HIGH EFFICIENCY EXTRACTOR VENTILATOR
GENERAL SPECIFICATIONS AND DESCRIPTION
Furnish Gaylord Ventilator Model “ELX-UVi-___________” as shown on plans and in accordance with the following specications:
CAPTURE AND CONTAINMENT: Each ventilator shall achieve capture and containment using the lowest possible airow rates through “passive” versus “active” design features, thus eliminating the wiring or adjustment of internal motors, plenums or jets. The ventilator shall include an integrated capture wall to achieve its airow rates. The lowest possible airow rates shall be tested to ASTM 1704-09 by the Food Service Technology Center and published on their website for easy conrmation.
http://www.shnick.com/publications/appliancereports/hoods/
ELX
ITEM NO. _______________
SERIES
ULTRAVIOLET SYSTEM: The ventilator shall include ultraviolet lamps mounted in modules located in the plenum section. There shall be one or more UVi modules, as dictated by the ventilator length, and each module shall be on a slide track for easy removal. Access to the UVi modules shall be through tooled removable UV module doors. Two pressure switches shall be provided to monitor the airow and prevent operation of the UVi lamps if the access doors are open, or if any “XGS” Extractor is removed, or if the airow is inadequate. Mounted on the face of the plenum of each ventilator section shall be status lights to monitor “UVi System On”, “UVi Lamp Failure” and “UVi System Stand By.” The Gaylord Command Center shall display text that duplicates the ventilator mounted status lights. The lamps shall run for 13,000 hours before they drop below 80% out of UVC on average. The Ballast compartment shall have a high temperature shut o feature to protect the components from Fan failure or air blockage. Lamps shall have a double seal for extra protection from grease or water inltration. The electrical compartment shall have multiple fans for extra cooling increasing the longevity of the electrical components.
CONSTRUCTION: The ventilator shall be of all stainless steel construction, not less than 18 gauge, type 300 series. All exposed surfaces shall be a number 4 nish. The use of aluminized steel or galvanized steel is not acceptable. The ventilator shall include a static pressure port in each section to be used in balancing exhaust air volumes. Continuous front and rear mounting brackets shall be provided to facilitate mounting to the wall and hanging from the overhead building structure. Each duct collar shall include as standard a Gaylord Balancing Damper (GBD) with opposed blades that adjust manually through access from within the canopy. Ventilators built in end-to-end multiple sections shall have as standard “Continuous Capture” from one end to the other to ease cleaning and improve capture and containment.
LIGHT FIXTURES: The ventilator shall be equipped with:
Recessed LED 6 Watts/Ft. Min.
Recessed uorescent 12 Watts/Ft. Min.
100 watt surface mounted incandescent 24 Watts/Ft. Min.
150 watt recessed incandescent 36 Watts/Ft. Min.
ACCEPTANCE & APPROVALS: Each ventilator shall include an integral “Autostart” controller and sensors to meet current IMC standards (optional outside North America). Each ventilator shall include a built-in 1” air space at the rear that is Listed for reduced clearance to combustibles, and is NFPA-96 and IMC compliant when mounting against a combustible wall. Each ventilator shall be Listed to UL Standard 710, ETL Sanitation, comply with all requirements of NFPA-96, IMC, UMC, BOCA, and SBCCI mechanical codes and be capture tested to ASTM 1704-09 with High Eciency Extractors tested to ASTM 2519-2005.
APPLICATION
Wall mounted canopy for use over all types of equipment; ovens, broilers, griddles, fryers, ranges, steam equipment, etc.
DESIGN FEATURES
• Internal Canopy Radius
• Enhanced “XGS” Extractor Angle and Slot Spacing
• Faceted “Super Capture”™ Lip
• Integrated Capture Wall
OPTIONAL EQUIPMENT
1. Decorative Facings and Trim
2. Demand Control Ventilation
3. Fire Extinguishing Systems
4. Pollution Control Systems
5. Utility Distribution Systems
6. “XGS” Spark Arrestor Extractors
Light xtures shall be factory pre-wired to a single connection point. Ventilators built in multiple sections shall be furnished with coiled ex conduit for interconnecting sections.
GAYLORD INDUSTRIES
10900 SW AVERY ST • TUALATIN, OREGON 97062 U.S.A.
PHONE: 800.547.9696 • FAX: 503.692.6048 • email: info@gaylordusa.com
www.gaylordusa.com
ELX
30” STANDARD ALSO AVAILABLE 24” HIGH, OR WITH A 12” FRONT
*16’ -0” MAX. UNIT LENGTH. FOR GREATER LENGTH, JOIN TWO OR MORE SECTIONS TOGETHER. ALLOW 6” MIN. OVERHANG AT EACH END. IF CHARBROILER IS AT END, OVERHANG 12”
48” MINIMUM.
DIMENSION VARIES
WITH DEPTH OF THE
EQUIPMENT.
SERIES
LIGHT FIXTURE
CONTINUOUS
HANGING BRACKET
SUPERCAPTURE™ LIP
NOTE: 18” OVERHANG
REQUIRED OVER
UPRIGHT BROILER
6’-8”
MTG. HT.
12”
MIN.
10”
OR 12”
“AUTOSTART” SENSOR
GAYLORD BALANCING DAMPER (LISTED)
1” MINIMUM AIR SPACE (LISTED FOR REDUCED CLEARANCE TO COMBUSTIBLES)
“XGS” SUPER HIGH EFFICIENCY FILTRATION EXTRACTOR
0.5 GALLON GREASE DRAWER
CAPTURE WALL
OPTIONAL SIDE PANELS MAY BE USED TO ENHANCE CAPTURE PERFORMANCE
Mechanical Requirements
The amount of exhaust volume required is dependent upon the type of cooking equipment and the type and volume of cooking. Contact factory for exhaust volumes, duct sizes, and static pressures.
Electrical
o Provide 208-250VAC, 50/60 Hz, Single Phase, 20 amp service for every
2 ventilator sections to power UVi lamps. Ventilator lights to be on separate circuit, 120 volt 50/60Hz standard, 220/240 volt optional.
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials
Form No. ELX-UVi 0212-20195 © Copyright 2010, Gaylord Industries Litho USA
Ventilator Lengths
Maximum unit length 16’-0”. For greater lengths, join two or more sections together. Check to ensure that there is adequate access into building and kitchen area.
Note: Ventilators manufactured outside North America; maximum unit length
*
10’-0”.
Hanging Weight
Ventilator Width 48” 54” 60”
Ventilator Wt. / Lineal Ft. Lbs. 95 100 105
Capture Wall Wt. / Lineal Ft. Lbs. 20 20 20