000 Installation  Manual

Page iv _________________________________________________________________________________

This Page Intentionally left Blank

_______________________________________

Page v

Table of Contents

Chapter 1 – Introduction

Introduction ……………………………………………………………………………………………………………………….. 1-1 Model Number Sequence and Explanation …………………………………………………………………………. 1-3 Functions and Features of the Command Center ………………………………………………………………… 1-5

Chapter 2 – Principles of Operation – C-7000 Command Center

Level 1, Operator Functions

Overview ……………………………………………………………………………………………………………………………. 2-1 Access to Operate Program ………………………………………………………………………………………………… 2-1 Basic Touch Screen Functions …………………………………………………………………………………………….. 2-2 Starting the Exhaust Fan – Manual Operation …………………………………………………………………….. 2-3 Stopping the Exhaust Fan – Manual Operation …………………………………………………………………… 2-5 Wash Cycle Notification and Monitoring …………………………………………………………………………….. 2-7 UV System Monitoring ……………………………………………………………………………………………………….. 2-12 PCU (Pollution Control Unit) Monitoring …………………………………………………………………………….. 2-14 Fire Extinguishing System Monitoring (External Fire Mode) ………………………………………………… 2-16 Ventilator Fire Mode Monitoring (Internal Fire Mode) ………………………………………………………. 2-17 Service Information ……………………………………………………………………………………………………………. 2-18 Detergent Ordering Information …………………………………………………………………………………………. 2-19

Level 2, Owner Service Functions

Accessing Level 2 for the First Time …………………………………………………………………………………….. 2-20 Creating a New Level 2 Password ……………………………………………………………………………………….. 2-22 Programming the Time of Day and Day of Week …………………………………………………………………. 2-23 Programming the Wash Cycles for Model ELXC Series Ventilators ……………………………………….. 2-26 Programming the Equipment Duty and the Length of the Wash Cycles ……………………………….. 2-28 Programming Automatic Start and Stop of the Exhaust Fan …………………………………………………. 2-32 Programming Automatic Start and Stop of the Exhaust Fan for the Same Time Everyday ……..2-33 Programming Automatic Start and Stop of the Exhaust Fan for Different Times Each Day …….2-37

Checking Total Counts (Tracking Critical Functions) …………………………………………………………….. 2-41 Testing Wash Cycles ……………………………………………………………………………………………………………. 2-43 Programming Delay Times Between Wash Cycles ………………………………………………………………… 2-47 Programming the Wash Cycle for Model CG3 Series Ventilators …………………………………………. 2-48 Programming the Length of the Wash Cycle and Equipment Duty for CG3 Series ……………….. 2-50

Level 3, Gaylord Service Functions

Access Level 3 …………………………………………………………………………………………………………………….. 2-52 Recommended Sequence of Programming …………………………………………………………………………. 2-53 Programming CG3 Mode …………………………………………………………………………………………………….. 2-54

Programming Damper Delay Mode …………………………………………………………………………………….. 2-55

Programming UV Mode ………………………………………………………………………………………………………. 2-56 Programming Number of Washes ……………………………………………………………………………………….. 2-57 Programming the Plenum Type …………………………………………………………………………………………… 2-60

Page vi____________________________________________________________________________

Table of Contents - Cont

Level 3, Gaylord Service Functions – Cont.

Programming Autostart ………………………………………………………………………………………………………. 2-62 Programming Local / Remote Detergent Pump ……………………………………………………………………. 2-64 Programming the Number of ESP Power Packs ……………………………………………………………………. 2-66 Checking Total Counts (Tracking Critical Functions) …………………………………………………………….. 2-67 Changing the Owner Service Function Password …………………………………………………………………. 2-69

Chapter 3 – Tables, Charts and Labels

Frequency and Length of Wash Cycle Chart for Model ELXC Series Ventilators ……………………. 3-1 Frequency and Length of Wash Cycle Chart for Model ELXC Series with PCU ………………………. 3-2 Frequency and Length of Wash Cycle Chart for Model CG3 Series Ventilators …………………….. 3-3

Frequency and Length of Wash Cycle Chart for Model CG3 Series with PCU ……………………….. 3-4 Detergent Consumption Chart ……………………………………………………………………………………………. 3-5 Water Consumption Chart – ELXC Series …………………………………………………………………………….. 3-5 Number of Washes – Example ELXC Series with PCU ………………………………………………………….. 3-6 Number of Washes – Example CG3-SPC Series ……………………………………………………………………. 3-6 Number of Washes – Example CG3 with PCU ………………………………………………………………………. 3-6 Control Matrix – ELXC Series ……………………………………………………………………………………………….. 3-7 Control Matrix – CG3 Series ………………………………………………………………………………………………… 3-8 Name Plate – Command Center / Wash Control Cabinet …………………………………………………….. 3-9 Name Plate – ELXC Series Ventilator ……………………………………………………………………………………. 3-9

Chapter 4 – Maintenance

Maintenance – Wash Control Cabinet …………………………………………………………………………………. 4-1 Recommend Detergent ………………………………………………………………………………………………………. 4-2

Chapter 5 - Troubleshooting

Trouble Shooting – Wash System ……………………………………………………………………………………….. 5-1 Trouble Shooting – Backflow Preventer ………………………………………………………………………………. 5-2 Troubleshooting – C-7000 Command Center ………………………………………………………………………. 5-5

Chapter 6 – Testing and Repair

Wash Control Cabinet – Water Pressure …………………………………………………………………………….. 6-1 Wash Control Cabinet – Water Temperature ……………………………………………………………………… 6-1 Wash Control Cabinet – Detergent Pump …………………………………………………………………………… 6-2 Wash Control Cabinet – Detergent Flow Switch …………………………………………………………………. 6-8 Wash Control Cabinet – Line Strainer …………………………………………………………………………………. 6-9 Wash Control Cabinet – Backflow Preventer ………………………………………………………………………. 6-9

Chapter 7 - Parts

Parts – C-7000 Command Center ……………………………………………………………………………………….. 7-1

Parts – Wash Control Cabinet – Plumbing ………………………………………………………………………….. 7-2 Parts – Wash Control Cabinet – Detergent Pump ……………………………………………………………….. 7-3

_______________________________________

Page vii

Table of Contents

Chapter 8 – Wiring Diagrams

Wiring Diagrams …………………………………………………………………………………………………………………. 8-1 Terminal Schedules ……………………………………………………………………………………………………………… 8-11 PLC Inputs ……………………………………………………………………………………………………………………………. 8-12 PLC Outputs …………………………………………………………………………………………………………………………. 8-13 Fuse Schedule ………………………………………………………………………………………………………………………. 8-14

Appendix A

Installation Requirements …………………………………………………………………………………………………… A-1

Limited Warranty …………………………………………………………………………………………… Inside Back Cover

Page viii_________________________________________________________________________________

This Page Intentionally left Blank

Chapter 1: Introduction, Page 1-1

Introduction

About this Manual

The purpose of this manual is to provide the Operator, Owner, Maintenance and Service personnel instructions for operating, and programming the Gaylord Model GPC-7000 Series Command Center/Wash Control Cabinet. The Command Center controls various functions of Gaylord Ventilation Equipment as described on page 1-5. This manual also includes information and guidance to contractors for initial installation of the Command Center/Wash Control Cabinet.

The manual is divided into chapters for easy reference to a particular subject. The pages in the chapters are numbered with the chapter number, then a dash, and then the page number. So for example pages in Chapter 2 are numbered 2-1, 2-2, 2-3 etc. Figures and Tables are numbered in a similar manner. For example Figure 5-3-2 is on page 5-3 and is the second figure. Please keep your manual in a convenient location for so it can be accessed easily.

If you have any questions or concerns with the installation, operation, or service of your Gaylord Model GPC-7000 Command Center/ Wash Control Cabinet, please contact Gaylord Industries;

Web: www.gaylordusa.com

E-Mail: info@gaylordusa.com

Main Phone: 503-691-2010

Toll Free: 800-547-9696

Related Technical Manuals

1.ELXC and ELXC-UVi Series Ventilators are controlled by a Gaylord Command Center. The specific manual for this Ventilator Series is titled Operation and Maintenance Manual for the Gaylord

Model ELXC and ELXC-UVi Series Ventilators.

2.If the C-7000 Command Center is controlling a Model CG3, CG3-UV, CG3-SPC or CG3-UV-SPC Series Ventilator the specific manual for this Ventilator Series is titled Operation and Maintenance

Manual for the Gaylord Model CG3 Series Ventilators.

3.If the C-7000 Command Center is controlling a Pollution Control Unit, Model RSPC-ESP Series the specific manual for this Series is titled Operation and Maintenance Manual for the Gaylord Model

RSPC -ESP Series Pollution Control Unit.

Operation and Maintenance Manuals may be downloaded from the Gaylord website: www.gaylordusa.com or be obtained by calling Gaylord Industries.

Chapter 1: Introduction, Page 1-2____________________________________________________________

Introduction – Cont.

Application

The C-7000 Command Center controls the exhaust fan(s), supply fan(s), wash cycles, and fire modes for different series of Gaylord Ventilators and Pollution Control equipment. The C-7000 is the standard control for the ELXC and ELXC-UVi Series Ventilators and is a replacement control for previous Series of Gaylord Ventilators. Specifically the control is used for the following:

Ventilator Series

Standard for:

ELXC

ELXC-UVi Replacement for:

CG3

CG3-UV

CG3-SPC

CG3-UV-SPC

CG

CG-SPC

Pollution Control and Other Equipment

RSPC Series Pollution Control Equipment

GDS Series Duct Sump

Control Location

Typically the C-7000 Command Center is installed in a Gaylord Wash Control Cabinet, as shown on Figure 1- 2-1, but may be installed in a Gaylord UDS (Utility Distribution System) or may be remotely mounted, such as in a managers or maintenance personnel’s office.

C-7000 Command Center

Figure 1-2-1

Command Center/Wash Control Cabinet

Chapter 1: Introduction, Page 1-3

Introduction – Cont.

Model Number Sequence

The C-7000 Gaylord Command Center is typically installed in a Wash Control Cabinet as shown in Figure 1- 2-1. The model number for the Wash Control Cabinet is made up of an alphabetic prefix followed by a series of alphabetic and/or numeric suffixes to designate the type of control and various options. Sequence

of model numbers is as follows.

 

 

 

 

 

1. ____

2.______

3._______

4.________ 5.________ 6.________

7.________

8. ________

 

Prefix

Control

ESP

UVi

ED

#

#

Low

Gaylord

 

 

 

 

Total

Local

Detergent

Plumbing

 

 

 

 

Sequences

Solenoids

 

9. _ ____

10.______

11._______12.________ 13.________ 14.________ 15.________

Remote

Cold

Light

Trim

Security

Plumbing

220 Volts

Detergent

Water

Switch

Ring

Access

Loop

 

Pump

Mist

 

 

 

Size

 

Explanation of Pre-Fixes and Suffixes

1.GPC

GPC ………………….. Gaylord Plumbing Cabinet.

2.Control #

7000 …………………. Utilizes C-7000 Control.

3.ESP (If Applicable)

ESP …………………….Has inputs and outputs for Electrostatic Precipitator (ESP), typically used for PCU Model RSPC-ESP, and Ventilator Series CG3-UVi-SPC and CG-SPC Series.

4.UVi (If Applicable)

UVi …………………….Has inputs and outputs for Ultraviolet light control (UVi) [1U, 2U, 3U, 6U].

5.ED (If Applicable)

ED ……………………..Has inputs and outputs for Electric Damper Motors (GFBD, GEBD, fully-featured CG3, or fully-featured GX2) [15, 17, 18, 19, GX, GXT].

6.# Sequences (Total # Wash Solenoids Controlled)

S# ………………………Indicates Total Number of plumbing sequences (solenoids) indicated to wash at different times (Always indicate the Number of Sequences/solenoids controlled).

Ex) S1 = 1 Plumbing Sequence. S3 = 3 Plumbing Sequences.

7.# of Local Solenoids

L# ……………………… Indicates Number of plumbing sequences (solenoids) installed locally IN the GPC7000 Cabinet (Leave Blank if Zero Local Solenoids).

Examples: L1 = 1 Plumbing Solenoid located IN GPC-7000 Cabinet. L3 = 3 Plumbing Solenoid located IN GPC-7000 Cabinet.

Chapter 1: Introduction, Page 1-4____________________________________________________________

Introduction – Cont.

Model Number Sequence – cont.

Notes:

For 1.00" Loops with Zero Local Solenoids - All Plumbing Components are 0.75", with 1.00" Inlet and 1.00" Outlet.

For 1.00" Loops with 1 or more Local Solenoids - All Plumbing Components are 1.00".

Any other Size Loops with Local Solenoids - All Plumbing Components are the Size specified.

8.Low Detergent

LD …………………….. If cabinet has a Low Detergent Flow switch installed.

9.Remote Detergent Pump

RD ……………………..If control will control a Remote Detergent Pump.

10.Cold Water Mist

CM …………………… If cabinet has a Cold Water Mist plumbing loop installed.

11.Light Switch

LS ……………………… If cabinet has a Light Switch installed.

12.Trim Ring

TR …………………….. If cabinet has a Trim Ring installed.

13.Security Access

SA ………………………If cabinet has Security Access (Keyed Lift and Turn latch).

14.Plumbing Loop Size

1.00 ……………………Indicates Plumbing Loop Size (diameter of pipe to and from the cabinet) in inches.

15.220 Volts

220V ………………….Indicates that Control is designed to be connected to 220VAC Supply Voltage.

Model Number Examples:

GPC-7000-S4-LD-1.00

GPC-7000-ESP-UVi-ED-S4-L2-LD-CM-LS-TR-SA-1.25-220V

Sub Panel Model Number Example:

GPC-SUB-S3-LD-1.25

Model Number/Serial Number Nameplate

The exact Model Number and Serial Number of the GPC-7000 Wash Control Cabinet is stamped on the Wash Control Cabinet Nameplate. Refer to Figure 3-9-1 on Page 3-9 for a sample Nameplate.

Chapter 1: Introduction, Page 1-5

Introduction – Cont.

Functions and Features of the C-7000 Command Center

Control of Exhaust and Supply Fans

Manually Start and Stop fans by pushing the START FAN and STOP FAN buttons on the touch screen.

May be programmed to automatically Start and Stop fans at specific times each day.

If the Ventilator is equipped with Gaylord Autostart sensors, the Command Center will automatically start the fans if the temperature in the Ventilator canopy reaches 90°F.

The Command Center may be interfaced with a Building Management System (BMS) for remote Start and Stop of the fans.

Control of Wash Cycles

Controls the frequency of the Wash Cycle based on the Duty of the cooking equipment, Light Duty, Light/Medium Duty, Medium Duty, Heavy Duty, and Extra Heavy Duty, and the number of hours of fan operation. This function is factory pre-programmed.

The Length of each wash cycle may be programmed from 3 to 10 minutes.

May be programmed for a delay of 1 to 99 minutes between Wash Cycles. This may be necessary if the building’s hot water system is not capable of supplying the required volume of water at one given time.

Controls up to 16 Wash Cycles (Solenoid Valves), with each being able to be programmed for Duty of cooking equipment and length of Wash Cycle.

May be programmed for a Rise Cycle for equipment, such as an RSPC Pollution Control Unit, that requires a rinse.

Control of Fire Mode and Interface with Fire Extinguishing Systems

Controls opening and closing of optional electric balancing damper and optional fire dampers in ELXC and ELX Series Ventilators.

Controls opening and closing of fire damper in CG and CG3 Series Ventilators.

Includes dry contacts for interfacing Fire Extinguishing System with gas solenoid valve, reset relays, building fire alarm systems, and Building Management Systems (BMS).

Primary Screen Displays (when activated)

FAN ON ----- FAN OFF ------ DAMPER OPENING ------ DAMPER CLOSING ------ UV LAMPS ON

UV LAMPS OFF ------ EXTRACTOR WASH # X ON ------- PLENUM WASH # X ON

WASH OFF IN XXX SEC ------ UV SAFETY STANDBY ------ ONE OR MORE UV LAMPS FAILED

CALL FOR SERVICE ------ FIRE IN THE HOOD ------ FIRE SYSTEM ACTIVATED

CALL FIRE DEPARTMENT ------ NO DETERGENT ------ FILL DETERGENT ------ CHECK PUMP

FOR DETERGENT CALL 503-783-0924 ------ FAN AUTOSTARTED DUE TO HIGH TEMP IN HOOD

FOR NEAREST SERVICE AGENT VISIT WWW.GAYLORDUSA.COM OR CALL 503-691-2010

Chapter 1: Introduction, Page 1-6____________________________________________________________

Introduction – Cont.

Functions and Features of the C-7000 Command Center – Cont.

Options

Available to operate Detergent Pumps mounted remote from the Gaylord Wash Control Cabinet.

Built in light switch for Ventilator lights.

Trim ring to finish off space between Wash Control Cabinet and wall.

Keyed Lift and Turn Latches for Wash Control Cabinet Door.

220 volt system.

Programming

Easy to program Touch Screen buttons.

3 levels of access to program: 1) Operator, 2) Owner, 3) Gaylord Representative or Gaylord Certified Service Agency (CSA). Pass Code required for levels 2 and 3.

Figure 1-6-1

C-7000 Touch Screen Display

_

Chapter 2: Principle of Operation, Page 2-1

C-7000 Command Center

C-7000 Command Center

Overview

The Command Center is typically mounted in the Gaylord Wash Control Cabinet (Refer to Figure 1-2-1). The Command Center controls all functions of Gaylord Ventilators, and other Gaylord equipment as described in Chapter 1. Some programming may be required depending on the type of Gaylord equipment and automatic operations desired. All programming is accomplished by using the touch buttons on the display screen.

Access to Operate and Program

The Gaylord Command Center has three levels of access to obtain information, and to program various functions. They are:

Level 1 – Operator- This level does not require an access code. This level allows the operator to perform the following:

1.Manually start and stop the exhaust fan(s).

2.Access to a display that gives information on how to obtain Gaylord Service.

3.Access to a display that gives information on how to obtain FORMULA G-510LF Detergent for the Ventilator Wash Cycles.

Level 2 – Owner – This level requires a one digit access code, programmed by the owner, or appointed person, to access. At this level the Owner can access the following functions:

1.Program the Current Time and Day of Week.

2.Program the length of the Extractor and Plenum Wash Cycles for ELXC Series Ventilators.

3.Program the length of the Wash Cycle if the Command Center serves a Gaylord Duct Sump, a CG3 Series Ventilator, and/or a Gaylord Pollution Control Unit (RSPC-ESP Series).

4.Set the Equipment Duty for all Wash Cycles.

5.Program Automatic Start and Stop of the exhaust fan for specific times and days of the week if desired.

6.Set the Delay Time between Wash Cycles

7.If the Ventilator is equipped with UV Lamps, access data that shows total UV Lamp run hours.

8.If the Ventilator is equipped with a thermostatically activated Fire Damper, access data that shows the number of times the thermostat activated. This function is called an Internal Fire Mode.

9.If the Ventilator is equipped with a Fire Extinguishing System, access data that shows the number of times the Fire Extinguishing System has discharged.

10.If the Ventilator is Water Wash, access data that shows the number of times the system has washed and the total number of run time in minutes.

11.Access data that shows the total number of times the exhaust fan has started.

12.Access data that shows the total run hours of the exhaust fan.

13.Conduct a Plenum and Extractor Wash Cycle test.

Chapter 2: Principle of Operation, Page 2-2_____________________________________________________

C-7000 Command Center – Cont.

Access to Operate and Program – Cont.

Level 3 – Gaylord Certified Service Agent – This Level requires a 3 digit code only available to Gaylord Certified Service Agents or a Gaylord Authorized Representative. This Level also provides access to the password for Level 2. In Level 3 the following functions are programmed:

1.Program the Command Center to operate a Remote Detergent Pump.

2.Program the Command Center to operate either an ELXC or CG3 Series Ventilator.

3.Program the Command Center to operate a Gaylord Duct Sump.

4.Program the Command Center to operate an Electric Fire Damper or an Electric Balancing Damper.

5.Program the Command Center to operate UV Lamps.

6.Program the Command Center to operate a Pollution Control Unit (PCU, ESP Series).

7.Program the number of ESP Power Packs.

8.Program an Autostart Delay after a Ventilator Wash Cycle.

9.Turn on the Autostart function if the Ventilator is equipped.

Basic Touch Screen Button Functions

MENU

PREV

QUIT

NEXT

CHKSY

Pushing this button takes you to the next menu display.

Pushing this button takes you back to the previous display.

Pushing this button takes you back to the mode of operation the Command Center is currently in.

Pushing this button takes you to the next display.

Pushing this button takes you to a display the checks either the Status of a UV system And/or a Pollution Control Unit.

This is an enter button used to enter numbers.

ES

This is an Escape button that takes you back to the previous menu.

C

 

 

 

CL

This in a Clear button that clears the number just pushed to “0”.

R

 

 

 

B

This is a Backspace button that removes the last number touched.

S

 

Chapter 2: Principle of Operation, Page 2-3

C-7000 Command Center – Cont.

Level One Functions

Starting the Exhaust Fan - Manual Operation

Before the exhaust fan is started, and if the Ventilator does not contain UV Lamps, the display will read as shown in Figure 2-3-1. If the Ventilator includes UV Lamps, the display screen will read as shown in Figure 2-3-2. To start the exhaust fan push START FAN on the display screen. Both the exhaust fan and supply fan will start, and if the Ventilator does not include UV Lamps the display will read as shown in Figure 2-4-1 and if it does include UV Lamps the display will read as shown in Figure 2-4-2.

Note 1, Electric Dampers: The Ventilator may be equipped with a Gaylord Electric Balancing Damper, designated “GEBD” in the Ventilator model number or a Gaylord Fire/Balancing Damper designated “GFBD” in the model number. The Ventilator model number can be found on the Ventilator Nameplate (Refer to Page 3-9 for a sample of the Nameplate). If the Ventilator includes one of these dampers, when the START FAN button is pushed there is a 10 second delay before the exhaust fan starts to allow the damper to begin opening. The display will read as shown in Figure 2-4-3 with a countdown clock showing the number of seconds until the exhaust fan comes on. In Figure 2-4-3, the countdown clock is at 8 seconds. Once the exhaust fan comes on the display will read as shown in Figure 2-4-1 or 2-4-2. It takes approximately 45 seconds for the damper to move from the closed to open position and for the exhaust to come up to 100%.

Note 2, Autostart: Typically Ventilators installed in the United States are equipped with a Gaylord Autostart Controller that automatically turns on the exhaust fan if the temperature at the sensors mounted in the Ventilator canopy exceeds 90°F. If the fan was started by Autostart the display will read as shown in Figure 2-4-4. Once the temperature drops below 90°F., the fan will continue to run for 15 minutes and then automatically shut off and the display will read as shown in Figure 2-3-1. In some instances Ventilators installed outside the United States will include and Autostart Control. Inclusion of an Autostart Control is designated by the suffix “AS” or “DCA” in the Ventilator model number (Refer to Page 3-9 for a sample nameplate).

Figure 2-3-1

Figure 2-3-2

Chapter 2: Principle of Operation Page 2-4_____________________________________________________

C-7000 Command Center – Cont.

Starting the Exhaust Fan - Manual Operation – Cont.

Figure 2-4-1

Figure 2-4-2

Figure 2-4-3

Figure 2-4-4

Note 1, Detergent Monitoring: The Wash Control Cabinet has a Detergent Sensor that, during a Wash Cycle, if the Detergent Container is low or if the Detergent Pump is not operating properly, the COMMAND CENTER C-7000 display at the top of the screen, will flash alternately between COMMAND CENTER C-7000 and LOW DETERGENT as shown in Figures 2-4-5 and 2-4-6. This will continue, even after the Wash Cycle has finished, until the Detergent Container is filled and/or the Detergent Pump has been repaired and a Wash Cycle begins.

Figure 2-4-5

Figure 2-4-6

Chapter 2: Principle of Operation, Page 2-5

C-7000 Command Center – Cont.

Starting the Exhaust Fan - Manual Operation – Cont.

Note 1, CHKSYS Button (Check System): While the exhaust fan is on, at the bottom of the display as shown in Figure 2-4-1, the button in the center reads CHKSYS which stands for Check System. If a Ventilator includes a UV System, or if there is a PCU (Pollution Control Unit) on the system, pushing this button brings up screens that advises the status of the UV and PCU systems. Refer to Pages 2-12 and 2-14 for detailed information on the CHKSYS button.

Figure 2-5-1

Stopping the Exhaust Fan – Manual Operation

Before the exhaust fan is stopped, and if the Ventilator does not contain UV Lamps, the display will read as shown in Figure 2-5-2. If the Ventilator includes UV Lamps, the display screen will read as shown in Figure 2-5-3. To stop the exhaust fan push STOP FAN on the display screen. Both the exhaust fan and supply fan will stop, and if the Ventilator does not include UV Lamps the display will read as shown in Figure 2-6-1 and if the Ventilator includes UV Lamps, the display screen will read as shown in Figure 2-6-2.

Figure 2-5-2

Figure 2-5-3

Chapter 2: Principle of Operation Page 2-6_____________________________________________________

C-7000 Command Center – Cont.

Stopping the Exhaust Fan – Manual Operation – Cont.

Figure 2-6-1

Figure 2-6-2

Note 1, Autostart Controller: Typically Ventilators installed in the United States are equipped with a Gaylord Autostart Controller that automatically turns on the exhaust fan if the temperature at the sensors mounted in the canopy of the Ventilator exceeds 90°F. If the temperature was above 90°F., when the STOP FAN button was pushed the exhaust and supply fan will stay on and the display will read as shown in Figure 2-6-3. Once the temperature drops below 90°F., the fan will continue to run for 15 minutes and then automatically shut off and the display will read as shown in Figure 2-6-1 or Figure 2-6-2.

Figure 2-6-3

Figure 2-6-4

Note 2, Electric Dampers: The Ventilator may be equipped with a Gaylord Electric Balancing Damper, designated “GEBD” in the Ventilator model number or a Gaylord Fire/Balancing Damper designated “GFBD” in the model number. The Ventilator model number can be found on the Ventilator Nameplate (Refer to Page 3-9 for a sample of the Nameplate). If the Ventilator includes one of these dampers, when the STOP FAN button is pushed the exhaust fan will go off and damper will begin closing. The display will read as shown in Figure 2-6-4 with a countdown clock showing the number of seconds until the damper closes. In Figure the countdown clock is at 8 seconds. Once the damper closes the display as shown in Figure 2-6-3 will come up.

Chapter 2: Principle of Operation, Page 2-7

C-7000 Command Center – Cont.

Wash Cycle Notification and Monitoring

Overview

The Wash Cycles for the Ventilator Extractor, Ventilator Plenum, Pollution Control Unit (PCU), and Duct Sump are programmed to come on based on the Cooking Equipment Duty. The programmed Cooking Equipment Duty dictates the number of hours of fan operation before the Wash Cycle comes on. Refer to Table T-3-1-1, Typical Example of Frequency and Length of Wash Cycles, on Page 3-1 for typical application. Washing the Ventilator based on hours of operation for specific Cooking Equipment Duties provides the optimum in cleaning performance with the lowest possible water and detergent consumption.

Screen Display When in a Wash Cycle – ELXC Series Ventilator

The ELXC Ventilator has two Wash Cycles, the Plenum Wash and the Extractor Wash. The Plenum Wash only comes on when the exhaust fan is off and the Extractor Wash only comes on when the exhaust fan is on. A Wash Cycle sequence is as follows:

Plenum Wash

1.While the exhaust fan is off, and when the hours of fan operation have been satisfied, as programmed by the Cooking Equipment Duty, the Plenum Wash will start and the display as shown on Figure 2-7-1 will come up.

2.The countdown clock shows the number of seconds left before the Wash Cycle turns off. The example in Figure 2-7-1 shows that Plenum Wash 1 is on and that there are 14 seconds left in the Wash Cycle.

3.Upon completion of the Plenum Wash, and if there are no additional Plenum Washes (Plenum 2, 3, 4 etc) then the display as shown in Figure 2-7-2 will come up.

Figure 2-7-1 Figure 2-7-2

Important Note: The Plenum Wash may be stopped at any time by bushing the STOP WASH(S) as shown in Figure 2-7-1.

Chapter 2: Principle of Operation Page 2-8_____________________________________________________

C-7000 Command Center – Cont.

Wash Cycle Notification and Monitoring – Cont.

4.If there are additional Plenum Washes, and their fan operation hours have been satisfied the display as shown on Figure 2-8-1 will come up, and there is a delay before the next Plenum Wash Cycle begins.

5.The countdown clock shows the number of minutes left before the delay ends. The example in Figure 2-8-1 shows that Plenum Wash 2 Delay is on and that there are 4 seconds left in the Delay.

Figure 2-8-1

Figure 2-8-2

6.Upon completion of the Delay, Plenum Wash 2 will begin and the display as shown on Figure 2- 8-2 will come up. The example in Figure 2-8-2 shows that Plenum Wash 2 is on and there are 15 seconds until the wash ends.

7.Additional Plenum Washes, with a delay between each, would continue in the same sequence if the hours of fan operation have been satisfied.

8.Upon completion of all the Plenum Wash Cycles, the display as shown on Figure 2-7-2 will come up.

Plenum Wash for a Pollution Control Unit (PCU) Gaylord Model RSPC-ESP Series

When the Command Center is controlling a PCU, Gaylord Model RSPC-ESP Series, it is always programmed to wash as the last Plenum Wash. The Wash Cycle sequence for a PCU is as follows:

1.Wash 1

2.Delay 1

3.Wash 2

4.Delay 2

5.Rinse

6.Wash Cycle Off

Chapter 2: Principle of Operation, Page 2-9

C-7000 Command Center – Cont.

Wash Cycle Notification and Monitoring – Cont.

The following is a detailed sequence:

1.While the exhaust fan is off, and when the hours of fan operation have been satisfied as programmed by the Cooking Equipment Duty, the PCU Plenum Wash #1 (the last Plenum Wash) will start and the display as shown on Figure 2-9-1 will come up. In this example Plenum 3 has been programmed for the PCU Wash.

2.The countdown clock shows the number of seconds left before the Wash #1 turns off. The example in Figure 2-9-1 shows that Plenum Wash 3, Wash Cycle 1 is on and that there are 6 seconds left in Wash #1.

3.Upon completion of Wash #1 the display as shown on Figure 2-9-2 comes up. There is a delay, as programmed, before Wash #2 begins and the countdown clock shows the number of seconds left before the Delay #1 ends. The example in Figure 2-9-2 shows that Plenum Wash 3, Wash #1 Delay is on and that there are 4 seconds left in the Delay.

Figure 2-9-1

Figure 2-9-2

4.Upon completion of Delay #1, the display as shown in Figure 2-9-3 comes up and Plenum Wash 3, Wash #2 begins. The countdown clock shows the number of seconds left in Wash #2, in this example 16 seconds.

5.Upon completion of Wash #2 the display as shown on Figure 2-9-4 comes up. There is a delay, as programmed, before the Rinse Cycle begins and the countdown clock shows the number of seconds left before the Delay #2 ends, 5 seconds in this example.

Figure 2-9-3

Figure 2-9-4

Chapter 2: Principle of Operation, Page 2-10___________________________________________________

C-7000 Command Center – Cont.

Wash Cycle Notification and Monitoring – Cont.

6.Upon completion of Delay #2, the display as shown on Figure 2-10-1 comes and the Rinse Cycle begins and the countdown clock shows the number of seconds left before the Rinse Cycle ends.

7.Upon completion of the Rinse Cycle, if there are no additional PCU Plenum Washes (Plenum 2, 3, 4 etc) then the display as shown in Figure 2-10-2 will come up.

Figure 2-10-1 Figure 2-10-2

Important Note: The Plenum Wash may be stopped at any time by bushing the STOP WASH(S) as shown in Figure 2-10-1.

Extractor Wash

1.While the exhaust fan is on, and when the hours of fan operation have been satisfied as programmed by the Cooking Equipment Duty, the Extractor Wash will start and the display as shown on Figure 2-10-3 will come up.

2.The countdown clock shows the number of seconds left before the Wash Cycle turns off. The example in Figure 2-10-3 shows that Extractor Wash 1 is on and that there are 9 seconds left in the Wash Cycle.

3.Upon completion of the Extractor Wash, and if there are no additional Extractor Washes (Extractor 2, 3, 4 etc) then the display as shown in Figure 2-10-4 will come up.

Figure 2-10-3

Figure 2-10-4

Chapter 2: Principle of Operation, Page 2-11

C-7000 Command Center – Cont.

Wash Cycle Notification and Monitoring – Cont.

4.If there are additional Extractor Washes, and their fan operation hours have been satisfied, the display as shown on Figure 2-11-1 will come up, and there is a delay before the next Extractor Wash Cycle begins. The countdown clock shows the number of seconds left before the delay ends. The example in Figure 2-11-1 shows that Extractor Wash 1 Delay is on and that there are 4 seconds left in the Delay.

Figure 2-11-1

Figure 2-11-2

5.Upon completion of the Delay, the next Extractor Wash will begin and the display as shown on Figure 2-11-2 will come up. The example in Figure 2-11-2 shows that Extractor Wash 2 is on and it will shut off in 14 seconds.

6.Additional Extractor Washes, and if the hours of fan operation have been satisfied, would continue in the same sequence.

7.Upon completion of all the Extractor Wash Cycles, the display as shown on Figure 2-11-3 will come up.

Figure 2-11-3

Important Note: The Extractor Wash may be stopped at any time by bushing the STOP WASH(S) as shown in Figure 2-11-1.

Chapter 2: Principle of Operation, Page 2-12___________________________________________________

C-7000 Command Center – Cont.

UV System Monitoring

If the Ventilator includes UV Lamps the Command Center monitors the status of three Primary functions. They are:

1.UV System Operating Properly. While the exhaust fan is on, and if the UV system is operating properly the display will read as shown in Figure 2-12-1.

2.UV Lamp Operation. If one or more of the UV Lamps are not operating, the display will read as shown in Figure 2-12-2 with the exhaust fan on and Figure with the exhaust fan off. Refer to the Operation, Maintenance, and installation Manual for the ELXC and ELXC-UVi Series Ventilators for troubleshooting.

3.UV Safety Standby. If one of the UV Safety Interlocks activates the system goes into a UV Standby mode and the display will read as shown in Figure 2-12-3 with the exhaust fan on. The UV STANDBY text only displays while the exhaust fan in on, not while the exhaust fan is off. Refer to the Operation, Maintenance, and installation Manual for the ELXC and ELXC-UVi Series Ventilators for troubleshooting.

Figure 2-12-1

Figure 2-12-2

Figure 2-12-3

Chapter 2: Principle of Operation, Page 2-13

C-7000 Command Center – Cont.

UV System Monitoring – Cont.

The UV system may also be checked by using the Check System button. While the exhaust fan is on, at the bottom of the display as shown in Figure 2-13-1, the button in the center reads CHKSYS which stands for Check System. When this button is pushed, a display as shown in Figure 2-13-2 will come up. If the Command Center is not controlling an ESP (Pollution Control Unit), and if the Ventilator does contain UV Lamps, then the display will read as shown in Figure 2-13-2. If the Command Center is controlling an ESP and the Ventilator doe not includes UV Lamps, then the display will read as shown in Figure 2-14-2.

Figure 2-13-1

Figure 2-13-2

Figure 2-13-3

Chapter 2: Principle of Operation, Page 2-14___________________________________________________

C-7000 Command Center – Cont.

PCU (Pollution Control Unit) Monitoring

If the Ventilator includes a Pollution Control System, Gaylord SPC Series (Smoke Pollution Control) or if there is a PCU (Pollution Control Unit) Gaylord Model RSPC-ESP Series, remote from the Ventilator, the Command Center monitors the status of two basic functions 1) The status of the ESP Cell and Power Pack (Electro Static Precipitator), and 2) if the system uses chemical to control the odor, the system notifies of a Low Oder Control Chemical condition. To check the status, proceed as follows:

1.While the exhaust fan is on, at the bottom of the display as shown in Figure 2-14-1, the button in the center reads CHKSYS which stands for Check System. When this button is pushed, and if the system is operating properly, the display as shown in Figure 2-14-2 will come up. If there is a problem the display as shown in Figure 2-14-3 will come up.

Figure 2-14-1

Figure 2-14-2

Figure 2-14-3

Important Note: In reference to Figure 2-14-3, the text at the bottom left of the display indicates the status of the detergent for the Wash Cycle of the PCU. If the detergent pump is operating properly, and there is detergent in the Detergent Container, the text will read DET OK (Detergent OK) as shown in Figure 2-14-3. If the Detergent Pump is not operating properly and or there is no detergent in the Detergent Container, the text will read NO DET (No Detergent). In this case check the level of detergent in the Detergent Container and if full, refer to Page 6-2 for corrective action.

Chapter 2: Principle of Operation, Page 2-15

C-7000 Command Center – Cont.

PCU (Pollution Control Unit) Monitoring – Cont.

1.To check the detailed status, push the ESP CHECK STATUS button, as shown in Figure 2-14-3, and the display as shown in Figure 2-15-1 will come up if the system is operational or Figure 2-15-2 if there is a problem with the Cells or Power Pack. The “A” and the “B” squares indicate that there are two ESP Power Packs. Each Power Pack can serve up to 4 ESP Cells, so if there were 8 Cells there would be two lettered squares, as shown in Figures 2-15-1 and 2-15-2, 12 cells three lettered squares, and 16 Cells four lettered squares. If there are no problems with a Power Pack or associated Cells, the lettered squares will have a dark background as shown in Figure 2-15-1 and the text at the bottom will read ESP OK. If there is a problem with the ESP Cells or Power Pack(s), the display as shown in Figure 2-15-2 will come up and the text at the bottom will read ESP FAULT. In this example, the “A” Power Pack is operating properly and the “B” Power Pack has a problem.

2.If Spray Odor Control is used, and if the there is chemical in the tank, the display will include the text LOW ODOR CHEM OK as shown in Figures 2-15-2 and 2-15-2. If the chemical tank is empty, the display will include the text LOW ODOR CHEM LOW as shown in Figure 2-15-3.

Important Note: The recommended spray odor control chemical is Gaylord Formula GS-710 and is available from the same Gaylord Distributor that provides Formula G-510LF used for the Ventilator Wash system. See page 2-19 for ordering information.

Figure 2-15-1

Figure 2-15-2

Figure 2-15-3

Figure 2-15-4

3. Push the RTN button (Return) twice to return to the main screen as shown in Figure 2-15-4.

Chapter 2: Principle of Operation, Page 2-16___________________________________________________

C-7000 Command Center – Cont.

Fire Extinguishing System Monitoring (External Fire Mode)

If a Ventilator includes a Fire Extinguishing System, the Command Center interacts with the fire system and various building systems. This is referred to as an External Fire Mode. If the Fire Extinguishing System discharges, the Command Center reacts as follows:

1.The display as shown on Figure 2-16-1 comes up. This display will stay on until the fire system is reset.

2.The protected cooking equipment and possibly other cooking equipment will shut off.

3.If the Fire Extinguishing System is wired to a building fire alarm system the alarm will activate.

4.If the Fire Extinguishing System is wired to a building management system (BMS) it will notify of a fire condition.

5.If the Fire Extinguishing System is wired to the Gaylord Command Center the following will occur:

a)If the exhaust and supply fan were on the exhaust fan would stay on and the supply fan would shut off. It the exhaust and supply fans were off, the exhaust fan would come on and the supply fan would stay off.

b)If the Ventilator Wash Cycle was on it would shut off.

c)If the Ventilator is equipped with a Gaylord Electric Balancing Damper (model GEBD) or a Gaylord Fire/Balancing Damper (model GFBD) the damper will open.

d)If the Ventilator is equipped with UV Lamps the Lamps will shut off.

6.After discharge, the Fire Extinguishing System must be recharged and once recharged the display as shown on Figure 2-16-2 will come up. The exhaust fan can now be started and the cooking equipment can be turned back on.

Figure 2-16-1

Figure 2-16-2

Important Note: Refer to the Ventilator Control Matrix on Page 3-7 for information on all the interactions with the building systems when the Ventilator Internal Fire Mode is activated (Fire Extinguishing System discharge).

Loading...
+ 105 hidden pages